background image

Form RGM 433-CV/LN, Mfg No. 177854 (Revision 1), Page 15

19. Check Installation & Start-up

Check the installation prior to start-up:

o

Check suspension. Unit must be secure and level.

o

Check clearances from combustibles. Requirements are shown in
Paragraph 7.

o

Check vent system to be sure that it is installed according to the
instructions in Paragraph 11.

o

Check piping for leaks and proper gas line pressure. Bleed gas lines
of trapped air. See Paragraph 12.

o

Check electrical wiring. Be sure all wire gauges are as recommended.
A service disconnect switch should be used. Verify that fusing or
circuit breakers are adequate for the load use.

Heater Start-Up:

WARNINGS: For your safety, read before
operating. If you do not follow these instructions
exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.

• This appliance does not have a pilot. It is

equipped with an ignition device which auto-
matically lights the burner. Do not try to light
the burner by hand.

• Before operating, smell all around the appli-

ance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and
will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any

phone in your building.

• Immediately call your gas supplier from a

neighbor's phone. Follow the gas supplier's in-
structions.

• If you cannot reach your gas supplier, call your

fire department.

• Use only your hand to turn the gas control ON/

OFF knob on the gas valve. Never use tools. If
the valve ON/OFF  knob will not turn by hand,
do not try to repair it. Call a qualified service
technician. Force or attempted repair may re-
sult in a fire or explosion.

• Should overheating occur, or the gas supply fail

to shut off, turn off the manual gas valve to the
appliance before shutting off the electrical sup-
ply.

• Do not use this appliance if any part has been

under water. Immediately call a qualified ser-

18. Burners

This unit heater has inshot burners designed to provide controlled flame
stability without lifting or flashback with either natural or propane gas.
The burners are lightweight and factory mounted in an assembly which
permits them to be removed as a unit for inspection or service.

vice technician to inspect the appliance and to
replace any part of the control system and any
gas control which has been under water.

Operating Instructions and Operating
Sequence

1. Set thermostat at lowest setting.
2. Turn off all electric power to the appliance.
3. This appliance is equipped with an ignition device which automati-

cally lights the burner. Do not try to light the burner by hand. Open
the access door and locate the gas control (ON/OFF) knob on the
gas valve. (See Figure 9.)

4. Turn the gas control knob clockwise 

C

C

C

C

C

 to "OFF".

5. Wait five (5) minutes to clear out any gas. Then smell for gas, in-

cluding near the floor. If you smell gas, STOP! and follow the
steps in the WARNINGS printed on the left or on the Operating
Label on the heater. If you do not smell gas, proceed to the next
step.

6. Turn the gas control knob counterclockwise 

to "ON".

7. Close the access door.
8. Turn on the electric power to the heater.
9. Set the thermostat to the desired setting.
NOTE: If the appliance does not operate, follow the instructions "To
Turn Off Gas to Appliance" printed below (and on the Operating Label
on the heater) and call your service technician.
10. Thermostat calls for heat, energizing the venter motor.
11. Venter pressure switch closes, firing the unit.
12. Burner flame is sensed and in 30 seconds, the fan motor is ener-

gized.

13. If the flame is extinguished during the main burner operation, the

integrated control system closes the main valve and must be reset
by interrupting power to the control circuit. (See lighting instruc-
tions on the heater.).

TO TURN OFF GAS TO THE APPLIANCE

1) Set thermostat to lowest setting
2) If service is to be performed, turn off all electric power to the

appliance.

3) Open the access door.
4) Turn the gas control knob clockwise 

C

C

C

C

C

 to "OFF". Do not force.

5) Close the access door.

Check installation after start-up:

o

 

Vent System Testing Procedure

1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as

required in the National Fuel Gas Code, ANSI Z223.1 or CAN/

Gas

Flow

Gas Control

Knob (shown

in the ON

position)

Figure 9 -
Gas Valve

Содержание FT30-CV

Страница 1: ...ath Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment HAZARD INTENSITY LEVELS 1 DANGER Failure to comply will result in severe perso...

Страница 2: ...and movable scaffold ing In addition the heaters must be located so as to be accessible for servicing adjustment etc 2 Warranty Refer to the limited warranty information on the Warranty Card in the O...

Страница 3: ...and 45 inches mm Top 1 25 Flue Connector 6 152 Access Panel 18 457 Non Access Side 1 25 Bottom 1 25 Rear 18 457 Units must be installed so that the clearances in the table are provided for combustion...

Страница 4: ...ll the assem bly so that the louvers will direct the air downward with the heater in its new position 3 Turn the access panel so that the labels are in an upright position Re attach the panel 10 Suspe...

Страница 5: ...n venting Common Venting Terms and Requirements Common vents must be vertical The common vertical portion may be either a Type B double wall vent a masonry chimney lined with a Type B or listed liner...

Страница 6: ...horizontal length is 6 ft 1 8M Vent Connector of another Category I appliance H R1 R2 Category I Appliance water heater Model FT CV or LN Model FT CV or LN Maximum Length of the Vent Connector of Oth...

Страница 7: ...103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257...

Страница 8: ...8 257 299 203 320 398 265 391 511 339 528 637 413 1 N A N A 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 N A N A 34 83 94 62 121 150 97 185 230 138 246 314 189...

Страница 9: ...776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 9...

Страница 10: ...N A N A 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1090 466 610 1386 597 1 N A N A 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1181 444 560 1537 580 2 N A N A...

Страница 11: ...in Do not rely on the heater for support of either horizontal or vertical vent pipe n Vent Terminal The vent terminal should be a minimum of six feet from adjoining buildings The vent terminal should...

Страница 12: ...40 24 84 51 160 98 320 195 490 299 930 567 100 38 23 79 48 150 92 305 186 460 281 870 531 125 34 21 72 44 130 79 275 168 410 250 780 476 150 31 19 64 39 120 73 250 153 380 232 710 433 175 28 17 59 36...

Страница 13: ...fan motor remains energized for an additional 180 seconds NOTE This is a three trial system should the unit not sense burner flame the unit will lockout for one hour before initiating another trial f...

Страница 14: ...CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS ARE FI...

Страница 15: ...r natural or propane gas The burners are lightweight and factory mounted in an assembly which permits them to be removed as a unit for inspection or service vice technician to inspect the appliance an...

Страница 16: ...r as practical close all building doors and windows and all doors between the space where the heater is and other spaces of the building Turn on clothes dryers and exhaust fans such as range hoods and...

Страница 17: ...urner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a fire explo sion hazard To prevent fuel gas spillin...

Страница 18: ...a year Inspection should in clude all joints seams and the vent cap Replace any defective parts Flame Sensor Refer to Figure 10 and locate the flame sensor Dis connect the wire remove the screw and th...

Страница 19: ...control at the thermostat or main power 6 Faulty combustion air proving switch 6 Replace combustion air proving switch 7 Main valve not operating 7 a Defective valve a If 24 volt is measured at the v...

Страница 20: ..._______________________________________________________ __________________________________________________________________ __________________________________________________________________ Phone ____...

Отзывы: