background image

Form 433-CV/LN, Page 18

the original fan guard. These specially designed screws will cut
through the coating on the fan guard to provide a ground for the fan
motor.)
Rotate the fan blade to check for adequate clearance. If adjustment
is required, loosen the mounting screws, re-position the fan guard,
and tighten the screws. Rotate the fan blade and re-check for ad-
equate clearance. Repeat this procedure until the assembly is posi-
tioned properly.

5. Reconnect the fan motor wires and replace the access panel.

6. Restore power to the heater and turn on the gas. Light, following

the instructions on the lighting instruction plate. Check for proper
operation.

25. Venter Motor

Remove dirt and grease from the motor housing. Venter motor is
permanently lubricated.
The integrated circuit board controls and monitors operation of the
venter motor. If the contacts fail to close the venter motor will not
run. If the contacts fail to open, the venter motor will not shut off,
preventing the combustion air pressure switch from opening.

26. Operating Gas Valve

The gas valve requires no field maintenance except careful removal
of external dirt accumulation and checking of wiring connections.
Instructions for testing pressure settings are in Paragraph 12.

WARNING: The operating valve is the prime
safety shutoff. All gas supply lines must be free
of dirt or scale before connecting to the unit to
ensure positive closure. See Hazard Levels, page
1.

27. Limit Control

I

f it is determined that the limit control needs replacing, use only a

factory-authorized replacement part that is designed for the size of
heater. To access the limit control, remove the louver assembly from
the front of the heater.
For approximate limit location, see Figure 11.

28. Combustion Air Pressure

Switch

See Figure 12 for location. If it is determined that the pressure switch
needs replacing, use only the factory-authorized replacement part
that is designed for the size of heater being serviced.

29. Flame Rollout Switch

Models FT 30 and 45 are equipped with a flame rollout safety switch.
The flame rollout switch is a temperature activated manually reset,
limit switch. The switch is mounted on the side of the burner box
in a location that senses temperature in a central horizontal loca-
tion at the rear of the burner assembly.
If the flame rollout switch activates to shutdown the heater, the
cause must be corrected.
If it is determined that the flame rollout switch needs replacing,
use only the factory-authorized replacement part that is designed
for use on this heater.

30. Vent System

Check the vent system at least once a year. Inspection should in-
clude all joints, seams, and the vent cap. Replace any defective
parts.

Flame Sensor - Refer to Figure 10 and locate the flame sensor. Dis-
connect the wire; remove the screw and the flame sensor. Clean with
an emery cloth.

Ignition Control - The integrated circuit board monitors the operation
of the heater including ignition. Do not attempt to disassemble the cir-
cuit board. However, each heating season the lead wires should be
checked for insulation deterioration and good connections.
Proper operation of the direct spark ignition system requires a mini-
mum flame signal of 1.0 microamps as measured by a
microampmeter.
For further information and check out procedure on the direct spark
ignition system, refer to the manufacturer's control operating instruc-
tions supplied with the heater.

23. Heat Exchanger

The outside of the tubular heat exchanger can be cleaned from the
front of the heater with an air hose and/or a brush. Remove all accumu-
lated dust and grease deposits.

CAUTION: Eye protection is recommended.

The inner surfaces of the heat exchanger can be reached for cleaning
with the burner and venter assemblies removed (See Paragraph 21).
Clean with a long furnace brush or a heavy wire to which steel wool
has been attached. Brush inside each heat exchanger tube until all for-
eign material is removed. A flashlight is helpful in examining the in-
side of the tubes.

24. Fan

Remove dirt and grease from the motor. Remove dirt and grease from
the fan guard and blades. Use care when cleaning the fan blades to
prevent causing misalignment or imbalance. Check that the hub of the
fan blades is secure to the shaft.

Follow these instructions for replacement of the fan guard, fan motor
and/or fan blades.

1. If the heater is installed, turn off the gas and disconnect the electric

power.

2. Remove the access panel or 2x4 junction box cover. Disconnect the

fan motor wires.

3. Remove the assembled parts (the fan guard, the motor and the fan

blade).

4. Disassemble and replace whatever parts are needed and reassemble

using whatever part(s) are being replaced and the original parts. If
the fan guard is being replaced, it is important that the same hard-
ware be used for attaching the motor to the fan guard as was used
with the original guard. These screws are especially made to cut
through the coating on the fan guard to provide adequate ground-
ing for the motor.

Be sure the fan blade is in the proper position on the shaft; refer to
the illustration and table in Figure 12.

Position the assembly on the heater. Attach the fan guard.
(IMPORTANT: If replacing the fan guard, use the screws that held

Figure 12 - Proper

Position of the Fan

Blade on the

Motor Shaft

Model 

S iz e

S et  S crew 

Torque 

(Inch-Lbs)

 "A" Hub 

to Motor

30, 45

80 ± 10

1-1/8"

Fan
Hub

A

Fan

22. Ignition System (cont'd)

Содержание FT30-CV

Страница 1: ...ath Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment HAZARD INTENSITY LEVELS 1 DANGER Failure to comply will result in severe perso...

Страница 2: ...and movable scaffold ing In addition the heaters must be located so as to be accessible for servicing adjustment etc 2 Warranty Refer to the limited warranty information on the Warranty Card in the O...

Страница 3: ...and 45 inches mm Top 1 25 Flue Connector 6 152 Access Panel 18 457 Non Access Side 1 25 Bottom 1 25 Rear 18 457 Units must be installed so that the clearances in the table are provided for combustion...

Страница 4: ...ll the assem bly so that the louvers will direct the air downward with the heater in its new position 3 Turn the access panel so that the labels are in an upright position Re attach the panel 10 Suspe...

Страница 5: ...n venting Common Venting Terms and Requirements Common vents must be vertical The common vertical portion may be either a Type B double wall vent a masonry chimney lined with a Type B or listed liner...

Страница 6: ...horizontal length is 6 ft 1 8M Vent Connector of another Category I appliance H R1 R2 Category I Appliance water heater Model FT CV or LN Model FT CV or LN Maximum Length of the Vent Connector of Oth...

Страница 7: ...103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257...

Страница 8: ...8 257 299 203 320 398 265 391 511 339 528 637 413 1 N A N A 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 N A N A 34 83 94 62 121 150 97 185 230 138 246 314 189...

Страница 9: ...776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 9...

Страница 10: ...N A N A 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1090 466 610 1386 597 1 N A N A 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1181 444 560 1537 580 2 N A N A...

Страница 11: ...in Do not rely on the heater for support of either horizontal or vertical vent pipe n Vent Terminal The vent terminal should be a minimum of six feet from adjoining buildings The vent terminal should...

Страница 12: ...40 24 84 51 160 98 320 195 490 299 930 567 100 38 23 79 48 150 92 305 186 460 281 870 531 125 34 21 72 44 130 79 275 168 410 250 780 476 150 31 19 64 39 120 73 250 153 380 232 710 433 175 28 17 59 36...

Страница 13: ...fan motor remains energized for an additional 180 seconds NOTE This is a three trial system should the unit not sense burner flame the unit will lockout for one hour before initiating another trial f...

Страница 14: ...CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS ARE FI...

Страница 15: ...r natural or propane gas The burners are lightweight and factory mounted in an assembly which permits them to be removed as a unit for inspection or service vice technician to inspect the appliance an...

Страница 16: ...r as practical close all building doors and windows and all doors between the space where the heater is and other spaces of the building Turn on clothes dryers and exhaust fans such as range hoods and...

Страница 17: ...urner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a fire explo sion hazard To prevent fuel gas spillin...

Страница 18: ...a year Inspection should in clude all joints seams and the vent cap Replace any defective parts Flame Sensor Refer to Figure 10 and locate the flame sensor Dis connect the wire remove the screw and th...

Страница 19: ...control at the thermostat or main power 6 Faulty combustion air proving switch 6 Replace combustion air proving switch 7 Main valve not operating 7 a Defective valve a If 24 volt is measured at the v...

Страница 20: ..._______________________________________________________ __________________________________________________________________ __________________________________________________________________ Phone ____...

Отзывы: