background image

Form RGM 433-CV/LN, Mfg No. 177854 (Revision 1), Page 17

NOTE: If the heater has been changed so that the controls are on the left side (Paragraph 9), their locations will
appear inverted.

Pressure

Switch

Flue

Collar

Flame Sensor

Transformer

Limit Control Location (located in

the heat exchanger compartment;

remove louvers to access)

Venter Motor

and Wheel Assy

Fan

Motor

Gas

Valve

Pressure Tap (for tubing

connection to the pressure switch)

Circuit Board (See LED

Codes on page 14 or 19.)

Ignitor

Burner/Manifold

Assembly

Flame

Rollout

Switch

Figure 10 - Location of Controls - View of

the Control Compartment

20. Burner Removal and

Cleaning

Instructions for Burner Removal (See Figure 10)

1. Shut the gas supply off ahead of the combination valve.

2. Turn off electric supply.

3. Remove the access panel; the vertical burner assembly is visible on

the left side of the heater.

4. Open the union in the gas line before the gas valve.

5. Disconnect the flame sensor wire and the ignitor wire.

6. Remove the screws that attach the burner assembly to the front panel

and inner wall. Pull the manifold/burner assembly out of the heater.

Clean the Burners (requires a wire brush,
cleaning cloth, and an automotive type aerosol
degreaser or refrigerant coil cleaner)

CAUTION: Use of eye protection is recommended.

Excessive dirt buildup on and inside the ports on the burner could
cause fuel gas to spill out of the back of the burner tube. Fuel gas
spilling out of the back of the burner tube will cause gas odor inside
the building, and if not corrected, could eventually cause a fire/explo-
sion hazard. To prevent fuel gas spilling from the back of the burners,
clean the burner ports at least annually. Remove any soot deposits from
the burner with a wire brush. Clean the ports with an aerosol degreaser
and/or compressed air. Wipe the inside of the burner tube clean. (Clean-
ing the burner with an aerosol degreaser is highly recommended as the
degreaser will retard future buildup of dirt.)
Inspect the cleaned burner for any damage or deterioration. If the burner
has any damage or signs of deterioration, replace it.
Re-assemble the heater and test for proper operation.

21. Burner Orifices

Heaters are shipped with orifices of proper size and type for gas and
altitude specified on the order. When ordering replacement orifices,
give BTUH content, specific gravity of gas, and altitude, as well as the
model and serial number of the heater.

22. Ignition System

To access the ignition system, follow Steps 1-3 in Paragraph 20.
Ignitor - Refer to Figure 10 and locate the ignitor (on the side of the
burner rack). Disconnect the wire; remove the screw and the ignitor.
Clean the ignitor assembly with an emery cloth.
Spark gap must be maintained to 1/8". See Figure 11.

Figure 11 - Ignitor

Assembly

Front View
showing Spark
Gap Measurement

IMPORTANT: When re-assembling, the brown ground wire must re-
main attached to the ignitor.

CAUTION: Due to high voltage on the spark wire
and electrode, do not touch when energized. See
Hazard Levels, page 1.

Содержание FT30-CV

Страница 1: ...ath Read the installation operation and maintenance instructions thoroughly before installing or servicing this equipment HAZARD INTENSITY LEVELS 1 DANGER Failure to comply will result in severe perso...

Страница 2: ...and movable scaffold ing In addition the heaters must be located so as to be accessible for servicing adjustment etc 2 Warranty Refer to the limited warranty information on the Warranty Card in the O...

Страница 3: ...and 45 inches mm Top 1 25 Flue Connector 6 152 Access Panel 18 457 Non Access Side 1 25 Bottom 1 25 Rear 18 457 Units must be installed so that the clearances in the table are provided for combustion...

Страница 4: ...ll the assem bly so that the louvers will direct the air downward with the heater in its new position 3 Turn the access panel so that the labels are in an upright position Re attach the panel 10 Suspe...

Страница 5: ...n venting Common Venting Terms and Requirements Common vents must be vertical The common vertical portion may be either a Type B double wall vent a masonry chimney lined with a Type B or listed liner...

Страница 6: ...horizontal length is 6 ft 1 8M Vent Connector of another Category I appliance H R1 R2 Category I Appliance water heater Model FT CV or LN Model FT CV or LN Maximum Length of the Vent Connector of Oth...

Страница 7: ...103 356 230 121 454 294 141 564 358 3 24 47 36 37 87 64 53 139 101 67 210 145 88 290 198 105 384 258 123 492 330 143 612 402 1 22 43 28 34 78 50 49 123 78 65 189 113 89 257 154 106 341 200 125 436 257...

Страница 8: ...8 257 299 203 320 398 265 391 511 339 528 637 413 1 N A N A 29 79 87 52 116 138 81 177 214 116 238 291 158 312 380 208 397 482 266 556 596 324 2 N A N A 34 83 94 62 121 150 97 185 230 138 246 314 189...

Страница 9: ...776 394 3 27 52 34 42 97 62 59 159 98 75 269 145 99 383 206 119 517 276 139 672 358 163 848 452 1 24 42 22 38 80 42 55 130 71 74 232 108 101 324 153 120 444 216 142 582 277 165 739 348 2 26 50 29 40 9...

Страница 10: ...N A N A 35 94 131 68 136 231 112 205 422 176 271 607 255 349 831 351 440 1090 466 610 1386 597 1 N A N A 23 84 104 49 122 200 89 182 410 151 243 617 232 315 875 328 402 1181 444 560 1537 580 2 N A N A...

Страница 11: ...in Do not rely on the heater for support of either horizontal or vertical vent pipe n Vent Terminal The vent terminal should be a minimum of six feet from adjoining buildings The vent terminal should...

Страница 12: ...40 24 84 51 160 98 320 195 490 299 930 567 100 38 23 79 48 150 92 305 186 460 281 870 531 125 34 21 72 44 130 79 275 168 410 250 780 476 150 31 19 64 39 120 73 250 153 380 232 710 433 175 28 17 59 36...

Страница 13: ...fan motor remains energized for an additional 180 seconds NOTE This is a three trial system should the unit not sense burner flame the unit will lockout for one hour before initiating another trial f...

Страница 14: ...CIRCUIT TO HIGH LIMIT OR FLAME ROLLOUT TERMINAL 5 FLASHES FLAME SENSED AND GAS VALVE NOT ENERGIZED STEADY ON INTERNAL FAILURE MICRO CONTROLLER FAILURE SELF CHECK NOTES 1 THE FOLLOWING CONTROLS ARE FI...

Страница 15: ...r natural or propane gas The burners are lightweight and factory mounted in an assembly which permits them to be removed as a unit for inspection or service vice technician to inspect the appliance an...

Страница 16: ...r as practical close all building doors and windows and all doors between the space where the heater is and other spaces of the building Turn on clothes dryers and exhaust fans such as range hoods and...

Страница 17: ...urner tube Fuel gas spilling out of the back of the burner tube will cause gas odor inside the building and if not corrected could eventually cause a fire explo sion hazard To prevent fuel gas spillin...

Страница 18: ...a year Inspection should in clude all joints seams and the vent cap Replace any defective parts Flame Sensor Refer to Figure 10 and locate the flame sensor Dis connect the wire remove the screw and th...

Страница 19: ...control at the thermostat or main power 6 Faulty combustion air proving switch 6 Replace combustion air proving switch 7 Main valve not operating 7 a Defective valve a If 24 volt is measured at the v...

Страница 20: ..._______________________________________________________ __________________________________________________________________ __________________________________________________________________ Phone ____...

Отзывы: