background image

Form I-XE/CRGB/RPB, Mfg No. 131782 Rev 4, Page 7

5. Clearances

Provide clearance to combustibles as shown in the table. Clearance to
combustibles is defined as the minimum distance from the heater to a
surface or object that is necessary to ensure that a surface temperature
of 90°F above the surrounding ambient temperature is not exceeded.
Clearance is also required to sides of furnace for combustion air space
and for convenient installation and burner control system service.

6. Combustion Air Requirements

6A. Indoor, Gravity-Vented Models XE/HXE

These furnaces are designed to take combustion air from the space in
which the furnace is installed. The air that enters into the combustion
process is vented to the outdoors. Sufficient air must enter the equip-
ment location to replace the air exhausted through the vent system.
Modern construction methods involve the greater use of insulation,
improved vapor barriers and weather-stripping, with the result that
buildings generally are much tighter structurally than they have been in
the past. The combustion air supply for gas-fired equipment can be
affected by these construction conditions because infiltration that would
have existed in the past may not be adequate. Extensive use of exhaust
fans aggravates the situation. In the past the filtration of outside air
assumed in heat loss calculations (one air change per hour) was assumed
to be sufficient. However, current construction methods may now re-
quire the introduction of outside air through wall openings or ducts.
Requirements for combustion air and ventilation air depend upon whether
the unit is located in a confined or unconfined space. An "unconfined
space" is defined as a space whose volume is not less than 50 cubic feet
per 1000 BTUH of the installed appliance. Under all conditions, enough
air must be provided to ensure there will not be a negative pressure
condition within the equipment room or space. A positive seal must be
made in all return-air connections and ducts. Even a slight leak can create
a negative pressure condition in a confined space and affect combustion.

WARNING: These gravity-vented, indoor furnaces
are designed to take combustion air from the space
in which the furnace is installed and are not designed
for connection to outside combustion air intake
ducts. Use of outside air ducts voids the warranty
and could cause hazardous operation. See Hazard
Levels, page 2.

Indoor, Gravity-Vented Furnace Located in a
Confined Space

Do not

 install a unit in a confined space without providing wall open-

ings leading to and from the space. Provide openings near the floor and
ceiling for ventilation and air for combustion as shown in 

FIGURE 2

,

depending on the combustion air source as noted in Items 1, 2 and 3.

Add total BTUH of all appliances in the confined space and divide by
figures below for square inch free area size of each (top and bottom)
opening.

1. Air from inside the building

 - openings 1 square inch free area per

1000 BTUH. Never less than 100 square inches free area for each open-
ing. See (1) in 

FIGURE 2

.

2. Air from outside through duct

 - openings 1 square inch free area per

2000 BTUH. See (2) in 

FIGURE 2

.

3. Air direct from outside

 - openings 1 square inch free area per 4000

BTUH. See (3) in 

FIGURE 2

.

NOTE:

 For further details on supplying combustion air to confined

space, see National Fuel Gas Code ANSI Z223.1a (latest edition) 5.3.3.

6B. Combustion Air for Gravity-Vented,

Outdoor Model Series CRGB

Combustion air enters through the screened air intakes located in the
furnace section access doors.

6C. Combustion Air for Power-Vented,

Outdoor Model
Series RPB

The combustion air and flue gas
openings are carefully designed
screened openings located on the
side of the unit just above the con-
trol access panel. Location of the
flue opening directly above the air
intake is designed to discourage re-
circulation of combustion prod-
ucts. See 

FIGURE 3.

6D. Chlorine - All Models

The presence of chlorine vapors in the combustion air of gas-fired heat-
ing equipment presents a potential corrosion hazard. Chlorine will,
when exposed to flame, precipitate from the compound, usually freon
or degreaser vapors, and go into solution with any condensation that is
present in the heat exchanger or associated parts. The result is hydro-
chloric acid which readily attacks all metals including 300 grade stainless
steel.
Care should be taken to separate these vapors from the combustion
process. This may be done by wise location of the furnace with regard
to exhausters or prevailing wind direction. Remember, chlorine is heavier
than air. This fact should be kept in mind when determining installation
locations of heating equipment and building exhaust systems.

7. Suspending/Mounting

7A. Suspending/Mounting Indoor, Gravity-

Vented Models XE/HXE

Location

 - Before suspending the furnace, check the supporting struc-

ture to verify that it has sufficient load-carrying capacity to support the
weight of the unit.

Approximate Net Weight - Indoor Furnaces

S i z e

75-100

125

150-175

200-225

250-300 350

400

lbs

233

295

332

386

494

515

576

kg

106

134

151

175

224

234

261

WARNING: Avoid installing a unit in an extremely
drafty area. Extreme drafts can shorten the life of
the heat exchanger and/or cause safety problems.

FIGURE 2 -
Confined Space: A
space whose volume
is less than 50
cubic feet per 1000
BTUH of the
installed appliance
input rating

Confined

Space

(1)

(1)

(2)

(2)

(3)

(3)

Flue Products

Outlet

Combustion

Air Inlet

FIGURE 3 - Combustion Air
Intake, Power-Vented
Models

REQUIRED CLEARANCES

Sides

Bottom

Model S eries

Top

Control

Opp osite

To 

Combustibles

To Non-

Combustibles

(H)XE

6" 

(152mm)

6" 

(152mm)

3" (76mm)

0

(H)RPB, 

(H)CRGB

36" 

(915mm)

6" 

(152mm)

0  *

0

(H)CRGB

30' (9M) radius from center of vent cap to obstructions 
such as walls, parapets or cupolas

Width of 

furnace 
p lus 6" 

(152mm) 

* When installed on a roof curb on a combustible roof, the roof area enclosed 
within the curb must be either ventilated, left op en, or covered with non-
combustible material which has an "R" value  at least 5.0. See 

FIGURE 8

, page 10.

Содержание CRGB Series

Страница 1: ...AquaSaver Timer Adjustment 34 Belts 24 Blocked Vent Switch 25 Blower Motors 24 Blower Rotation 24 Burner Air Adjustment 30 Burner Rack Removal 42 Burners 29 Carryover System 29 Check Installation and...

Страница 2: ...rhalogenatedhydrocarbonsorany contaminant silicone aluminium oxide etc that adheres to the spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c...

Страница 3: ...x 19 1 2 495mm Return Air Openings with Optional Cabinet X Hanger Centerline Standard and Optional Blower Cabinet Dimensions inches andmm Gravity Vented Indoor Models XE HXE Gas Connection Natural Pr...

Страница 4: ...side the downturn plenum cabinet For dimensions with downturn plenum cabinet with a cooling coil cabinet see page 6 FIGURE1B Dimensions Outdoor Gravity VentedModel Series CRGB Vent Cap Gas Connection...

Страница 5: ...ottom of cabinet side If system has a cooling coil cabinet add length dimension on page 6 for full system length The two position discharge dampers in Option AQ8 fit in the discharge air opening The d...

Страница 6: ...ownturnPlenumCabinet factoryattachedto either type of Cooling Coil Cabinet Front View DX Coil Cabinet with Horizontal Discharge Option AU3 Liquid Line Connections 7 8 or 1 3 8 5 1 8 130 8 203 3 4 19 3...

Страница 7: ...r from inside the building openings 1 square inch free area per 1000 BTUH Never less than 100 square inches free area for each open ing See 1 in FIGURE 2 2 Air from outside through duct openings 1 squ...

Страница 8: ...the pipe hanger to a 1 threaded pipe See the suspension method on the left in FIGURE 4 As an alternative method the factory installed pipe hanger may be removed and the heater suspended as illustrated...

Страница 9: ...lled 1 Position curb cross rails and curb side rails as illustrated in FIGURE 8 page 10 If there are two side pieces to a side fasten them with splice plates and hardware as illustrated in the splicin...

Страница 10: ...e is horizontal If the system has an AU11 AU12 AU13 AU14 cooling coil cabinet there is a downturn plenum with vertical discharge Options AU2 AU3 AU11 AU12 AU13 and AU14 are not factory installed Optio...

Страница 11: ...should be supported every six feet 1 8M using a non combustible material such as strap steel or chain Do not rely on the drafthood or heater for support of either horizontal or vertical vent pipe 6 V...

Страница 12: ...re horizontal venting is required or where negative building pressure inhibits gravity venting in stall an optional power venter Option CA Use only a power venter provided by the furnace manufacturer...

Страница 13: ...mmended size is 1 2 x1 2 20 gauge FIGURE11B InstallationoftheVentCap includedinthe optionpackage andthefield suppliedPipingandSupports Oval Adapter Assy PN 103025 Venter Seal Plate P N 43446 9 Condens...

Страница 14: ...air duct should come in con tact with masonry walls Insulate around all air duct through ma sonry walls with not less than 1 2 1 is recommended of insula tion Through Unheated Space Insulate all expo...

Страница 15: ...l connections are made disconnect the pilot supply at the control valve and bleed the system of air Reconnect the pilot line and leak test all connections by brushing on a soap solution WARNING All co...

Страница 16: ...ding MUST be made in accordance with the National Electric CodeANSI NFPANo 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer should be a...

Страница 17: ...ontrols available as part of the gas and air control options Check the wiring diagram and literature supplied with the unit for operation of factory installed optional controls See FIGURE 19 for locat...

Страница 18: ...ND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO TEMPERATURE RATING OF AT LEAST 105 C EXCEPT FOR MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A 4 CAUTION IF ANY OF THE ORIGIN...

Страница 19: ...W LEADS CAP RED 8 USE 18 GA WIRE FOR 24 VOLT CONTROL WIRING ON UNIT NONE NOTES 4 CAUTION IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MAT...

Страница 20: ...L WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOLLOWING CONTROLS ARE SUP...

Страница 21: ...N IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOL...

Страница 22: ...E SAFETY SWITCH PORTION OF THE CONTROL THE SWITCH ACTION PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZED THE A PILOT FLAME ON EACH OPERATING CYCLE THE SENSING PROBE ENERGIZING THE PILOT GAS VALVE...

Страница 23: ...ND ENERGIZES THE MAIN VALVE THE MAIN GAS IGNITES AND THE UNIT FIRES AT LOW RATE 3 ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT THE UNIT FIRES AT FULL RATE 4 IF THE FLAME IS EXTINGUISHED DURING M...

Страница 24: ...outlet temperature turn the adjustable half of the pulley outward One turn of the pulley will change the speed 8 10 5 Tighten the setscrew on the flat portion of the pulley shaft 6 Replace the belt an...

Страница 25: ...ing pressure levels off If a restriction or excessive flue length or turns cause the sensing pres sure to become less than the switch setpoint the pressure switch will function to shut off the main bu...

Страница 26: ...e same as the one illustrated 1 Remove the access panel in the ductwork adjacent to the control compartment access panel 2 Element is retained by spring clips 3 Round gasket and metal retaining plate...

Страница 27: ...IGURE24 Signal Conditioner used in Options AG21 and AG40 Carryover Regulator Modulating Valve Single Stage Gas PrimaryGas FlowPressure Switch WhiteLabel 1 1 w c GasFlow PressureSwitch WhiteLabel 1 1 w...

Страница 28: ...per open Is there voltage between Terminal 88 and Terminal 7 Is there voltage between Terminal 4 on ignition permissive relay and Terminal 7 Replace 1 time delay relay Replace ignition permissive rela...

Страница 29: ...6 38mm 79 23 32 18 25mm 7 16 1 16 11mm 1 6 Option AH2 and spark pilot with lockout is Option AH3 NOTE Outdoor units in Canada using propane require lockout Indoor units in U S and Canada using propane...

Страница 30: ...ers cont d INDOOR Gravity Vented Furnace Models XE HXE Natural gas burners are equipped with two flash carryover systems that receive a supply of gas simultaneously with the main burner NOTE A natural...

Страница 31: ...esuppliedwithairforcombustionasrequired by Code and in Paragraph 6A of this heater installation manual MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPERLYOPERATINGCONDITION lockout control if...

Страница 32: ...3 Bottom Panel Position the air hood bottom panel so that it is to the inside of the two side panels and above the factory installed support angle Attach to the side panels If the bottom panel does n...

Страница 33: ...ecessary Follow these instructions to field connect the water supply and make neces sary checks and adjustments before operating the cooling module with a lock nut and a sealing gasket Check these fit...

Страница 34: ...ockwise to increase the ON time or counterclockwise to decrease the ON time One complete turn will adjust the cycle by 12 to 14 seconds All Modules Check the reservoir for any water leaks The reservoi...

Страница 35: ...e the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting 3 Force a fresh water supply through the water inlet hose and thoroughly flush the...

Страница 36: ...let DamperOptionsonIndoor ModelsXE HXE FIGURE 41B Location of Controls for30 OutsideAirHood andDamperOptions AR6orAR7 OutdoorModelsonly FIGURE41D Exampleof OutsideAirand Return Air Damper Linkage Damp...

Страница 37: ...w c Heater Filter Size Metal Fillers Size A B C D E F1 F2 75 100 125 20x20 20x20 150 175 20x25 20x25 13 16 13 16 200 225 16x25 16x20 16x25 16x20 250 300 20x25 20x20 20x25 20x20 350 20x25 20x25 20x25...

Страница 38: ...B D D E 25 635mm 20 508mm 20 508mm 25 635mm Size 350 D D D C C Size 400 25 635mm 20 508mm B D Key Filter Code Filter Size A 16 x 20 B 20 x 20 C 16 x 25 D 20 x 25 E 25 x 25 Shaded areas are filter blo...

Страница 39: ...d with op tional discharge dampers the damper motor wires must be connected to the terminal blocks in the furnace electrical compartment If the coil cabinet being installed does not include a downturn...

Страница 40: ...ection remove the center hole plug FIGURE 46H To install side and top fillerpanels remove screws from top corners of both cabinets and the entire row across the cooling coil cabinet Removerowofscrews...

Страница 41: ...or lint accumulation Clean as needed Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 12 for re...

Страница 42: ...ryover systems with air pressure 40 Cleaning the Heat Exchanger To clean the outer surfaces circulating air side of the heat exchanger gain access by removing the inspection panels in the ductwork or...

Страница 43: ...causes 8 Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch 9 Replace combustion air proving switch 10 Activated blocked vent switch indoor system 10 Correct ve...

Страница 44: ...AG39 or AG40 see page 28 For replacement parts refer to Form P X XE for indoor units or Form P RG RP RBL for outdoor units Problem Probable Cause Remedy Pump does not run Unit is 1 Electrical connecti...

Отзывы: