background image

Form I-XE/CRGB/RPB, Mfg No. 131782 Rev 4, Page 25

controls or miswiring, and will require correction of
the cause of failure and the replacement of the fan
and limit control and wiring before the unit can be
returned to service. See Hazard Levels, page 2.

16. Fan Control

1. A fan control provides for the following control of the blower.

(a) After the gas valve opens, there is a time delay of blower opera-
tion to prevent the discharge of cold air.
(b) Blower operation continues after the thermostat is satisfied as
determined by the fan time delay.

2. To be sure that the blower can continue to operate, the power sup-

ply to the furnace 

MUST NOT

 be interrupted 

except

 when servic-

ing the unit.

3. If the customer wants the furnace off at night, the gas valve circuit

SHOULD BE OPENED by a single pole switch wired in series with
the thermostat. Some thermostats are provided with this feature.
Multiple units controlled from a single thermostat are shut off in the
same manner. For proper operation, be sure the fan control wiring is
observed. For location, see 

FIGURE 19

, Item 12.

Service NOTE:

 To replace the fan control on units manufactured

prior to 11/04, a replacement kit is required. Order P/N 209184.

17. Blocked Vent Switch (Indoor

Models XE/HXE)

The blocked vent switch is a heat-activated, manually reset, safety
device that interrupts the electric supply to the gas valve when the vent
is 100% blocked. The sensor is located near the relief opening of the
drafthood; the reset button is inside the control compartment by the
drafthood side.
If the sensor detects heated flue gases in the drafthood relief opening
area, the blocked vent safety device will activate to shut down the
furnace. The cause for the switch shutting down the furnace must be
determined and corrected. The blocked vent switch is designed to acti-
vate when the vent is blocked but may also be affected by a negative
building pressure or an inadequate vent system.
After the problem has been corrected, remove the furnace control side
panel and push the manual reset button on the blocked vent switch to
restart the furnace. Replace control panel.

WARNING: In the event the blocked vent sensor
causes the furnace to shut off, determine and correct
the cause. Failure to do so could result in personal
injury or death.

NOTE

: Effective April 1991, this model of indoor, gravity-vent fur-

naces is equipped with a blocked vent shut-off system. These units
manufactured prior to April 1991 do not include the blocked vent switch.

18. Combustion Air Proving Switch

(Power-Vented Model RPB)

The combustion air proving switch ensures that proper combustion
airflow is available. The switch is a single-pole, double-throw switch,
which senses pressure caused by the flow of combustion air from the
venter. The switch is designed to close when a decreasing pressure is
sensed in the outlet duct of the gas collection box. For location, see

FIGURE 19

, Item 2.)

On start-up when the furnace is cold, the sensing pressure is at the most
negative level, and as the furnace and the flue system warm-up, the
sensing pressure becomes less negative. After the system has reached
equilibrium (approximately 20 minutes), the sensing pressure levels off.
If a restriction or excessive flue length or turns cause the sensing pres-
sure to become less than the switch setpoint, the pressure switch will
function to shut off the main burners. The main burners will remain off
until the system has cooled and/or the flue system resistance is reduced.

The table below gives approximate water column negative pressure
readings and switch setpoints for sea level operating conditions.

Startup Cold

Equilibrium

Factory Setpoint

-1.05" w.c.

-.73" w.c.

-.58 

±

 .05" w.c.

DANGER: Safe operation requires proper venting
flow. Never bypass the combustion air proving
switch or attempt to operate the unit without the
venter running and proper flow in the vent system.
Hazardous condition could result. See Hazard
Levels, page 2.

19. Reverse Flow, Limit Control

(Outdoor Models CRGB & RPB)

These outdoor furnaces are factory equipped with an automatic reset
reverse flow limit control. This control is located in the blower compart-
ment, mounted in the blower junction box adjacent to the blower inlet
opening, and is wired in series with the main limit control mounted on
the heat exchanger duct side. For location, see 

FIGURE 19

, Item 32.

In case of belt breakage or motor failure, the limit control will be opened
by the high temperatures caused by reverse flow from the heat ex-
changer to the blower compartment, thus breaking the circuit to the
automatic electric gas valve and preventing burner operation.

20. Optional High Ambient Limit

Control (Outdoor Models)

The optional high ambient limit control functions to shutoff the burner
when the entering outside air reaches a set temperature. The tempera-
ture setting is field adjustable from 0-100°F. For location, see 

FIGURE

19

, Item 21.

21. Operating Valve

All furnaces are equipped with a 24-volt combination valve which in-
cludes the automatic electric on-off valve controlled by the room ther-
mostat, the pressure regulator, the safety pilot valve, and the manual
shutoff valve. The standard gas valve allows for single-stage control
from a single-stage, 24-volt thermostat.

WARNING: The operating valve is the prime safety
shutoff. All gas supply lines must be free of dirt or
scale before connecting the unit to ensure positive
closure. See Hazard Levels, page 2.

22. Optional 2-Stage Operation -

Heating Only Application

The standard combination control valve is replaced with a two-stage
combination gas control valve providing for low fire or high fire opera-
tion controlled by a two-stage thermostat. First stage (low fire) is fac-
tory set (not field adjustable). Both high and low stages are controlled
by a Servo regulator, maintaining constant gas input under wide varia-
tions in gas supply pressure. See instructions packed with the unit for
specific gas valve specifications, wiring, and operating instructions.

23. Optional 2-Stage Operation -

Makeup Air Application

Two-stage makeup air units are equipped with a two-stage gas valve,
but instead of control from a two-stage room thermostat, the outlet air
temperature is monitored and controlled by a two-stage ductstat. When
the discharge air temperature drops to the setpoint, low fire is ener-
gized. If low fire cannot satisfy the ductstat setting, high fire is ener-
gized.

Makeup air applications are usually adjusted to discharge an outlet air
temperature between 65°F and 75°F. In all applications, the allowable

Содержание CRGB Series

Страница 1: ...AquaSaver Timer Adjustment 34 Belts 24 Blocked Vent Switch 25 Blower Motors 24 Blower Rotation 24 Burner Air Adjustment 30 Burner Rack Removal 42 Burners 29 Carryover System 29 Check Installation and...

Страница 2: ...rhalogenatedhydrocarbonsorany contaminant silicone aluminium oxide etc that adheres to the spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c...

Страница 3: ...x 19 1 2 495mm Return Air Openings with Optional Cabinet X Hanger Centerline Standard and Optional Blower Cabinet Dimensions inches andmm Gravity Vented Indoor Models XE HXE Gas Connection Natural Pr...

Страница 4: ...side the downturn plenum cabinet For dimensions with downturn plenum cabinet with a cooling coil cabinet see page 6 FIGURE1B Dimensions Outdoor Gravity VentedModel Series CRGB Vent Cap Gas Connection...

Страница 5: ...ottom of cabinet side If system has a cooling coil cabinet add length dimension on page 6 for full system length The two position discharge dampers in Option AQ8 fit in the discharge air opening The d...

Страница 6: ...ownturnPlenumCabinet factoryattachedto either type of Cooling Coil Cabinet Front View DX Coil Cabinet with Horizontal Discharge Option AU3 Liquid Line Connections 7 8 or 1 3 8 5 1 8 130 8 203 3 4 19 3...

Страница 7: ...r from inside the building openings 1 square inch free area per 1000 BTUH Never less than 100 square inches free area for each open ing See 1 in FIGURE 2 2 Air from outside through duct openings 1 squ...

Страница 8: ...the pipe hanger to a 1 threaded pipe See the suspension method on the left in FIGURE 4 As an alternative method the factory installed pipe hanger may be removed and the heater suspended as illustrated...

Страница 9: ...lled 1 Position curb cross rails and curb side rails as illustrated in FIGURE 8 page 10 If there are two side pieces to a side fasten them with splice plates and hardware as illustrated in the splicin...

Страница 10: ...e is horizontal If the system has an AU11 AU12 AU13 AU14 cooling coil cabinet there is a downturn plenum with vertical discharge Options AU2 AU3 AU11 AU12 AU13 and AU14 are not factory installed Optio...

Страница 11: ...should be supported every six feet 1 8M using a non combustible material such as strap steel or chain Do not rely on the drafthood or heater for support of either horizontal or vertical vent pipe 6 V...

Страница 12: ...re horizontal venting is required or where negative building pressure inhibits gravity venting in stall an optional power venter Option CA Use only a power venter provided by the furnace manufacturer...

Страница 13: ...mmended size is 1 2 x1 2 20 gauge FIGURE11B InstallationoftheVentCap includedinthe optionpackage andthefield suppliedPipingandSupports Oval Adapter Assy PN 103025 Venter Seal Plate P N 43446 9 Condens...

Страница 14: ...air duct should come in con tact with masonry walls Insulate around all air duct through ma sonry walls with not less than 1 2 1 is recommended of insula tion Through Unheated Space Insulate all expo...

Страница 15: ...l connections are made disconnect the pilot supply at the control valve and bleed the system of air Reconnect the pilot line and leak test all connections by brushing on a soap solution WARNING All co...

Страница 16: ...ding MUST be made in accordance with the National Electric CodeANSI NFPANo 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer should be a...

Страница 17: ...ontrols available as part of the gas and air control options Check the wiring diagram and literature supplied with the unit for operation of factory installed optional controls See FIGURE 19 for locat...

Страница 18: ...ND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO TEMPERATURE RATING OF AT LEAST 105 C EXCEPT FOR MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A 4 CAUTION IF ANY OF THE ORIGIN...

Страница 19: ...W LEADS CAP RED 8 USE 18 GA WIRE FOR 24 VOLT CONTROL WIRING ON UNIT NONE NOTES 4 CAUTION IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MAT...

Страница 20: ...L WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOLLOWING CONTROLS ARE SUP...

Страница 21: ...N IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOL...

Страница 22: ...E SAFETY SWITCH PORTION OF THE CONTROL THE SWITCH ACTION PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZED THE A PILOT FLAME ON EACH OPERATING CYCLE THE SENSING PROBE ENERGIZING THE PILOT GAS VALVE...

Страница 23: ...ND ENERGIZES THE MAIN VALVE THE MAIN GAS IGNITES AND THE UNIT FIRES AT LOW RATE 3 ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT THE UNIT FIRES AT FULL RATE 4 IF THE FLAME IS EXTINGUISHED DURING M...

Страница 24: ...outlet temperature turn the adjustable half of the pulley outward One turn of the pulley will change the speed 8 10 5 Tighten the setscrew on the flat portion of the pulley shaft 6 Replace the belt an...

Страница 25: ...ing pressure levels off If a restriction or excessive flue length or turns cause the sensing pres sure to become less than the switch setpoint the pressure switch will function to shut off the main bu...

Страница 26: ...e same as the one illustrated 1 Remove the access panel in the ductwork adjacent to the control compartment access panel 2 Element is retained by spring clips 3 Round gasket and metal retaining plate...

Страница 27: ...IGURE24 Signal Conditioner used in Options AG21 and AG40 Carryover Regulator Modulating Valve Single Stage Gas PrimaryGas FlowPressure Switch WhiteLabel 1 1 w c GasFlow PressureSwitch WhiteLabel 1 1 w...

Страница 28: ...per open Is there voltage between Terminal 88 and Terminal 7 Is there voltage between Terminal 4 on ignition permissive relay and Terminal 7 Replace 1 time delay relay Replace ignition permissive rela...

Страница 29: ...6 38mm 79 23 32 18 25mm 7 16 1 16 11mm 1 6 Option AH2 and spark pilot with lockout is Option AH3 NOTE Outdoor units in Canada using propane require lockout Indoor units in U S and Canada using propane...

Страница 30: ...ers cont d INDOOR Gravity Vented Furnace Models XE HXE Natural gas burners are equipped with two flash carryover systems that receive a supply of gas simultaneously with the main burner NOTE A natural...

Страница 31: ...esuppliedwithairforcombustionasrequired by Code and in Paragraph 6A of this heater installation manual MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPERLYOPERATINGCONDITION lockout control if...

Страница 32: ...3 Bottom Panel Position the air hood bottom panel so that it is to the inside of the two side panels and above the factory installed support angle Attach to the side panels If the bottom panel does n...

Страница 33: ...ecessary Follow these instructions to field connect the water supply and make neces sary checks and adjustments before operating the cooling module with a lock nut and a sealing gasket Check these fit...

Страница 34: ...ockwise to increase the ON time or counterclockwise to decrease the ON time One complete turn will adjust the cycle by 12 to 14 seconds All Modules Check the reservoir for any water leaks The reservoi...

Страница 35: ...e the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting 3 Force a fresh water supply through the water inlet hose and thoroughly flush the...

Страница 36: ...let DamperOptionsonIndoor ModelsXE HXE FIGURE 41B Location of Controls for30 OutsideAirHood andDamperOptions AR6orAR7 OutdoorModelsonly FIGURE41D Exampleof OutsideAirand Return Air Damper Linkage Damp...

Страница 37: ...w c Heater Filter Size Metal Fillers Size A B C D E F1 F2 75 100 125 20x20 20x20 150 175 20x25 20x25 13 16 13 16 200 225 16x25 16x20 16x25 16x20 250 300 20x25 20x20 20x25 20x20 350 20x25 20x25 20x25...

Страница 38: ...B D D E 25 635mm 20 508mm 20 508mm 25 635mm Size 350 D D D C C Size 400 25 635mm 20 508mm B D Key Filter Code Filter Size A 16 x 20 B 20 x 20 C 16 x 25 D 20 x 25 E 25 x 25 Shaded areas are filter blo...

Страница 39: ...d with op tional discharge dampers the damper motor wires must be connected to the terminal blocks in the furnace electrical compartment If the coil cabinet being installed does not include a downturn...

Страница 40: ...ection remove the center hole plug FIGURE 46H To install side and top fillerpanels remove screws from top corners of both cabinets and the entire row across the cooling coil cabinet Removerowofscrews...

Страница 41: ...or lint accumulation Clean as needed Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 12 for re...

Страница 42: ...ryover systems with air pressure 40 Cleaning the Heat Exchanger To clean the outer surfaces circulating air side of the heat exchanger gain access by removing the inspection panels in the ductwork or...

Страница 43: ...causes 8 Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch 9 Replace combustion air proving switch 10 Activated blocked vent switch indoor system 10 Correct ve...

Страница 44: ...AG39 or AG40 see page 28 For replacement parts refer to Form P X XE for indoor units or Form P RG RP RBL for outdoor units Problem Probable Cause Remedy Pump does not run Unit is 1 Electrical connecti...

Отзывы: