background image

Form I-XE/CRGB/RPB, Page 24

WARNING: If you turn off the power supply, turn
off the gas. See Hazard Levels, page 2.

15. Limit and Energy Cutoff

Controls

Heaters are equipped with a non-adjustable high limit switch which
shuts off the gas in the event of motor failure, lack of air due to dirty
filters, or restrictions at the inlet or outlet of the unit. See Paragraph 30
for limit control check. For location, see 

FIGURE 19

, Item 11.

Indoor Model XE systems are also equipped with a fusible link in the
thermocouple circuit which acts to cause safety pilot drop out in case
of limit control malfunction or failure of the blower motor in combina-
tion with the automatic valve failing to close. This ECO control acts as
a super high limit providing redundant safety control and is calibrated
to open at a much higher temperature than the standard automatic
reset limit.

An ECO fusible link interruption can be caused by the following
combination of failures:
1. Automatic gas valve stuck in open position.
2. Restricted air flow over heat exchanger due to motor failure,

broken blower belt, or defective fan control.

3. Ruptured gas pressure regulator.
4. Improper wiring.

WARNING: An ECO circuit interruption is a major
failure caused by a malfunction of the primary safety

13. Blowers, Belts and Drives

Check belt tension. Proper
belt tension is important to
the long life of the belt and
motor. A loose belt will cause
wear and slippage. Too much
tension will cause excessive
motor and blower bearing
wear. Adjust the belt tension
by turning the adjusting screw on the motor base until the belt can be
depressed 3/4" (19mm). (See 

FIGURE 20

.) After correct tension is

achieved, re-tighten the locknut on the adjustment screw. Be sure that the
belt is aligned in the pulleys.

Adjusting Blower Speed

The blower speed may be adjusted to achieve the desired outlet tempera-
ture, as long as the adjustment is within the temperature rise and the static
pressure limits shown on the furnace rating plate. Motors are factory set
between maximum and minimum blower speeds.

If the duct resistance is low, the blower may deliver too high an air
volume. If the resistance is very low, the blower may deliver excess air to
overload the motor, causing the overload protector to cycle the motor.
Reducing the blower speed will correct these conditions. If ductwork is
added to an installation, it may be necessary to increase the blower speed.
Decreasing blower speed will increase outlet temperature; increasing blower
speed will decrease outlet temperature.

At final adjustment, amperes should not exceed motor nameplate
amp rating. The installation must be adjusted to obtain a tempera-
ture rise within the range specified on the furnace rating plate.

The belt drive on these units is equipped with an adjustable pulley which
permits adjustment of the blower speed. Follow these instructions to
adjust the blower speed.

1.

Turn off the gas and the electric power.

2. Loosen belt tension and remove the belt.

3.

Loosen the setscrew on the side of the pulley away from the motor.

4. To increase the blower speed, decreasing outlet temperature

,

turn the adjustable half of the pulley inward. 

To decrease the blower

speed, increasing the outlet temperature

, turn the adjustable half

of the pulley outward. One turn of the pulley will change the speed 8-
10%.

5.

Tighten the setscrew on the flat portion of the pulley shaft.

6.

Replace the belt and adjust the belt tension. Adjust tension by turning
the adjusting screw on the motor base until the belt can be depressed
3/4" (19mm). See 

FIGURE 20

. Re-tighten the lock nut on the adjust-

ing screw. Be sure that the belts are aligned in the pulley grooves
properly and are not angled from pulley to pulley.

7.

Turn on the gas and electric. Light the heater following the instruc-
tions on the lighting instruction plate.

8.

Check the motor amps with an amp meter. The maximum motor amp
rating on the motor nameplate must not be exceeded.

When service is complete, check for proper operation.

Blower Rotation

Each blower housing is marked for proper rotation. Rotation may be
changed on single-phase motors by re-wiring in the motor terminal box.
Three-phase motors may be reversed by interchanging two wires on the
3-phase supply connections.

Optional Airflow Proving Switch (Makeup Air
only) - Outdoor Models with Option BW1

The optional airflow proving switch ensures that the circulating air blower
is functionally providing an adequate amount of airflow prior to the unit
being fired. The switch is a single pole/normally open device which closes
when an increase in pressure, above the setpoint, is sensed in the circulat-
ing air blower. The switch is located in the blower junction box. (See

FIGURE 19

, Item 40).

Contacts are set to close at .10" w.c. (+.05" or -.02" w.c.).

3/4” (19mm)

FIGURE 20 - Check Belt Tension

14. Blower Motors

Use an amp meter to check motor amps. The following chart lists full
load amps for various HP's and voltages. Amps may be adjusted down-
ward by reducing blower RPM or increasing duct system static pres-
sure.
This chart can be used for sizing line wiring but should not be inter-
preted as the exact motor amps. See the motor rating plate for exact
motor specifications.

Full Load Amps - Blower Motors (Open)

(Single Speed- Average Values)

HP

1/4 1/3 1/2 3/4

1

1-1/2

2

3

5

115V 1PH

5.1

5.5

8.8 11.0 13.0 15.0 20.4 24.8 N/A

208V 1PH

2.1

3.2

5.1

6.3

7.5

8.3

11.3 14.0 28.0

230V 1PH

2.3

2.8

4.4

5.5

6.5

7.5

10.2 12.4 26.0

208V 3PH

1.1

1.4

2.3

2.9

3.7

5.6

7.0

9.0 13.4

230V 3PH

1.4

1.6

2.0

2.6

3.2

5.0

6.6

8.6 13.2

460V 3PH

.75

.80

1.0

1.3

1.6

2.7

3.5

4.3

6.6

575V 3PH

N/A N/A N/A N/A 1.1

1.6

2.1

3.6

5.4

Optional Variable Frequency Drive

When an optional variable frequency drive is ordered, the motor oper-
ates on two speeds as determined by the electrical frequency. High
speed is used for cooling and low speed for heating. 60 hertz is the
maximum high speed. Maximum speed for low speed heating is the
frequency that will provide the maximum temperature rise of the heater.

Follow the variable frequency controller manufacturer's instructions
that are packaged with the heater (in the owner's envelope) to program
the variable frequency drive settings. The formula for motor speed is
N=120xf/p where N is speed; f is frequency; and p is number of poles
(3600 RPM motor has 2 poles; an 1800 RPM motor has 4 poles).

Example:

1800 RPM motor on 60Hz; N = 120 x 60/4 = 1800
1800 is synchronous speed; assume 2% slip. Motor
will run between 1750 and 1790 RPM at full load
depending on design. Run the same motor at 45Hz
(120 x 45/4 = 1350). 1350 RPM less 2% slip equals
about 1300 RPM.

Содержание CRGB Series

Страница 1: ...AquaSaver Timer Adjustment 34 Belts 24 Blocked Vent Switch 25 Blower Motors 24 Blower Rotation 24 Burner Air Adjustment 30 Burner Rack Removal 42 Burners 29 Carryover System 29 Check Installation and...

Страница 2: ...rhalogenatedhydrocarbonsorany contaminant silicone aluminium oxide etc that adheres to the spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c...

Страница 3: ...x 19 1 2 495mm Return Air Openings with Optional Cabinet X Hanger Centerline Standard and Optional Blower Cabinet Dimensions inches andmm Gravity Vented Indoor Models XE HXE Gas Connection Natural Pr...

Страница 4: ...side the downturn plenum cabinet For dimensions with downturn plenum cabinet with a cooling coil cabinet see page 6 FIGURE1B Dimensions Outdoor Gravity VentedModel Series CRGB Vent Cap Gas Connection...

Страница 5: ...ottom of cabinet side If system has a cooling coil cabinet add length dimension on page 6 for full system length The two position discharge dampers in Option AQ8 fit in the discharge air opening The d...

Страница 6: ...ownturnPlenumCabinet factoryattachedto either type of Cooling Coil Cabinet Front View DX Coil Cabinet with Horizontal Discharge Option AU3 Liquid Line Connections 7 8 or 1 3 8 5 1 8 130 8 203 3 4 19 3...

Страница 7: ...r from inside the building openings 1 square inch free area per 1000 BTUH Never less than 100 square inches free area for each open ing See 1 in FIGURE 2 2 Air from outside through duct openings 1 squ...

Страница 8: ...the pipe hanger to a 1 threaded pipe See the suspension method on the left in FIGURE 4 As an alternative method the factory installed pipe hanger may be removed and the heater suspended as illustrated...

Страница 9: ...lled 1 Position curb cross rails and curb side rails as illustrated in FIGURE 8 page 10 If there are two side pieces to a side fasten them with splice plates and hardware as illustrated in the splicin...

Страница 10: ...e is horizontal If the system has an AU11 AU12 AU13 AU14 cooling coil cabinet there is a downturn plenum with vertical discharge Options AU2 AU3 AU11 AU12 AU13 and AU14 are not factory installed Optio...

Страница 11: ...should be supported every six feet 1 8M using a non combustible material such as strap steel or chain Do not rely on the drafthood or heater for support of either horizontal or vertical vent pipe 6 V...

Страница 12: ...re horizontal venting is required or where negative building pressure inhibits gravity venting in stall an optional power venter Option CA Use only a power venter provided by the furnace manufacturer...

Страница 13: ...mmended size is 1 2 x1 2 20 gauge FIGURE11B InstallationoftheVentCap includedinthe optionpackage andthefield suppliedPipingandSupports Oval Adapter Assy PN 103025 Venter Seal Plate P N 43446 9 Condens...

Страница 14: ...air duct should come in con tact with masonry walls Insulate around all air duct through ma sonry walls with not less than 1 2 1 is recommended of insula tion Through Unheated Space Insulate all expo...

Страница 15: ...l connections are made disconnect the pilot supply at the control valve and bleed the system of air Reconnect the pilot line and leak test all connections by brushing on a soap solution WARNING All co...

Страница 16: ...ding MUST be made in accordance with the National Electric CodeANSI NFPANo 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer should be a...

Страница 17: ...ontrols available as part of the gas and air control options Check the wiring diagram and literature supplied with the unit for operation of factory installed optional controls See FIGURE 19 for locat...

Страница 18: ...ND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO TEMPERATURE RATING OF AT LEAST 105 C EXCEPT FOR MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A 4 CAUTION IF ANY OF THE ORIGIN...

Страница 19: ...W LEADS CAP RED 8 USE 18 GA WIRE FOR 24 VOLT CONTROL WIRING ON UNIT NONE NOTES 4 CAUTION IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MAT...

Страница 20: ...L WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOLLOWING CONTROLS ARE SUP...

Страница 21: ...N IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOL...

Страница 22: ...E SAFETY SWITCH PORTION OF THE CONTROL THE SWITCH ACTION PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZED THE A PILOT FLAME ON EACH OPERATING CYCLE THE SENSING PROBE ENERGIZING THE PILOT GAS VALVE...

Страница 23: ...ND ENERGIZES THE MAIN VALVE THE MAIN GAS IGNITES AND THE UNIT FIRES AT LOW RATE 3 ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT THE UNIT FIRES AT FULL RATE 4 IF THE FLAME IS EXTINGUISHED DURING M...

Страница 24: ...outlet temperature turn the adjustable half of the pulley outward One turn of the pulley will change the speed 8 10 5 Tighten the setscrew on the flat portion of the pulley shaft 6 Replace the belt an...

Страница 25: ...ing pressure levels off If a restriction or excessive flue length or turns cause the sensing pres sure to become less than the switch setpoint the pressure switch will function to shut off the main bu...

Страница 26: ...e same as the one illustrated 1 Remove the access panel in the ductwork adjacent to the control compartment access panel 2 Element is retained by spring clips 3 Round gasket and metal retaining plate...

Страница 27: ...IGURE24 Signal Conditioner used in Options AG21 and AG40 Carryover Regulator Modulating Valve Single Stage Gas PrimaryGas FlowPressure Switch WhiteLabel 1 1 w c GasFlow PressureSwitch WhiteLabel 1 1 w...

Страница 28: ...per open Is there voltage between Terminal 88 and Terminal 7 Is there voltage between Terminal 4 on ignition permissive relay and Terminal 7 Replace 1 time delay relay Replace ignition permissive rela...

Страница 29: ...6 38mm 79 23 32 18 25mm 7 16 1 16 11mm 1 6 Option AH2 and spark pilot with lockout is Option AH3 NOTE Outdoor units in Canada using propane require lockout Indoor units in U S and Canada using propane...

Страница 30: ...ers cont d INDOOR Gravity Vented Furnace Models XE HXE Natural gas burners are equipped with two flash carryover systems that receive a supply of gas simultaneously with the main burner NOTE A natural...

Страница 31: ...esuppliedwithairforcombustionasrequired by Code and in Paragraph 6A of this heater installation manual MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPERLYOPERATINGCONDITION lockout control if...

Страница 32: ...3 Bottom Panel Position the air hood bottom panel so that it is to the inside of the two side panels and above the factory installed support angle Attach to the side panels If the bottom panel does n...

Страница 33: ...ecessary Follow these instructions to field connect the water supply and make neces sary checks and adjustments before operating the cooling module with a lock nut and a sealing gasket Check these fit...

Страница 34: ...ockwise to increase the ON time or counterclockwise to decrease the ON time One complete turn will adjust the cycle by 12 to 14 seconds All Modules Check the reservoir for any water leaks The reservoi...

Страница 35: ...e the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting 3 Force a fresh water supply through the water inlet hose and thoroughly flush the...

Страница 36: ...let DamperOptionsonIndoor ModelsXE HXE FIGURE 41B Location of Controls for30 OutsideAirHood andDamperOptions AR6orAR7 OutdoorModelsonly FIGURE41D Exampleof OutsideAirand Return Air Damper Linkage Damp...

Страница 37: ...w c Heater Filter Size Metal Fillers Size A B C D E F1 F2 75 100 125 20x20 20x20 150 175 20x25 20x25 13 16 13 16 200 225 16x25 16x20 16x25 16x20 250 300 20x25 20x20 20x25 20x20 350 20x25 20x25 20x25...

Страница 38: ...B D D E 25 635mm 20 508mm 20 508mm 25 635mm Size 350 D D D C C Size 400 25 635mm 20 508mm B D Key Filter Code Filter Size A 16 x 20 B 20 x 20 C 16 x 25 D 20 x 25 E 25 x 25 Shaded areas are filter blo...

Страница 39: ...d with op tional discharge dampers the damper motor wires must be connected to the terminal blocks in the furnace electrical compartment If the coil cabinet being installed does not include a downturn...

Страница 40: ...ection remove the center hole plug FIGURE 46H To install side and top fillerpanels remove screws from top corners of both cabinets and the entire row across the cooling coil cabinet Removerowofscrews...

Страница 41: ...or lint accumulation Clean as needed Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 12 for re...

Страница 42: ...ryover systems with air pressure 40 Cleaning the Heat Exchanger To clean the outer surfaces circulating air side of the heat exchanger gain access by removing the inspection panels in the ductwork or...

Страница 43: ...causes 8 Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch 9 Replace combustion air proving switch 10 Activated blocked vent switch indoor system 10 Correct ve...

Страница 44: ...AG39 or AG40 see page 28 For replacement parts refer to Form P X XE for indoor units or Form P RG RP RBL for outdoor units Problem Probable Cause Remedy Pump does not run Unit is 1 Electrical connecti...

Отзывы: