background image

 

 

 

DD-

17DSI • DD-17DSIW

 

NT-

12S/SE • NT-16S/SE • NT-20S/SE

 

NT-

24SP • NT-30SP • NT-34SP

 

NT-40

 

P-30S/40

 

SF-

20 • SF-25 • SF-30 • SF-35 • SF-42

 

SF-

20F • SF-25F • SF-30F • SF-35F • SF-42F

 

SH-

35 • SH-42

 

SH-

35F • SH-42F

 

SHD-2542

 

SFV-

35 • SFV-42

 

SFV-

35F • SFV-42F

 

SUBURBAN MANUFACTURING COMPANY

 

 Broadway Street

 

676

 

Dayton, Tennessee 37321

 

423-775-2131

 

Fax: 423-775-7015

 

www.rvcomfort.co

 

m

 

i[email protected]

 

Suburban

 

RV FURNACES

 

SERVICE MANUAL

 

Содержание DD-17DSI

Страница 1: ...SF 30 SF 35 SF 42 SF 20F SF 25F SF 30F SF 35F SF 42F SH 35 SH 42 SH 35F SH 42F SHD 2542 SFV 35 SFV 42 SFV 35F SFV 42F SUBURBAN MANUFACTURING COMPANY Broadway Street 676 Dayton Tennessee 37321 423 775...

Страница 2: ...on Furnaces 29 30 Wiring Diagrams 30 34 Furnace Removal 35 36 SF SH and SHD 2542 Electrode Gap Specifications Positioning 37 NT and Park Model Electrode Gap Specifications Positioning 38 Maintenance 3...

Страница 3: ...s Supply Pressure Requirements Line Pressure Minimum 11 WC Maximum 14 WC WC water column Voltage Requirements Voltage DC 12 volt D C Minimum 10 5 volts D C Maximum 13 5 volts D C Service Tools Require...

Страница 4: ...SF 30 30 000 7 1 2 17 20 Electronic 35 SF 35 35 000 7 1 2 17 20 Electronic 35 SF 42 40 000 7 1 2 17 20 Electronic 35 SH 35 35 000 9 1 4 17 20 Electronic 40 SH 42 40 000 9 1 4 17 20 Electronic 42 SHD 2...

Страница 5: ...ll Suburban forced draft furnaces regardless of the model or the method in which they are installed They are 1 Selecting a Location 2 Venting 3 Return Air 4 Ducting Refer to the furnace installation m...

Страница 6: ...between the exhaust and intake caulking Refer to the vent assembly installation in the manual The vent must be straight There can be no offsets or turns in the vent All vent tubes which connect to th...

Страница 7: ...7 SH VENT ASSEMBLY INSTALLATION SF and SH SERIES Figure 2 SF Figure 2A...

Страница 8: ...8 SH and SHD 2542 VENT ASSEMBLY INSTALLATION SF and SH SERIES Figure 3 SF Figure 3A...

Страница 9: ...9 SH VENT ASSEMBLY INSTALLATION SFV Figure 4 SF Figure 4A...

Страница 10: ...10 Figure 5A Figure 5...

Страница 11: ...11 Figure 6...

Страница 12: ...12 Figure 6A VENT ASSEMBLY INSTALLATION DD SERIES Note Vent cap must be installed on DD furnace when bench testing Figure 7...

Страница 13: ...VENT ASSEMBLY INSTALLATION NT SERIES 13 NT 12 16 20S and SE NT 12 16S Figure 8 NT 12 16 20SE Figure 9 Figure 10...

Страница 14: ...VENT ASSEMBLY INSTALLATION NT SERIES 14 NT 20S Figure 11 Figure 12...

Страница 15: ...MAX LENGTH Extension Tube Range 520498 2 1 4 to 3 1 8 520499 3 1 8 to 4 7 8 520500 4 7 8 to 7 520501 7 to 9 Figure 14 NT 24 30 34SP P 30S EXTENSION TUBE KIT NUMBER MIN MAX LENGTH Extension Tube Range...

Страница 16: ...16 VENT ASSEMBLY INSTALLATION NT 40 and P 40 P 40 Figure 16 NT 40 Figure 17...

Страница 17: ...ea of the sofa or bed Return air from the living area of the trailer is drawn in through the grille and into the return air openings in the furnace cabinet Figure 19 illustrates the return air circula...

Страница 18: ...o means for return air recirculation should not be counted in the required duct area Also ducts 2 in diameter or smaller should not be counted in the required duct area When installing a duct system a...

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...265 NT 30SP Ducted 30 000 PROPANE 12 VDC 2 5 5 5 2 wc 345 NT 34SP Ducted 34 000 PROPANE 12 VDC 2 5 7 5 1 wc 373 NT 40 Ducted 40 000 PROPANE 12 VDC 2 5 9 5 155 20B 441 Park Models P 30S Ducted 30 000 P...

Страница 29: ...20 000 PROPANE 12 VDC 3 8 5 2 wc 300 SFV 25 25F Ducted 25 000 PROPANE 12 VDC 3 8 5 2 wc 300 SFV 30 30F Ducted 30 000 PROPANE 12 VDC 3 8 5 2 wc 300 SFV 35 35F Ducted 35 000 PROPANE 12 VDC 3 9 4 2 wc 37...

Страница 30: ...comes up to speed air flow closes the sail switch completing the circuit The sail switch is placed into the system as a safety to prove there is adequate air for combustion The next operation is cont...

Страница 31: ...nse sail switch and limit switch circuits and the thermostat inputs during the heating period The flame is sensed through the spark wire and electrode Therefore it is essential that the electrode is p...

Страница 32: ...cycle the limit switch circuit opens and remains open the gas valve will close and the blower motor will continue to run 90 Second Shut Down When the thermostat has reached its set point and the deman...

Страница 33: ...will remain in the second stage operation until thermostat is satisfied 90 Second Shut Down When the thermostat has reached its set point and the demand for heat ends the gas valve will be de energize...

Страница 34: ...loses No contact points and the heat Yes connections replace thermostat if anticipator anticipator is shorted No Check 12vdc at blue wire check the Yes Replace thermostat amp draw to thermostat Yes No...

Страница 35: ...re at the manifold or for Did the gas valve open restrictions in the burner orifice Yes No Yes Check for restriction in Replace the gas valve combustion air Intake wasps etc No No Check flame contact...

Страница 36: ...in the gas supply line If no gas is coming through the burner check for obstruction in gas line in main burner orifice or in main burner b Gas is coming through burner but spark will still not ignite...

Страница 37: ...he problem especially where the horizontal type gas bottle is being used the following steps should be take to prepare the gas system against further moisture problems Corrective Measures 1 Disconnect...

Страница 38: ...38 Figure 24 Figure 25 Figure 23 Remote Flame Sense With Time Delay Fan Control Board SF 20 25 30 35 42F Local Flame Sense NT Models With Time Delay...

Страница 39: ...39 Figure 26 Local Flame Sense SF Models With Time Delay Figure 27 Fan Control Board NT 12 16 20S and SE...

Страница 40: ...40 Figure 28 Fan Control Board NT 24 30 34SP and NT 40 Figure 29 Fan Control...

Страница 41: ...41 P 30S Figure 30 Fan Control Board P 40...

Страница 42: ...cap assembly by removing applicable screws 3 Remove the cabinet front two 2 screws 4 Remove the 2 two tie down screws securing the chamber to the cabinet 5 Remove the furnace from the cabinet by pulli...

Страница 43: ...rode should be positioned as outlined in the drawing 1 Remove the furnace chamber assembly from the furnace cabinet following instructions listed in the installation manual 2 Remove the burner access...

Страница 44: ...positioned as outlined in the drawing 1 1 8 spark gap between electrode and ground 2 Maintain electrode position of 3 16 over burner ports Figure 32 LOCAL FLAME SENSE PARK MODEL ELECTRODE GAP SPECIFIC...

Страница 45: ...ues under these conditions it could result in serious injury to the occupants of the RV or even death Cleaning of the main burner and an inspection of the venting system should be done at least once a...

Страница 46: ...46 Figure 36 Figure 37...

Страница 47: ...trode assembly on remote sense units 5 Install the furnace so electrical components and connections are protected from water 6 Wire the furnace direct to the battery when possible 7 Use two wrenches o...

Страница 48: ...SUBURBAN MANUFACTURING COMPANY 676 Broadway Street Dayton Tennessee 37321 423 775 2131 Fax 423 775 7015 www rvcomfort com E mail info1 suburbanmfg com 2007...

Отзывы: