30
SEQUENCE OF OPERATION
For Furnaces Equipped With Time Delay
The thermostat controls the operating circuit to the furnace by reacting to room temperature to open
and close a set of contact points which allows current to flow to the ON and OFF switch then to the
relay.
The relay receives the power and allows power to pass through to the switch within the relay. This
is done by a heater coil within the relay which actuates a bi-metal disc closing the relay circuit.
The power then flows to the motor and allows the blower to operate. One end of the motor shaft
drives the room air wheel. The other end of the motor shaft drives the combustion air wheel that
delivers the required air to the burner for combustion.
The limit switch is an in-line device which protects the furnace from over heating conditions. The
contacts in the limit switch open at a given temperature setting, shutting off power to the ignition
system which controls the gas valve.
As the room air wheel comes up to speed, air flow closes
the
sail switch completing the circuit. The sail switch is
placed
into the system as a safety to prove there is adequate air
for combustion.
The next operation is controlled by the Direct Spark
Ignition, (DSI) system
as power is applied to the DSI board. The system will do
the following.
1.
The board has a timing circuit which allows the
blower
topurge the chamber of any products of combustion or
gas.
2.
The board will then apply power to the gas
valve.
At thesame time it produces a high voltage power supply to the electrode producing spark at
the burner.
3.
The board will also confirm the presence of a flame. Ifthe flame is not sensed after
7 seconds, the module will try two (2) more times and then go into lock-out. The flame is
sensed through the spark wire and electrode.
When the thermostat has reached the set point with the room air temperature,
the contacts will open removing power from the controls. The blower will remain
on until the relay opens and stops the motor.
NOTE: On some models, sail switch is before limit switch.
Sequence of Operation for Fan Control Module Board
Part Number 520820
Time Line
Description - Sequence of Events
Содержание DD-17DSI
Страница 7: ...7 SH VENT ASSEMBLY INSTALLATION SF and SH SERIES Figure 2 SF Figure 2A...
Страница 8: ...8 SH and SHD 2542 VENT ASSEMBLY INSTALLATION SF and SH SERIES Figure 3 SF Figure 3A...
Страница 9: ...9 SH VENT ASSEMBLY INSTALLATION SFV Figure 4 SF Figure 4A...
Страница 10: ...10 Figure 5A Figure 5...
Страница 11: ...11 Figure 6...
Страница 13: ...VENT ASSEMBLY INSTALLATION NT SERIES 13 NT 12 16 20S and SE NT 12 16S Figure 8 NT 12 16 20SE Figure 9 Figure 10...
Страница 14: ...VENT ASSEMBLY INSTALLATION NT SERIES 14 NT 20S Figure 11 Figure 12...
Страница 16: ...16 VENT ASSEMBLY INSTALLATION NT 40 and P 40 P 40 Figure 16 NT 40 Figure 17...
Страница 19: ......
Страница 20: ......
Страница 21: ......
Страница 22: ......
Страница 23: ......
Страница 24: ......
Страница 25: ......
Страница 26: ......
Страница 27: ......
Страница 39: ...39 Figure 26 Local Flame Sense SF Models With Time Delay Figure 27 Fan Control Board NT 12 16 20S and SE...
Страница 40: ...40 Figure 28 Fan Control Board NT 24 30 34SP and NT 40 Figure 29 Fan Control...
Страница 41: ...41 P 30S Figure 30 Fan Control Board P 40...
Страница 46: ...46 Figure 36 Figure 37...