background image

Form I-XE/CRGB/RPB, Page 14

Heater

Duct

Access Panel

in Duct

(152mm)

10” (254mm)

1

2

3

“U” Channel

(See FIGURE 15.)

WARNING

This appliance is equipped for a maximum gas sup-
ply pressure of 1/2 psi, 3.5 kPa, or 14 inches water
column. Supply pressure higher than 1/2 psi re-
quires installation of an additional service regula-
tor external to the unit.

PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI:

 Disconnect the heater and manual

valve from the gas supply line which is to be tested. Cap or plug the
supply line.

Test Pressures Below 1/2 PSI: 

Before testing, close the manual

valve on the heater.

FIGURE 14 - Connecting Supply Air Duct to the Furnace

(1) Flanges on the furnace (heat exchanger) turn out as shown. (2)
Shape duct connection as shown - "U" on top and bottom; "L" on
sides. (3) Slide "U" channels over furnace top and bottom flanges
making connection. Form "U" channels to seal sides. 

Drill and lock

with sheetmetal screws.

Furnace

Duct

“U” Channel of

Light Gauge Metal

FIGURE 15 -
Install "U"
Channel on
Sides of Duct
Connection

11. Gas Piping and Pressures

All piping must be in accordance with requirements outlined in the
National Fuel Gas Code ANSI/Z223.1a (latest edition) or CSA-B149.1
and B149.2 (See Paragraph 1). Gas supply piping installation should
conform with good practice and with local codes.
Duct furnaces for natural gas are orificed for operation with gas having
a heating value of 1000 (±50) BTUH per cubic ft. If the gas at the
installation does not meet this specification, consult the factory for
proper orificing.

Bottom Duct/Furnace Connections

 - On outdoor models, insert

ducts from below roof deck through roof opening into the heater.
Form 1" (25mm) flanges, fold over, and fasten with sheetmetal screws
inside heater. Gain access to the unit by removing side panels from
the blower and downturn plenum sections. Ducts must be attached
and sealed to provide airtight connections.

Return Air Duct/Furnace Connection

 - All return air ducts should

be attached and sealed to return air flanges to provide airtight con-
nection.

Return Air Duct/Grill Size

 - Make certain that return air ducting

or grills have a free area equal to the return duct size connection.

18”

(457mm)

3/4”

(19mm)

3/4”

(19mm)

G

FIGURE 13 - Duct Connection

Dimensions (inches/mm) for

Horizontal Discharge

(See Paragraph 4 for bottom duct connection sizes.)

inches mm

75, 100

12-1/2

318

125

15-1/4

387

150, 175

20-3/4

527

200, 225

26-1/4

667

250, 300

34-1/2

876

350

40

1016

400

45-1/2 1156

G

S ize

Through Masonry Walls

 - No warm air duct should come in con-

tact with masonry walls. Insulate around all air duct through ma-
sonry walls with not less than 1/2" (1" is recommended) of insula-
tion.

Through Unheated Space

 - Insulate all exposed warm air ducts

passing through an unheated space with at least 1/2" (1" is recom-
mended) of insulation.

Duct Supports

 - Suspend all ducts securely from adjacent buildings

members. Do not support ducts from unit duct connections.

Duct Sizing

 - Proper sizing of the supply air ductwork is necessary

to ensure a satisfactory heating installation. The recognized author-
ity for such information is the Air Conditioning Contractors Asso-
ciation, 2800 Shirlington Road, Suite 300, Arlington, VA 22206
(www.acca.org). A manual covering duct sizing in detail may be
purchased directly from them.

CAUTION: An external duct system static pressure not within
the limits shown on the rating plate, or improper motor pulley
or belt adjustment, may overload the motor. See Hazard Levels,
page 2.

Removable Panels

 - The ducts should have removable access pan-

els on both upstream and downstream sides of the furnace. These
openings must be accessible when the furnace is in service and should
be a minimum of 6" x 10" in size so smoke or reflected light may be
observed inside the casing to indicate the presence of leaks in the
heat exchanger. The covers for the openings must be attached in such
a manner as to prevent leakage. See 

FIGURE 14

.

Horizontal Discharge Duct Length - On indoor, gravity-vented
Model XE

, a 

minimum

 horizontal duct length of 18" (457mm) is

required

 at the furnace discharge before any vertical rise is made in

front of the drafthood relief opening. This is required to prevent
interference with the builtin drafthood. 

For all installations

 with a

horizontal discharge, a minimum horizontal duct run of 24" (610mm)
is 

recommended

 before turns or branches are made in the duct

system to reduce losses at the furnace outlet.

10. Duct Connections (cont'd)

Requirements and Suggestions (cont'd)

Supply Air Duct/Furnace Horizontal Connection

 - The seal be-

tween the furnace and the duct must be mechanical. Duct connection
should be made with "U" type flanges on the top and bottom of the
connecting duct. Slide the duct over the flanges of the heater giving
an airtight fit. Provide "U" type channels for the other side flanges to
ensure tight joints. Use sheetmetal screws to fasten ducts and "U"
channels to the furnace flange. See 

FIGURES 14 and 15

.

CAUTION: Joints where supply air ducts attach to the furnace
must be sealed securely to prevent air leakage into drafthood
or burner rack area. Leakage can cause poor combustion,
pilot problems, shorten heat exchanger life and cause poor
performance. See Hazard levels, page 2.

Содержание CRGB Series

Страница 1: ...AquaSaver Timer Adjustment 34 Belts 24 Blocked Vent Switch 25 Blower Motors 24 Blower Rotation 24 Burner Air Adjustment 30 Burner Rack Removal 42 Burners 29 Carryover System 29 Check Installation and...

Страница 2: ...rhalogenatedhydrocarbonsorany contaminant silicone aluminium oxide etc that adheres to the spark ignition flame sensing probe b Wiring is not in accordance with the diagram furnished with the heater c...

Страница 3: ...x 19 1 2 495mm Return Air Openings with Optional Cabinet X Hanger Centerline Standard and Optional Blower Cabinet Dimensions inches andmm Gravity Vented Indoor Models XE HXE Gas Connection Natural Pr...

Страница 4: ...side the downturn plenum cabinet For dimensions with downturn plenum cabinet with a cooling coil cabinet see page 6 FIGURE1B Dimensions Outdoor Gravity VentedModel Series CRGB Vent Cap Gas Connection...

Страница 5: ...ottom of cabinet side If system has a cooling coil cabinet add length dimension on page 6 for full system length The two position discharge dampers in Option AQ8 fit in the discharge air opening The d...

Страница 6: ...ownturnPlenumCabinet factoryattachedto either type of Cooling Coil Cabinet Front View DX Coil Cabinet with Horizontal Discharge Option AU3 Liquid Line Connections 7 8 or 1 3 8 5 1 8 130 8 203 3 4 19 3...

Страница 7: ...r from inside the building openings 1 square inch free area per 1000 BTUH Never less than 100 square inches free area for each open ing See 1 in FIGURE 2 2 Air from outside through duct openings 1 squ...

Страница 8: ...the pipe hanger to a 1 threaded pipe See the suspension method on the left in FIGURE 4 As an alternative method the factory installed pipe hanger may be removed and the heater suspended as illustrated...

Страница 9: ...lled 1 Position curb cross rails and curb side rails as illustrated in FIGURE 8 page 10 If there are two side pieces to a side fasten them with splice plates and hardware as illustrated in the splicin...

Страница 10: ...e is horizontal If the system has an AU11 AU12 AU13 AU14 cooling coil cabinet there is a downturn plenum with vertical discharge Options AU2 AU3 AU11 AU12 AU13 and AU14 are not factory installed Optio...

Страница 11: ...should be supported every six feet 1 8M using a non combustible material such as strap steel or chain Do not rely on the drafthood or heater for support of either horizontal or vertical vent pipe 6 V...

Страница 12: ...re horizontal venting is required or where negative building pressure inhibits gravity venting in stall an optional power venter Option CA Use only a power venter provided by the furnace manufacturer...

Страница 13: ...mmended size is 1 2 x1 2 20 gauge FIGURE11B InstallationoftheVentCap includedinthe optionpackage andthefield suppliedPipingandSupports Oval Adapter Assy PN 103025 Venter Seal Plate P N 43446 9 Condens...

Страница 14: ...air duct should come in con tact with masonry walls Insulate around all air duct through ma sonry walls with not less than 1 2 1 is recommended of insula tion Through Unheated Space Insulate all expo...

Страница 15: ...l connections are made disconnect the pilot supply at the control valve and bleed the system of air Reconnect the pilot line and leak test all connections by brushing on a soap solution WARNING All co...

Страница 16: ...ding MUST be made in accordance with the National Electric CodeANSI NFPANo 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer should be a...

Страница 17: ...ontrols available as part of the gas and air control options Check the wiring diagram and literature supplied with the unit for operation of factory installed optional controls See FIGURE 19 for locat...

Страница 18: ...ND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO TEMPERATURE RATING OF AT LEAST 105 C EXCEPT FOR MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A 4 CAUTION IF ANY OF THE ORIGIN...

Страница 19: ...W LEADS CAP RED 8 USE 18 GA WIRE FOR 24 VOLT CONTROL WIRING ON UNIT NONE NOTES 4 CAUTION IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MAT...

Страница 20: ...L WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOLLOWING CONTROLS ARE SUP...

Страница 21: ...N IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE 3 DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED 2 THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT 1 THE FOL...

Страница 22: ...E SAFETY SWITCH PORTION OF THE CONTROL THE SWITCH ACTION PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZED THE A PILOT FLAME ON EACH OPERATING CYCLE THE SENSING PROBE ENERGIZING THE PILOT GAS VALVE...

Страница 23: ...ND ENERGIZES THE MAIN VALVE THE MAIN GAS IGNITES AND THE UNIT FIRES AT LOW RATE 3 ON A CALL FOR HEAT BY THE HIGH STAGE OF THERMOSTAT THE UNIT FIRES AT FULL RATE 4 IF THE FLAME IS EXTINGUISHED DURING M...

Страница 24: ...outlet temperature turn the adjustable half of the pulley outward One turn of the pulley will change the speed 8 10 5 Tighten the setscrew on the flat portion of the pulley shaft 6 Replace the belt an...

Страница 25: ...ing pressure levels off If a restriction or excessive flue length or turns cause the sensing pres sure to become less than the switch setpoint the pressure switch will function to shut off the main bu...

Страница 26: ...e same as the one illustrated 1 Remove the access panel in the ductwork adjacent to the control compartment access panel 2 Element is retained by spring clips 3 Round gasket and metal retaining plate...

Страница 27: ...IGURE24 Signal Conditioner used in Options AG21 and AG40 Carryover Regulator Modulating Valve Single Stage Gas PrimaryGas FlowPressure Switch WhiteLabel 1 1 w c GasFlow PressureSwitch WhiteLabel 1 1 w...

Страница 28: ...per open Is there voltage between Terminal 88 and Terminal 7 Is there voltage between Terminal 4 on ignition permissive relay and Terminal 7 Replace 1 time delay relay Replace ignition permissive rela...

Страница 29: ...6 38mm 79 23 32 18 25mm 7 16 1 16 11mm 1 6 Option AH2 and spark pilot with lockout is Option AH3 NOTE Outdoor units in Canada using propane require lockout Indoor units in U S and Canada using propane...

Страница 30: ...ers cont d INDOOR Gravity Vented Furnace Models XE HXE Natural gas burners are equipped with two flash carryover systems that receive a supply of gas simultaneously with the main burner NOTE A natural...

Страница 31: ...esuppliedwithairforcombustionasrequired by Code and in Paragraph 6A of this heater installation manual MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND PROPERLYOPERATINGCONDITION lockout control if...

Страница 32: ...3 Bottom Panel Position the air hood bottom panel so that it is to the inside of the two side panels and above the factory installed support angle Attach to the side panels If the bottom panel does n...

Страница 33: ...ecessary Follow these instructions to field connect the water supply and make neces sary checks and adjustments before operating the cooling module with a lock nut and a sealing gasket Check these fit...

Страница 34: ...ockwise to increase the ON time or counterclockwise to decrease the ON time One complete turn will adjust the cycle by 12 to 14 seconds All Modules Check the reservoir for any water leaks The reservoi...

Страница 35: ...e the water feed line from the downstream side of the ball valve and unscrew the water bleed line barbed hose fitting 3 Force a fresh water supply through the water inlet hose and thoroughly flush the...

Страница 36: ...let DamperOptionsonIndoor ModelsXE HXE FIGURE 41B Location of Controls for30 OutsideAirHood andDamperOptions AR6orAR7 OutdoorModelsonly FIGURE41D Exampleof OutsideAirand Return Air Damper Linkage Damp...

Страница 37: ...w c Heater Filter Size Metal Fillers Size A B C D E F1 F2 75 100 125 20x20 20x20 150 175 20x25 20x25 13 16 13 16 200 225 16x25 16x20 16x25 16x20 250 300 20x25 20x20 20x25 20x20 350 20x25 20x25 20x25...

Страница 38: ...B D D E 25 635mm 20 508mm 20 508mm 25 635mm Size 350 D D D C C Size 400 25 635mm 20 508mm B D Key Filter Code Filter Size A 16 x 20 B 20 x 20 C 16 x 25 D 20 x 25 E 25 x 25 Shaded areas are filter blo...

Страница 39: ...d with op tional discharge dampers the damper motor wires must be connected to the terminal blocks in the furnace electrical compartment If the coil cabinet being installed does not include a downturn...

Страница 40: ...ection remove the center hole plug FIGURE 46H To install side and top fillerpanels remove screws from top corners of both cabinets and the entire row across the cooling coil cabinet Removerowofscrews...

Страница 41: ...or lint accumulation Clean as needed Check the vent system for soundness Replace any parts that do not appear sound Check the wiring for any damaged wire Replace damaged wiring See Paragraph 12 for re...

Страница 42: ...ryover systems with air pressure 40 Cleaning the Heat Exchanger To clean the outer surfaces circulating air side of the heat exchanger gain access by removing the inspection panels in the ductwork or...

Страница 43: ...causes 8 Reset lockout by interrupting control at thermostat 9 Faulty combustion air proving switch 9 Replace combustion air proving switch 10 Activated blocked vent switch indoor system 10 Correct ve...

Страница 44: ...AG39 or AG40 see page 28 For replacement parts refer to Form P X XE for indoor units or Form P RG RP RBL for outdoor units Problem Probable Cause Remedy Pump does not run Unit is 1 Electrical connecti...

Отзывы: