OK / Set
-
!
GND
S1
S2
S3
S4
S5
S7
S6
S8
CS10
Sensors
L N
L'
R7-A
R7-M
R7-R
floating relay
R3
R2
R1
semiconductor
Bus
VBus
S9
S10
R6
R5
R4
1 (1) A (100 ... 240) V~
4 (1) A (100 ... 240) V~
R1-R6
R7
V40
DIn
T4A
IP 20
Vor Öffnen Gerät spannungslos
schalten!
Isolate mains before removing cover!
Masse-Sammelklemme benutzen
Use ground common terminal block
Erdungsleiter-Sammel-
klemme benutzen!
Use ground common
terminal block!
Neutralleiter-
Sammelklemme benutzen!
Use neutral conductor
collective block!
Netz / Mains 100 ...
240
V~
50-60 Hz
N
Made in Germany
DeltaSol E
®
1.1 Mounting to walls
1. Installation
1.2
Electrical connection
VBus
®
neutral conductor -
common terminal block
grounding conductor -
common terminal block
power supply terminals
fuseT4 A
(supply to all relays)
sensor terminals
load terminals
sensor -
ground-common terminal block
1.2.1 Overview of electrical connections
fastening
fastening
display
push button
fuse T4A
front cover
push-push locking mechanism
push to open
push to close
screw
135 mm
144 mm
The unit must only be located in dry interior locations. It
is not suitable for installation in hazardous locations and
should not be placed close to any electromagnetic fields. The
controller must additionally be supplied from a double-pole
switch with contact gap of at least 0.12" / 3 mm. Please pay
attention to separate routing of sensor cables and power
supply cables.
Î
Open the front cover by pushing it. Unscrew the cross-
head screw from the cover and remove it along with
the front cover from the housing.
Î
Mark the upper fastening point on the wall and drill
and fasten the enclosed wall plug and screw leaving the
head protruding.
Î
Hang the housing from the upper fastening point and
mark the lower fastening point through the hole in
the terminal box (centers on 5,3" / 135 mm). Drill and
insert the lower wall plug.
Î
Hang the housing from the upper fastening point and
attach with the lower screw.
Î
Complete wiring connections in accordance with
terminal allocations.
Î
Insert cover and attach with the cross-head screw.
Close the front cover properly.
WARNING! Electric shock!
Opening the housing will expose
live parts!
Î
Switch off power supply and dis-
connect the device from power
supply before opening the housing!
D e lt a S o l
®
E
© RESOL 10306_DeltaSol_E.mon
us.ind
d
|
4