background image

en

29

Sensor/
terminal

Designation

Description

S1

TCOL1

Temperature collector 1

S2

TST1B

Temperature tank 1 base

S3

TCOL2

Temperature collector 2

S4

TST2B

Temperature tank 2 base

S5

Optional sensor for measure-
ment purposes or options

V40

Relay

Description

R1

Solar pump collector 1

R2

Solar pump collector 2

R3

3-port valve tank 1/2

R4

optional:
Thermal disinfection 
Parallel relay 
Heat dump

The controller compares the temperatures at the collector sensors S1 and S3 to 
the temperatures at S2 and S4. If one of the measured temperature differences is 
higher than the adjusted switch-on temperature differences, the corresponding 
pump (R1, R2) or both pumps will be activated and the corresponding tank will be 
loaded up to the adjusted maximum temperature via the valve (R3). 

PWM 

B

PWM 

A

System 8
Solar system with east-/west collectors and 2 tanks (valve logic)

Note: 3-port valve normally open - tank 1 (S2)

Содержание DeltaSol BX L

Страница 1: ...om this unit Please keep this manual carefully DeltaSol BX L www resol com Manual Installation Operation Functions and options Troubleshooting Manual for the specialized craftsman 11210575 11210575 Th...

Страница 2: ...not exposed to strong electromagnetic fields Target group These instructions are exclusively addressed to authorized skilled personnel Only qualified electricians should carry out electrical works In...

Страница 3: ...w 4 2 Installation 5 2 1 Mounting 5 2 2 Electrical connection 5 2 3 Data communication Bus 6 2 4 SD memory card slot 6 2 5 Overview of basic system layouts 7 2 6 Systems 8 3 Operation and function 36...

Страница 4: ...lse voltage 2 5 kV Data interface RESOLVBus SD card slot VBus current supply 35 mA Functions T control pump speed control energy metering operating hours counter for the solar pump evacuated tube coll...

Страница 5: ...g in accordance with the terminal allocation see chap 2 2 Put the cover on the housing Attach with the fastening screw cover screw 2 2 Electrical connection WARNING Electric shock Upon opening the hou...

Страница 6: ...e 7 Note For more details about the commissioning procedure see page 40 2 3 Data communication Bus The controller is equipped with a RESOL VBus for data transfer and energy supply to external modules...

Страница 7: ...age 14 2 tank solar system with pump logic and heat exchange control page 17 3 tank solar system with valve logic and heat exchange control page 20 3 tank solar system with pump logic and heat exchang...

Страница 8: ...to the adjusted switch on temperature difference the pump R1 will be switched on and the tank will be loaded until the switch off temperature difference or the maximum tank temperature is reached Sen...

Страница 9: ...se 2 46 S2MAX 60 C 140 F Tank maximum limitation 2 46 SMXS2 4 Sensor tank max 2 46 LST2 ON Loading tank 2 47 COL Collector CEM 130 C 270 F Collector emergency temperature 48 OCCO OFF Collector cooling...

Страница 10: ...OFF Tank cooling 55 OHDP OFF Heat dump 56 ODTFT T function option 58 OTH Thermostat function option 61 PUMP Speed PUMP1 PSOL Speed variant pump 1 47 PUMP2 PSOL Speed variant pump 2 47 PUMP3 OnOF Spee...

Страница 11: ...es the temperature at sensor S1 to the temperatures at sensors S2 and S4 If the measured temperature differences are higher than the adjusted switch on temperature differences the pump R1 will be acti...

Страница 12: ...x 2 46 LST2 ON Loading tank 2 47 COL Collector CEM 130 C 270 F Collector emergency temperature 48 OCCO OFF Collector cooling option 48 CMAX 110 C 230 F Collector maximum temperature 48 OCMN OFF Collec...

Страница 13: ...58 0 C 135 0 F Switch off temperature maximum limitation 57 MIN4O 5 0 C 42 0 F Switch on temperature minimum limitation 58 MIN4F 10 0 C 50 0 F Switch off temperature minimum limitation 58 OTH Thermos...

Страница 14: ...ar pump tank 1 R2 Solar pump tank 2 R3 optional Thermal disinfection Parallel relay Heat dump R4 The controller compares the temperature at sensor S1 to the temperatures at sensors S2 and S4 If the me...

Страница 15: ...0 C 140 F Tank maximum limitation 2 46 SMXS2 4 Sensor tank max 2 46 LST2 ON Loading tank 2 47 COL Collector CEM 130 C 270 F Collector emergency temperature 48 OCCO OFF Collector cooling option 48 CMAX...

Страница 16: ...ons OSYC OFF System cooling 55 OSTC OFF Tank cooling 55 OHDP OFF Heat dump 56 ODTFT T function option 58 OTH Thermostat function option 61 PUMP Speed PUMP1 PSOL Speed variant pump 1 47 PUMP2 PSOL Spee...

Страница 17: ...ump The controller compares the temperature at sensor S1 to the temperatures at sensors S2 and S4 If the measured temperature differences are higher than the adjusted switch on temperature differences...

Страница 18: ...ading tank 2 47 COL Collector CEM 130 C 270 F Collector emergency temperature 48 OCCO OFF Collector cooling option 48 CMAX 110 C 230 F Collector maximum temperature 48 OCMN OFF Collector minimum limit...

Страница 19: ...limitation 57 MAX4F 58 0 C 135 0 F Switch off temperature maximum limitation 57 MIN4O 5 0 C 42 0 F Switch on temperature minimum limitation 58 MIN4F 10 0 C 50 0 F Switch off temperature minimum limit...

Страница 20: ...n Zustand Valve logic Flow direction when the valve is normally open The controller compares the temperature at sensor S1 to the temperatures at sensors S2 S4 and S5 If the measured temperature differ...

Страница 21: ...tank max 2 46 LST2 ON Loading tank 2 47 LOAD3 Loading 3 DT3O 6 0 K 12 0 Ra Switch on temperature difference 3 46 DT3F 4 0 K 8 0 Ra Switch off temperature difference 3 46 DT3S 10 0 K 20 0 Ra Set tempe...

Страница 22: ...FF Pause speed option 54 PDELA OFF Pump delay option 54 COOL Cooling functions OSYC OFF System cooling 55 OSTC OFF Tank cooling 55 OHDP OFF Heat dump 56 OTH Thermostat function option 61 PUMP Speed PU...

Страница 23: ...ar pump tank 3 R4 optional Thermal disinfection Parallel relay Heat dump The controller compares the temperature at sensor S1 to the temperatures at sensors S2 S4 and S5 If the measured temperature di...

Страница 24: ...2 0 Ra Switch on temperature difference 3 46 DT3F 4 0 K 8 0 Ra Switch off temperature difference 3 46 DT3S 10 0 K 20 0 Ra Set temperature difference 3 46 RIS3 2 K 4 Ra Rise 3 46 S3MAX 60 C 140 F Tank...

Страница 25: ...5 min Circulation runtime 51 PSPEE OFF Pause speed option 54 COOL Cooling functions OSYC OFF System cooling 55 OSTC OFF Tank cooling 55 OHDP OFF Heat dump 56 OTH Thermostat function option 61 PUMP Spe...

Страница 26: ...he valve is normally open The controller compares the temperature at sensor S1 to the temperatures at sensors S2 S3 and S4 If the measured temperature differences are higher than the adjusted switch o...

Страница 27: ...46 LST2 ON Loading tank 2 47 LOAD3 DT3O 6 0 K 12 0 Ra Switch on temperature difference 3 46 DT3F 4 0 K 8 0 Ra Switch off temperature difference 3 46 DT3S 10 0 K 20 0 Ra Set temperature difference 3 4...

Страница 28: ...untime 51 PSPEE OFF Pause speed option 54 PDELA OFF Pump delay option 54 COOL Cooling functions OSYC OFF System cooling 55 OSTC OFF Tank cooling 55 OHDP OFF Heat dump 56 OTH Thermostat function option...

Страница 29: ...ermal disinfection Parallel relay Heat dump The controller compares the temperatures at the collector sensors S1 and S3 to the temperatures at S2 and S4 If one of the measured temperature differences...

Страница 30: ...48 OCCO1 OFF Collector cooling option 1 48 CMAX1 110 C 230 F Maximum collector temperature 1 48 OCMI1 OFF Collector minimum limitation option 1 49 CMIN1 10 0 C 50 0 F Minimum collector temperature 1 4...

Страница 31: ...ause speed option 54 PDELA OFF Pump delay option 54 COOL Cooling functions OSYC OFF System cooling 55 OSTC OFF Tank cooling 55 OHDP OFF Heat dump 55 OTH Thermostat function option 61 PUMP Speed PUMP1...

Страница 32: ...alve logic Flow direction when the valve is normally open The controller compares the temperatures at the collector sensors S1 and S3 to the tank temperatures at the sensors S2 S4 and S5 If one of the...

Страница 33: ...difference 3 46 DT3F 4 0 K 8 0 Ra Switch off temperature difference 3 46 DT3S 10 0 K 20 0 Ra Set temperature difference 3 46 RIS3 2 K 4 Ra Rise 3 46 LST3 ON Loading tank 3 47 COL 1 Collector CEM 130 C...

Страница 34: ...Tank set option 53 TST1 45 C 120 F Set tank temperature tank 1 53 TST2 45 C 120 F Set tank temperature tank 2 53 TSTS3 45 C 120 F Set tank temperature tank 3 53 tLB 2 min Loading break time 51 tRUN 15...

Страница 35: ...tion to the relay connection the pump must also be connected to the controller via the VBus PWM interface adapter In the PUMP adjustment channel ADAP has to be selected R1 S2 S1 Temp Sensor Pt1000 L R...

Страница 36: ...ture Status level TCOL TST1B Menu level ARR LOAD1 LOAD2 LOAD3 COL COL1 COL2 LLOGI Adjustment level DT O DT F DT S RIS S MAX SMXS The menu structure of the controller consists of 3 levels the status le...

Страница 37: ...ment display channel values and the adjustment parameters are displayed Temperatures and temperature differences are indicated with the unit C F or K R respectively Tool bar The additional symbols in...

Страница 38: ...monitoring display The system selected is indicated in the system monitoring display It consists of several system component symbols which are depending on the current status of the system either fla...

Страница 39: ...ction active TCOL Temperature collector TCOL1 Temperature collector 1 TST1B Temperature tank 1 base TSTT Temperature tank top S3 Temperature sensor 3 TST2B Temperature tank 2 base TST3B Temperature ta...

Страница 40: ...tialization phase in which all symbols are indicated in the display The directional pad flashes red When the controller is commissioned for the first time or when it is reset it will run a commissioni...

Страница 41: ...stems with two 3 port valves ARR 5 7 9 Complete the commissioning menu by pressing button 5 The controller is then ready for operation and nor mally the factory settings will give close to optimum ope...

Страница 42: ...e tank 2 base in 3 tank systems only TST3B Temperature tank 3 base Display of temperatures at S3 S4 and S5 S3 S4 S5 Sensor temperatures Display range 40 260 C 40 0 500 0 F Indicates the current temper...

Страница 43: ...r to finish the reset In order to interrupt the RESET process do not press any button for about 5 s The display returns to the display mode Display of heat quantity kWh MWh Heat quantity in kWh MWh In...

Страница 44: ...arting delay time has been adjusted the adjusted delay time is displayed flashing in this channel Display of heating period TDIS Heating period Display range 0 00 23 59 hh mm If the thermal disinfecti...

Страница 45: ...ons and adjustments which can be activated or changed respectively if necessary Select the system first see chap 3 T control LOAD 1 2 3 DT1 2 3 O Switch on temperature diff Adjustment range 1 0 50 0K...

Страница 46: ...re difference decreases by the adjustable rise value RIS the pump speed decreases by 10 Maximum tank temperature LOAD 1 2 3 S1 2 3 MAX Maximum tank temperature Adjustment range 4 95 C 40 200 F in step...

Страница 47: ...PULS Burst control via semiconductor relay Adjustment for a high efficiency pump HE pump with speed control via adapter PSOL PWM signal PWM A for R1 PWM B for R2 ADAP Pump on pump off the correspondi...

Страница 48: ...omponents against overheating collector emergency shutdown If the maximum collector temperature is exceeded is displayed flashing Collector cooling COL 1 2 OCCO 1 2 Selection OFF ON Factory setting OF...

Страница 49: ...erature prevents the pump from being switched on too often at low collec tor temperatures If the collector temperature falls below the adjusted minimum temperature is displayed flashing Evacuated tube...

Страница 50: ...ment If the runtime TCRU is set to more than 10 s the pump will be run at 100 for the first 10 s of the runtime For the remaining runtime the pump will be run at the adjusted minimum speed nLO If the...

Страница 51: ...be switched off Note This function can only become active if the tank temperature is higher than the collector temperature Note Since this function uses the limited heat quantity of the tank the anti...

Страница 52: ...loaded up to its maximum temperature first Only when the priority tank is fully loaded will the subordinate tank s next in priority be loaded 3 In progressive loading StUF the tank with the lowest te...

Страница 53: ...If the selected priority tank reaches its set temperature the subordinate tanks will be loaded successively up to their set temperatures After that the priority tank is loaded up to its maximum tempe...

Страница 54: ...ory setting OFF If the pause speed is activated the relay of the tank which has been loaded last remains switched on during the loading break time Speed is determined by the value adjusted in nLO LLOG...

Страница 55: ...tank temperature is higher than the adjusted maximum tank temperature and the switch on temperature difference DTCO is reached the solar system remains activated or is switched on Solar loading is co...

Страница 56: ...ad justed collector overtemperature OTCL the relay will be switched off A selection can be made between pump logic and valve logic OTPUM ON pump logic OTPUM OFF valve logic If pump logic is selected...

Страница 57: ...um limitation Additionally minimum and maximum temperature limitations and the correspond ing switch on and switch off differences can be set for the independent tempera ture differential control Both...

Страница 58: ...ection ON OFF Factory setting OFF The optional T function uses the senors S3 heat source and S5 heat sink to switch the adjustable relay Note The optional T function is available in system 1 and 3 onl...

Страница 59: ...F in steps of 0 5 C 1 0 F Factory setting 50 0 C 125 0 F If the temperature falls below the adjusted value TH2O the relay will be switched on If the temperature exceeds the adjusted value TH2F the re...

Страница 60: ...eps of 15 minutes If the switch on and the switch off times are identical the time frame is inactive If the thermostat function should run from 06 00 a m and 09 00 a m only adjust t1O to 06 00 a m and...

Страница 61: ...nt value MAN The following adjustments can be carried out Auto relay in automatic mode ON relay is switched on OFF relay is switched off nLO relay is switched with adjusted minimum speed nHI relay is...

Страница 62: ...rature at the reference sensor falls below the disinfection temperature When the monitoring period ends the reference relay activates the backup heating The disinfection period starts to count as soon...

Страница 63: ...gins If the starting time is adjusted to 00 00 factory setting the delay function is inactive When thermal disinfection is activated different display channels appear depending on the current status o...

Страница 64: ...ow rate value or with aV40 flowmeter Enable the energy metering option in the channel OHQM Select the type of flow rate detection in the channel FTYPE Flow rate detection type 1 fixed flow rate value...

Страница 65: ...rgy metering withV40 flowmeter The energy metering calculation uses the difference between the flow and return temperatures and the volume flow transmitted by the flowmeter Adjust 2 in the channel FTY...

Страница 66: ...Factory setting 15 The date and time can be entered Both are required for the thermostat function ROSA ROSA ROSA numbers Adjustment range 0000 9999 In the ROSA channel the 4 digit number given by the...

Страница 67: ...valve is normally open Temperature unit UNIT Temperature unit Adjustment range C F Factory setting C In this adjustment channel the temperature unit can be chosen The unit can be switched between C an...

Страница 68: ...the menu item REMC After REM is displayed remove the card from the slot OSDC FORM Format card Formatting the SD card Select the menu item FORM During the formatting process FORM will be displayed The...

Страница 69: ...difference 58 RIS4 2 K 4 Ra T function rise 59 TH1O 65 0 C 150 0 F Thermostat function 1 switch on temperature 59 TH1F 60 0 C 140 0 F Thermostat function 1 switch off temperature 59 TH2O 45 0 C 120 0...

Страница 70: ...or disinfection 63 OTDIS ON Deactivation Thermal disinfection 63 OPARR Parallel relay option 63 PARRE 2 Parallel relay 63 INVER OFF Inversion 63 OHQM Energy metering option 64 FTYPE 1 Flow rate detect...

Страница 71: ...Set temperature difference tank 1 S2MAX 60 4 95 C 40 200 F Tank maximum limitation tank 1 LST2 On On OFF Loading tank 2 on DT3O 6 1 0 50 0 K 2 0 90 0 Ra Switch on temperature difference tank 2 DT3F 4...

Страница 72: ...Please check if the resistance values correspond with the table Directional pad flashes red The symbol is indicated on the display and the symbol flashes Sensor fault An error code instead of a tempe...

Страница 73: ...between tank and collector increases enormously during operation the collector circuit cannot dissipate the heat Collector circuit pump defective no yes Heat exchanger calcified Check replace it Deca...

Страница 74: ...ght is higher than the outdoor temperature no yes Controller might be defective replace it Is the pump stuck Turn the pump shaft using a screw driver now passable Pump is defective replace it yes no D...

Страница 75: ...measured temperature difference with the help of pre defined parameters glycol type concentration heat capacity etc 10 2 Interface adapters Interface adaptersVBus USB andVBus LAN The newVBus USB inter...

Страница 76: ...made of antireflective filterglass and is printed with a light resistant UV lacquering The universal RESOL VBus allows the parallel connection of 8 large displays as well as additionalVBus modules AM1...

Страница 77: ...2 47 M Manual mode 61 Maximum speed 48 Maximum tank temperature 46 Maximum temperature limitation 57 Minimum collector limitation 49 Minimum speed 47 Minimum temperature limitation 58 Monitoring peri...

Страница 78: ...en 78...

Страница 79: ...en 79...

Страница 80: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Отзывы: