OTH / STH
Thermostatic backup heating sensor
Selection: S3, S5
Factory setting: S3 / S5
Depending on the system selected, the sensor for the thermostatic backup heating
can either be selected or is pre-set.
OTH / RTH
Thermostatic backup heating relay
Selection:
Factory setting: R3
Depending on the system selected, the relay for the thermostatic backup heating can
either be selected or is pre-set.
Manual mode
MAN / MAN1 (2, 3):
Adjustment range: Auto,ON, OFF, nLO, nHI
Factory setting: Auto
MAN / MAN4
Adjustment range: Auto, ON, OFF
Factory setting: Auto
For control and service work, the operating mode of the controller can be manu-
ally adjusted. For this purpose, select the adjustment value MAN.The following
adjustments can be carried out:
Auto : relay in automatic mode
ON : relay is switched on
OFF : relay is switched off
nLO : relay is switched with adjusted minimum speed
nHI : relay is switched with adjusted maximum speed
The controller is equipped with a shortcut that enables a quick access to the MAN
menu (manual mode).
Î
In order to access the MAN menu, press buttons
➅
and
➆
at the same time,
then press button
❷
.
Note
Always adjust the operating mode back to “Auto” when the control and
service work is completed.
Otherwise normal operation will not be pos-
sible.
Blocking protection
BLPR1(2, 3)
Adjustment range: ON / OFF
Factory setting: ON
In order to protect the pumps against blocking after standstill, the controller is
equipped with a blocking protection function. This function switches on the relays
one after another every day at 12:00 a.m. for 10 s at 100 %.