Sensor/
terminal
Designation
Description
S1
TCOL
Temperature collector 1
S2
TST1B
Temperature tank 1 base
S3
TCOL2
Temperature collector 2
S4
TST2B
Temperature tank 2 base
S5
TST3B
Temperature tank 3 base
V40
optional: fl owmeter
Relay
Description
R1
Solar pump tank 1
R2
Solar pump tank 2
R3
Valve tank 1/2, 3
R4
Valve tank 2/3
Ventillogik
1
2
3
4
Durchflussrichtung
im stromlosen Zustand
Ventillogik
1
2
3
4
Durchflussrichtung
im stromlosen Zustand
Valve logic
Flow direction when the
valve is normally open
The controller compares the temperatures at the collector sensors S1 and S3 to
the tank temperatures at the sensors S2, S4 and S5. If one of the measured tem-
perature differences is higher than the adjusted switch-on temperature differences,
the corresponding pump (R1, R2) will be activated and the corresponding tank will
be loaded up to the adjusted maximum temperature via the valves R3, R4. In this
system, one of the tanks can be loaded with priority.
System 9
3-tank solar system with east-/west collectors
Ventillogik
1
2
3
4
Durchflussrichtung
im stromlosen Zustand
PWM
B
PWM
A