58
en
Minimum temperature limitation for the heat exchange
DT4 / MIN4O
Switch-on temperature
Adjustment range: 0.0 … 94.5 °C [30.0 … 199.0 °F]
in steps of 0.5 °C [1.0 °F]
Factory setting: 5.0 °C [42.0 °F]
DT4 / MIN4F
Switch-off temperature
Adjustment range: 0.5 … 95.0 °C [31.0 … 200.0 °F]
in steps of 0.5 °C [1.0 °F]
Factory setting: 10.0 °C [50.0 °F]
If the temperature falls below the adjusted value MIN4O, the relay will be switched
off. If the adjusted value MIN4F is exceeded, the relay will be energized.
Δ
T function
ODTFT
Δ
T function
Selection: ON / OFF
Factory setting: OFF
The optional
Δ
T function uses the senors S3 (heat source) and S5 (heat sink) to
switch the adjustable relay.
Note
The optional
Δ
T function is available in system 1 and 3 only.
ODTFT / DT4O
Switch-on difference
Adjustment range: 1.0 … 50.0 K [2.0 … 90.0 °Ra]
in steps of 0.5 K [1.0 °Ra]
Factory setting: 6.0 K [12.0 °Ra]
ODTFT / DT4F
Switch-off difference
Adjustment range: 0.5 … 49.5 K [1.0 … 89.0 °Ra]
in steps of 0.5 K [1.0 °Ra]
Factory setting: 4.0 K [8.0 °Ra]
The switch-on and switch-off differences DT4O and DT4F are valid for this function.
Minimum limitation for the
Δ
T function
DT4 / TH10
Switch-on temperature
Adjustment range: 0.0 … 95.0 °C [30.0 … 200.0 °F]
in steps of 0.5 °C [1.0 °F]
Factory setting: 65.0 °C [150.0 °F]
Содержание DeltaSol BX L