Fig. 8.4
shows the arrangement for connecting four solar panels in parallel. This arrangement is
applicable if the solar panels are to be mounted in a
2x2
configuration as shown above. Please
note that the positioning of the junction boxes must be followed for the cables to reach the MC4
Branch Connectors. This connection requires
three (3)
pairs of MC4 Branch Connectors. When
one or multiple panels are mounted at different locations- that is, separated by a distance, the
panels must be extended with MC4 Extension Cables (sold separately).
8.3 Four panels in parallel (12V systems, 1x4 configuration)
Figure 8.5
Four RNG-100D Panels in parallel
Fig. 8.5
above shows the arrangement for connecting four solar panels in parallel. This
arrangement is applicable if the solar panels are to be mounted in a
1x4
configuration as shown
above. For this configuration you will need to purchase 4x1.5’ MC4 Solar Extension Cables. This
connection requires a
three (3)
pairs of MC4 Branch Connectors. When one or multiple panels
are mounted at different locations- that is, separated by a distance, the panels must be extended
with MC4 Extension Cables (sold separately).
Содержание Off-Grid Kit
Страница 8: ...8 Wiring 1 Unscrew battery terminals and connect battery connections...
Страница 10: ...10 4 Insert battery remote sensor block terminal and connect wires POLARITY SENSITIVE...
Страница 16: ...16...
Страница 17: ...17 Repeat for each Z Bracket in the set at each corner...
Страница 18: ...18...
Страница 20: ...20...
Страница 21: ...21 NOTE Orient panel in level plumb layout as desired before fixing in position...
Страница 23: ...23 Repeat for all brackets NOTE Seal around all edges of bracket and screws...
Страница 26: ...26 NOTE Mark all holes locations in this step as the panel must be removed for well nut insertion...
Страница 27: ...27...
Страница 29: ...29 NOTE Orient panel in level plumb layout as desired before fixing in position...
Страница 30: ...30 Repeat for all fasteners NOTE Screw has compressed and expanded the well nut binding into the roof material...
Страница 36: ...36 NOTE Start lag bolt threading by hand...
Страница 37: ...37 Rail System Construction 2 1...
Страница 38: ...38 4 3...
Страница 39: ...39 6 5...
Страница 40: ...40 Repeat for all continuous rail sets Rail Seating 7 1...
Страница 41: ...41 3 2...
Страница 42: ...42 5 4...
Страница 43: ...43 Panel Securement WARNING End clamps must be installed a minimum of 1 30 mm from the rail edges 6 1...
Страница 44: ...44 3 2...
Страница 45: ...45 5 4 NOTE Ensure that the End Clamp is spaced a minimum distance of 1 25 from rail end face...
Страница 46: ...46 Continue mid clamp procedure for each additional panel 6 7...
Страница 55: ...55 Figure 7 Figure 8...