"Settings" menu item (continued) - Expert
Manual mode - relay test
With this menu item, you can control the individual actuators (pumps, mixing valves, etc.) manually or specify
values of probes for checking.
Parameter
Selection parameter
Manual mode
Permanent / Deactivated / 15 minutes
Solar cycle pump
A01
Auto / On / Off
Speed
A01
10 % - 100 %
Pump 1st mixed cycle
A02
Auto / On / Off
Pump 3rd mixed cycle
A02.2
Auto / On / Off
Pump unmixed cycle
A03
Auto / On / Off
HW circulation pump
A04
Auto / On / Off
HW changeover valve
A10
Auto / On / Off
Changeover valve heat generator
A11
Auto / On / Off
Passive cooling
A12
Auto / On / Off
Passive cooling
A12.2
Auto / On / Off
Pump 2nd mixed cycle
A13
Auto / On / Off
Pump 4th mixed cycle
A13.2
Auto / On / Off
Mixing valve 1st mixed cycle
A20/A21
Open / Stop / Close / Auto
Mixing valve 3rd mixed cycle
A20.2/A21.2
Open / Stop / Close / Auto
Bypass valve
A22/A23
Open / Stop / Close / Auto
Bypass valve
A22.2/A23.2
Open / Stop / Close / Auto
Mixing valve 2nd mixed cycle
A24/A25
Open / Stop / Close / Auto
Mixing valve 4th mixed cycle
A24.2/A25.2
Open / Stop / Close / Auto
Auxiliary heat generator
A32
Auto / On / Off
Auxiliary heat generator
A32.2
Auto / On / Off
Alarm signal
A34
Auto / Closed / Open
Solar cycle pump status
A40
Auto / On / Off
Speed
A40
10 % - 100 %
Pump 1st mixed cycle
A41
Auto / On / Off
Speed
A41
10 % - 100 %
Pump 3rd mixed cycle
A41.2
Auto / On / Off
Speed
A41.2
10 % - 100 %
Pump unmixed cycle
A42
Auto / On / Off
Speed
A42
10 % - 100 %
Internal pump
A43
Auto / On / Off
Speed
A43
10 % - 100 %
69