Room target temperature
In order to specify the point of the summer/winter
changeover, you must first determine the value
"colder/hotter" because this is coupled with the
heating limit temperature (see "Example setting").
This parameter is used to calculate the desired
target room temperature.
The value 0.0 °C gives a desired room tempera-
ture of 20 °C.
This value can be changed from -10 °C (room
target tempe10 °C) to +10 °C (room target
tempe30 °C).
upon
Overview (user)
¯
Colder/hotter
Heating limit (summer mode)
The value required to switch off heating operation
of the heat pump can be set in the parameter "Dif-
ference from heating limit".
Overview (user)
¯
Settings
¯
Heating/cooling
¯
Mode
¯
Difference from heating limit
The value 0.0 K means that the heat pump only
switches to summer mode if the room set tempera-
ture, e.g. 20 °C, is reached at the external probe.
Please note the diagram in Fig. 9 for information
on which value should be set here.
Example setting:
The "colder/hotter" parameter (room target temper-
ature) of +2 °C means a desired room temperature
of +22 °C.
The "Difference from heating limit" parameter
(summer/winter changeover) of 7.0 K means
heating operation of the heat pump up to an out-
side temperature of +15 °C
(+22 °C room target temperature - 7.0 K "colder/
hotter" = +15 °C).
The heating operation is interrupted when the
desired heating limit is exceeded and after the time
stored for the building time constant has passed.
Only the hot water supply is still active.
The building time constant is preset by REMKO in
the factory at 10 hours. Setting the building time
constant should prevent the heat pump from
cycling. The better the building standard, the
longer the possible setting of the building time con-
stant. This value can only be changed in the expert
level and must generally only be saved once.
Expert level (password protected)
¯
Settings
¯
Heating/cooling
¯
Building adaptation
¯
Difference from heating limit
REMKO Smart-Control Touch
32