Coil surface area m2
2
3
5
7.5
15 l/min
29.4
28.7
31.3
32.9
35.0
30.1
40.2
37.5
30 l/min
43.6
41.8
52.7
51.4
63.6
61.2
98.4
86.4
Coil rating (kW)
60l/miin
59.7
55.8
76.9
76.5
97.9
91.7
132.2
126.4
15 l/min
43
55
80
91
112
130
180
225
30 l/min
29
38
48
59
62
72
99
124
Indirect heat time (mins)
60l/miin
21
28
32
39
40
50
48
62
15 l/min
0.002
0.001
30 l/min
0.004
0.008
0.006
0.007
Pressure drop through primary coil (Mpa)
60l/miin
0.032
0.044
0.025
0.03
Heat loss (kWh in 24h)
1.72
2.14
2.74
3.33
3.60
4.17
4.30
4.50
Hot water capacity (volume of water >40°C) drawn off
384
482
776
961
1206
1399
1930
2482
Weight full (kg)
505
610
964
1188
1569
1872
2445
2950
Weight empty (kg)
105
110
164
188
319
322
445
450
Max supply pressure
1.6 MPa (16 bar)
Max design pressure
0.8 MPa (8 bar)
Max operating pressure
0.6 MPa (6 bar)
Max expansion vessel charge pressure
1.0 MPa (10 bar)
Expansion relief valve setting
0.8 MPa (8 bar)
T&P valve setting
1 Mpa (10 bar), 90-95°C
Maximum primary pressure (indirect only)
0.3 MPa (3 bar)
Notes:
1. Indirect cylinders tested in conformance with BS EN 12897:2006.
2. Indirect heat up times based on a 45°C temperature rise, based on a primary flow temperature of 80°C +/- 2°C
Table 3: Inlet control kits and expansion vessel specification dependant on model
Commercial Cylinder
Volume (ltr)
Pressure Reducing Valve
Pressure Relief Valve
Single Check
Valve
400 - 500
1" Integrated inlet control valve
Содержание 1000 Indirect
Страница 2: ......
Страница 11: ......
Страница 13: ...Figure 3 Indirect wiring diagram 1 Thermostat Option 2...
Страница 15: ...Figure 4 Single phase wiring schematic...
Страница 18: ...2 port zone valve...
Страница 19: ......
Страница 24: ......
Страница 31: ......
Страница 35: ...Figure 12 Auxiliary controls...
Страница 36: ...Figure 13 Indirect controls page 18 8 Operation 8 1 General...
Страница 45: ...3 7 8 Part No See table Part No 95 605 176 9 12 13 Part No See table Part No 95 605 182...
Страница 46: ...14 15 Part No 95 607 367 Part No 95 607 425 16 18 19 21 Part No See table Part No See table...
Страница 47: ...22 23 24 Part No 95 605 192 95 605 194 Part No 95 605 103 25 26 Part No 7033371 Part No 95 612 650...
Страница 48: ...27 28 Part No 95 612 652 Part No 95 605 884 29 30 31 Part No 7031564 7031565 Part No 95 607 690...
Страница 49: ...32 33 Part No 95 607 691 Part No 95 980 025 34 35 36 Part No 95 980 009 Part No 95 607 366 95 607 404...
Страница 51: ...page 27 page 28 page 29 MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST...
Страница 52: ......
Страница 54: ......