Intermittently
Expansion vessel charge pressure has
reduced below 3.5 bar, or set too high
See Maintenance section for re-charging of expansion vessel procedure
Water discharges
from expansion valve Continually
Cold water combination valve pressure reducer not working
correctly.
Expansion valve seat damaged
Check pressure from cold water combination valve.
If greater than 3.5 bar replace pressure reducing valve cartridge.
Remove expansion valve cartridge, check condition of seat. If necessary fit new
expansion valve
Water discharges
from T&P relief
valve
Thermal control failure
CAUTION: Water will be very hot!
Switch off power to immersion heater(s) and shut down boiler.
DO NOT turn off water supply.
When discharge stops check all thermal controls, replace if faulty
Milky water
Oxygenated water
Water from a pressurised system releases oxygen bubbles when flowing.
The milkiness will disappear after a short while
11. Decommissioning
11.1 Decommissioning procedure
#
Isolate electrical supplies and make safe
#
Isolate the water supply
#
Drain the cylinder
#
Drain the primary circuit (indirect only)
#
Remove cylinder
#
Cap pipework
Environmental information
Products are manufactured from many recyclable materials. At the end of their useful life they should be disposed of at a Local Authority
Recycling Centre in order to realise the full environmental benefits.
Insulation is by means of an approved CFC/HCFC free polyurethane foam with an ozone depletion factor of zero.
page 21
12. Spare parts
12.1 Spare parts list
A full range of spare parts are available for the cylinder range. Refer to the Technical Data label on the unit to identify the model installed and
ensure the correct part is ordered.
Содержание 1000 Indirect
Страница 2: ......
Страница 11: ......
Страница 13: ...Figure 3 Indirect wiring diagram 1 Thermostat Option 2...
Страница 15: ...Figure 4 Single phase wiring schematic...
Страница 18: ...2 port zone valve...
Страница 19: ......
Страница 24: ......
Страница 31: ......
Страница 35: ...Figure 12 Auxiliary controls...
Страница 36: ...Figure 13 Indirect controls page 18 8 Operation 8 1 General...
Страница 45: ...3 7 8 Part No See table Part No 95 605 176 9 12 13 Part No See table Part No 95 605 182...
Страница 46: ...14 15 Part No 95 607 367 Part No 95 607 425 16 18 19 21 Part No See table Part No See table...
Страница 47: ...22 23 24 Part No 95 605 192 95 605 194 Part No 95 605 103 25 26 Part No 7033371 Part No 95 612 650...
Страница 48: ...27 28 Part No 95 612 652 Part No 95 605 884 29 30 31 Part No 7031564 7031565 Part No 95 607 690...
Страница 49: ...32 33 Part No 95 607 691 Part No 95 980 025 34 35 36 Part No 95 980 009 Part No 95 607 366 95 607 404...
Страница 51: ...page 27 page 28 page 29 MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST...
Страница 52: ......
Страница 54: ......