9-6
9.5 Applicable Wires for PG Module
Applicable wire size, fastening screws and fastening torque for terminals are listed in the
table below. Select appropriate wires and screw in consideration of temperature rise caused
by the type of wires, wiring methods and wiring lengths.
Use a cable dedicated for the applicable devices.
Use a 1.25mm
2
twisted pair wire for connection to the terminal.
Table 9-3 Wiring Conditions for Terminals of PG Module
Terminal
Size
TB1: 0-49
TB2: 0-49
Wire [mm
2
]
1.25
Wire [AWG]
16
Terminal screw
M3
Fastening torque [N m]
0.5
– 0.75
Applicable pressure
terminal
FN 1.25 - 3 (JST Mfg. Co., Ltd.)
or TMEV 1.25
– 3
TMEV1.25Y-3S
TMEE1.25Y-3S
(Nichifu Terminal Industries Co.,
Ltd. or equivalent)
Note:
1. The specifications described in the table above indicate the terminal block for the PG
module (PS7XW-10080).
2. Make sure that the pressure terminal is suitable for the wire and UL/CSA certified. For
pressure terminal wiring, be sure to use the instrument of the specified terminal
manufacturer.