20
Settings
4.5. - Tmax S2
4.6. - Priority Storage 2
Switch-off temperature at sensor S2
If this value is exceeded at sensor 2 and the other conditions are also met, then the
controller switches the associated pump and/or valve off. If sensor 2 falls below this
value again and the other conditions are also met, then the controller switches the
pump and/or valve on again.
Priority of Storages S2
This determines the order, in which the storages are charged. If the same priority is set
for 2 storages, the charging is not switched over until charging the active storage is not
possible anymore.
Temperature values which are set high will allow higher solar heat
accumulation but it shall be checked that all system components are
resistant to high temperatures and scalding protection is provided.
Regulus solar thermal systems are safe for heating water up to 95 °C.
4.7. -
ΔT2
4.8. - Tmax S3
4.13. - Tmax pool
Settings see “4.4. - ΔT1”
Settings see “4.5. - Tmax S2”
Switch-off temperature at pool sensor
If this value is exceeded at the applicable sensor, the controller switches the associa-
ted pump and/or valve off. If the temperature falls below this value again and the other
conditions are also met, then the controller switches the pump and/or valve on again.
Temperature values that are set too high can lead to scalding or damage
to the system. Scalding protection must be provided by the customer!
Danger
Danger