19
Priority of Storages
This determines the order in which the storages are charged. If the same priority is set
for 2 storages, the charging is not switched over until charging the active storage is not
possible anymore.
4. - Settings
The system parameters are set in menu “4.
Settings”.
4.1. - Tmin S1
4.3. - Priority Storage 1
Sensor S1 switch-on temperature
If this value is exceeded at sensor 1 and the other conditions are also met, then the
controller switches the associated pump and/or valve on. If the temperature at sen-
sor 1 drops below this value by 5 °C, then the pump and/or the valve are switched off
again.
This does not under any circum-
stances replace the safety elements
to be provided by the customer!
Settings
Switch-on/switch-off temperature difference for solar heat:
If this temperature difference between the reference sensors is exceeded and the
other conditions are also met, then the controller switches the applicable relay on.
When the temperature drops to ΔT Off, then the relay is switched off.
4.4. -
ΔT1 / ΔT (pool)
If the set temperature difference is too small, this may result in ineffective
operation, depending on the system and sensor positions.Special switching
conditions apply for speed control (see 6.3. - Speed control R1)!
Warning
Caution
Caution
Various settings can be made depending on the selection of hydraulic
variant 1-27. The following pages contain generally valid descriptions for
the settings.
The menu is closed by pressing “esc” or selec-
ting “Exit settings”.
4.1. - Tmin S1