18
3. - Operating modes
In menu “3. Operating modes” the
controller can either be placed in
automatic mode, switched off, or placed in
a manual operating mode.
The menu is closed by pressing “esc” or
selecting “Exit operating modes”.
Automatic mode is the normal operating mode of the controller.
Only automatic mode provides proper controller function taking into account the
current temperatures and the parameters that have been set
3.1. - Automatic
Operating modes
3.2. - Manual
The relay and thus the connected pump, valve or heating rod are switched on and
off manually by pressing a key, with no regard to the current temperatures and the
parameters which have been set. The measured temperatures are also shown.
3.3. - Off
When the operating mode “Off” is activated, all controller functions are
switched off. This can lead, for example, to overheating of the solar
collector or other system components. The measured temperatures are
displayed even when the controller is Off.
The manual mode is intended to be used by a technician when
commissioning or checking the system. Activating manual mode in
current operation can lead to system damage or overheating of water in
the hot water storage tank!
Warning
Danger