3
│
Sentinel Kinetic Advance S, SX - www.regulus.eu
Installation Rules
1.The installer is responsible for the installation and electrical connection of the sentinel system on
site. It is the responsibility of the installer to ensure that the equipment is safely and securely
installed and left only when mechanically and electrically safe.
2. All regulations and requirements must be strictly followed to prevent hazards to life and property,
both during and after installation, and during any subsequent servicing and maintenance.
3. The unit’s condensate drain must be connected to the building’s wastewater drainage system.
4. Certain applications may require the installation of sound attenuation to achieve the sound levels
required.
5. The unit must not be connected directly to a tumble dryer.
6. The supply and exhaust valves must be fully opened prior to commissioning.
7. The intake air must be drawn from the exterior of the property.
8. The unit should be allowed to stabilise during commissioning for a minimum period of 5 minutes
when changing between boost and normal speeds.
9. Ensure that the unit’s external grilles (openings) are at least 1000mm apart. The exhaust grille
should be located at least 600mm away from any flue outlet. The inlet grille should be located at
least 2000mm away from any flue outlet.
10. This product and associated duct installation should be carried out in accordance with local rules.
Disposal
IMPORTANT INFORMATION ON PROPER DISPOSAL OF E-WASTE AS REQUIRED BY THE EC DIRECTIVE 2002/96/EC (WEEE)
Do not dispose of this product as unsorted municipal waste. Please dispose of this product by
returning it to the point of sale or to your local municipal collection point for recycling.
Respecting these rules will help to preserve, protect and improve the quality of the envi-
ronment, protect human health and utilize natural resources prudently and rationally.
The crossed out wheeled bin with marking bar, printed ether in the Manual or on the product
itself, identifies that the product must be disposed of at a recycling collection site.
WEEE Registration Number: 02771/07-ECZ