Sentinel Kinetic Advance S, SX  - www.regulus.eu

Contents

Warnings and Safety Information ................................................................... 2

Installation Guidance ................................................................................................................ 3

About this document ........................................................................................ 4

Contents ......................................................................................................................................... 4

Technical Data ................................................................................................... 5

Product Description ................................................................................................................... 5

Product Dimensions ................................................................................................................... 6 

Technical Specification .............................................................................................................. 7

Flow Rate settings ...................................................................................................................... 8

Summer Bypass Mode ............................................................................................................... 9

Accessories .................................................................................................................................. 10

Installation ...................................................................................................... 11

Overview ..................................................................................................................................... 11

Wall Mounting the Unit ........................................................................................................ 12

Floor Mounting the Unit ........................................................................................................ 13

Floor Mounting the Unit (Alternate Method) ............................................................... 14

Vertical Discharge Condensate Installation ..................................................................... 15

Attach the Ducting ................................................................................................................... 16

Electrical Installation ............................................................................................................... 17

Connect Switches and Sensors ............................................................................................ 18

Connect the Power Supply .................................................................................................. 20

Commissioning .............................,,,,,,,,,......................................................... 21

Powering up the Unit ............................................................................................................. 21

Overview ..................................................................................................................................... 21

Control Unit Touch Screen Display .................................................................................... 21

Modifying Settings .................................................................................................................. 22

Commissioning Screens Summary ................................................................................... 23

Modifying Commissioning Settings ................................................................................... 25

Operation and Monitoring ............................................................................ 34

Control Unit Screens Summary ........................................................................................... 34

User controls ............................................................................................................................. 36

Settings and Performance .................................................................................................... 37

Commissioning the Unit via USB ....................................................................................... 41

Default settings ......................................................................................................................... 42

Control via WiFi .......................................................................................................................... 43

Maintenance ................................................................................................... 45

Filter Maintenance ................................................................................................................... 45

Periodic Maintenance ............................................................................................................ 46

Spares ........................................................................................................................................... 47

Troubleshooting ............................................................................................. 48

Diagnosing a Problem .......................................................................................................... 48

Product fiche ............................................................................................................................. 51

Содержание 16487

Страница 1: ...www regulus eu SENTINEL KINETIC ADVANCE SENTINEL KINETIC ADVANCE EN Installation and Commissioning Instructions SENTINEL KINETIC ADVANCE S SX...

Страница 2: ...qualified person after completion 3 Ensure the mains supply voltage frequency and phase complies with the rating label 4 The unit should be provided with a local double pole fused spur fitted with a 3...

Страница 3: ...be allowed to stabilise during commissioning for a minimum period of 5 minutes when changing between boost and normal speeds 9 Ensure that the unit s external grilles openings are at least 1000mm apa...

Страница 4: ...rge Condensate Installation 15 Attach the Ducting 16 Electrical Installation 17 Connect Switches and Sensors 18 Connect the Power Supply 20 Commissioning 21 Powering up the Unit 21 Overview 21 Control...

Страница 5: ...ign concept provides significant energy recovery on household heat costs coupled with the optimum comfort conditions In addition a Kinetic Advance SX unit maintains a constant airflow independent of c...

Страница 6: ...inel Kinetic Advance S SX www regulus eu Product Dimensions Figure 2 Sentinel Kinetic Advance Dimensions Remove front cover see page 17 to view Rating label Label is positioned to the right of the con...

Страница 7: ...m3 h at 150 Pa Power AC Voltage Input 220 240 V AC single phase AC Frequency Input 50 Hz nominal Supply Fuse code 9532 Product Fuse 2 A located on main PCB Rated Power max 190 W Physical Height excl s...

Страница 8: ...ach mode is set independently and not defined by the mode name When setting up Over Pressure or Fireplace Mode the supply rate must be set higher than extract rate This is to provide a positive intern...

Страница 9: ...s will operate Indoor temp should be set 2 3 C higher than the central heating thermostat to prevent the bypass operating in winter and 2 3 C lower than any air conditioning thermostat if fitted Outdo...

Страница 10: ...ccessory The optional Switched Live LS expansion accessory offers two extra switched live inputs LS2 and LS3 for boosting via light switches 220 240V AC or Normal Boost switch This connection has the...

Страница 11: ...lified and competent person If the unit is wall mounted the wall should have sufficient strength to support the unit The unit may also be floor mounted either directly to the floor or using standard k...

Страница 12: ...to the wall bracket Ensure the bracket position is horizontal Step 2 Attach the wall bracket to the wall using appropriate fixings Step 3 Lift the unit and locate the two hooks on the rear onto the w...

Страница 13: ...the wall bracket is used in conjunction with any floor mount solution to prevent the unit from tipping Step 2 Mark the wall bracket position using the dimensions shown Note the position of the top of...

Страница 14: ...of the unit is horizontal in both axis The manufacturer recommends that where possible the wall bracket is used in conjunction with any floor mount solution to prevent the unit from tipping Step 4 Ma...

Страница 15: ...nditions occur outlet pipes must be insulated to avoid blockage by ice which may cause damage to the unit and surroundings This installation guide is for a Right Hand configured unit as specified on p...

Страница 16: ...nsate outlet Ensure the sealing gasket is fitted inside the blanking cap Attach the Ducting 1 Always use a short piece of insulated flexible duct maximum 150 mm long extended to its full length when c...

Страница 17: ...sliding it upwards and away from the unit Step 3 Remove the two screws on either side of the access panel Lift the panel outwards from the bottom edge to remove Note The access panel is tethered on th...

Страница 18: ...EMC engineering practice any sensor switched live or Volt free cables should not be installed within 50 mm of other cable or on the same metal cable tray as other cables Connect any switches or sensor...

Страница 19: ...ode Output A 5 V LED driving signal output between the and terminals that enables remote indication of a unit fault DIAG Diagnostic Diagnostic port USB USB Commissioning port LS1 Switched Live 220 240...

Страница 20: ...n the manner shown above Connect the other end of the cable via a 3A circuit breaker code 9532 Use cable clamps and clips to secure the cable as appropriate Connecting a Boost Light Switch A Switched...

Страница 21: ...the system is installed according to the system designers intent incorporating any acoustic ducting that all joints are air tight ducting is well supported bends are avoided close to vents and that th...

Страница 22: ...The user menu home screen consists of a User Mode LOW BOOST PURGE button a Machine status bar and a Settings Performance bar The Machine status scrolls through Mode of operation Summer bypass status...

Страница 23: ...following pages show all available settings within the commissioning menu Please note that some settings may not be available or may be in a different order due to pre configuration by your distribute...

Страница 24: ...24 Sentinel Kinetic Advance S SX www regulus eu...

Страница 25: ...Load USB Settings Settings can be automatically loaded to the unit via the USB port Note This option will only appear on the Quick Start sequence Access to this screen can be obtained by using the Re...

Страница 26: ...description of the unit handling Press to save and return to the commissioning menu Filter Check Select the time interval for checking the filters using the buttons on the screen between 1 month and...

Страница 27: ...ble Scroll through the settings using the buttons and select the mode pre set for each User mode Press to save and return to the commissioning menu User Mode Adjust the supply and extract airflows for...

Страница 28: ...iffer from image shown depending on unit specification Select the Port to view the Go To Mode speed setting Delay and Over run parameters Select the parameters to edit them Scroll through the settings...

Страница 29: ...he buttons on the screen Outdoor Temperature The outdoor temperature is the minimum air temperature that the bypass will permit This is to prevent cold draughts Change the indoor temperature using the...

Страница 30: ...elative humidity setback feature suppresses nuisance tripping as humidity gradually increases with falling temperature Go to Mode Scroll through the settings using the buttons and select the required...

Страница 31: ...balanced mode must also be used when a combustion device without a dedicated air supply is present Airflow Imbalanced Airflow mode reduces the Intake flow and increases the Extract flow in varying pr...

Страница 32: ...the buttons and select the Go To mode for each Schedule Days Scroll through the days of the week using the buttons and select each day to be included in the Schedule program Time Span Adjust the start...

Страница 33: ...ory and will be retained irrespective of mains supply breaks however the unit can also be restored back to factory defaults at this screen Press EXIT to return to the User Menu Home screen To complete...

Страница 34: ...Screens Summary The following Control Unit screens are available for daily operation and monitoring of the unit Refer to installation and Commissioning guide for further information on these settings...

Страница 35: ...35 Sentinel Kinetic Advance S SX www regulus eu Control Unit Screens Summary The following Control Unit screens are available in the Settings Performance section...

Страница 36: ...oll through the pre defined user modes factory defaults are BOOST LOW and PURGE using the buttons either side of the User Mode button Select the required function by pressing the centre button When a...

Страница 37: ...Menu Diagnostics Days Run and Filter check are reported values and do not have editable parameters in this section Performance The performance menu shows key performance indicators such as recovered...

Страница 38: ...ES Press LATER to return to the Settings Menu Display Settings Change the brightness of the touch screen using the buttons Summer Bypass See page 9 for a full description of the Summer Bypass modes an...

Страница 39: ...he buttons and select the Go To mode Note Number of available modes may differ from image shown depending on bypass setting and the modes set in the commissioning process Mode Scheduling Use a schedul...

Страница 40: ...speed up above the set Maximum Mode Silent Hours can be set to reoccur on specific days and times Service Phone The service phone number can be entered by the installer and should be used if the unit...

Страница 41: ...ing the Unit via USB When carrying out commissioning on multiple similar installations commissioned settings may be downloaded and saved onto a USB at the end of the setup routine see page 34 They can...

Страница 42: ...oint 70 Control Mode Normal Frost Protection Airflow Mode Mode schedule 1 All days set to 0 00 on 00 00 off inactive Mode schedule 2 All days set to 0 00 on 00 00 off inactive Service Phone Not Set Se...

Страница 43: ...devices equipped with Bluetooth 4 0 and running Android 4 3 Jelly Bean or later Follow the instructions in the App to connect with the WiFi unit UNDERSTANDING THE PRODUCT LABEL AP SSID The name of the...

Страница 44: ...ent Axia support for further assistance Solid Purple Network controller update mode Should not appear in normal operation Solid Red Communications fault between mainboard and WiFi controller Slow Flas...

Страница 45: ...hrough The rate at which the filters become dirty will vary hugely depending on the environment and the activity within the property See page 47 for a list of spare filters 1 Open the filter drawers b...

Страница 46: ...he heat exchanger out from the unit Step 4 Wash the outer cover and heat exchanger in warm water using a mild detergent and dry thoroughly NOTE Keep water away from all electrical components and wirin...

Страница 47: ...47 Sentinel Kinetic Advance S SX www regulus eu Spares The following spare parts may be ordered from the manufacturer Under preparation...

Страница 48: ...tance contact the service provider and quote the fault code number and the product serial number which can be found behind the front cover Note that the fault code is not displayed until the fault has...

Страница 49: ...49 Sentinel Kinetic Advance S SX www regulus eu This page is intentionally blank and can be used for making notes regarding the product fiche...

Страница 50: ...50 Sentinel Kinetic Advance S SX www regulus eu This page is intentionally blank and can be used for making notes regarding the product fiche...

Страница 51: ...trol Factor CTRL 0 65 Control Typology Local Demand Control Declared Max Internal External Leakage Rates 5 Internal 5 External Mixing Rate of Non Ducted BVUs not intended to be equipped with one duct...

Страница 52: ...cted during operation that are set by the Installation and Commissioning Instructions generally binding regulations or technical standards and shown on the product itself The warranty especially does...