41
│
Sentinel Kinetic Advance S, SX - www.regulus.eu
Diagnostics
Scroll through the Diagnostics list using the
buttons to access the following information.
Machine Status, Days Run, Filter Check, Bypass,
Energy Consumption, Air flows, Option boards.
Input status, Output Status, WiFi Status, WiFi
signal.
Note: Optional upgrades may be necessary to view
all information.
&
Commissioning the Unit via USB
When carrying out commissioning on multiple similar installations, commissioned settings may be
downloaded and saved onto a USB at the end of the setup routine (see page 34). They can then be
uploaded onto subsequent units saving time on site. The option to upload the settings is available at
the beginning of the commissioning quick start menu (see page 25).
No two systems are exactly the same and the settings and flow rates at each installation should be verified.
The USB does not have to be blank however only the most recent file will be read.