P33CE-11 Direct Vent Gas Fireplace
|
27
installation
Termination Cap
Wall Thimble 2 pieces
(10" (254mm) Outer Diameter)
2” x 4” or 2” x 6”
(21mm x 102mm
or 21mm x 152mm)
6-7/8"
(175mm)
dia. air intake
4" (102mm)
dia. flue pipe
with spring spacer
Screws
(4 per connection)
Screws
(3 per
connection)
Outside
Wall
Mur extérieur
Furring
Strips
Fourrures en bois
Furstrp.eps
see also c34020a.eps
furstrpf.eps
french
Installation Procedures
for Regency
®
Direct Vent System (Flex)
Minimum and Maximum Vent Clearances
1)
Locate the unit in the framing, rough in the gas
(preferably on the right side of the unit) and the
electrical (Junction block is on the left side) on
the left. Locate the centerline of the termination
and mark wall accordingly. Cut a 10"(254mm)
hole in the wall (inside dimension).
Note: To make the installation more
a e s t h e t i c a l ly p l e a s i n g , w e
recommend framing out a square
to mount the terminal to.
*
If this is an outside corner, the minimum distance between the vent and the outside
corner is 6" (15cm) with
AstroCap
termination cap or 12" (30cm) with Dura-Vent ter-
mination cap. See "F" in the diagram in "Exterior Vent Termination Locations" Section.
Note: A 2-1/2" (64mm) horizontal top and
1-1/2" (38mm) horizontal sides &
bottom clearance around the liner
must be maintained except that only
a 1" (25mm) clearance is needed at
the termination end. We recommend
framing a 10"(254mm) x 10"(254mm)
(inside dimensions) hole to give
structural rigidity for mounting the
termination.
Note: If installing termination on a siding
covered wall, furring strips must be
used to ensure that the termination
is not recessed into the siding.
2)
Level the fireplace and fasten it to the framing
using nails or screws through the nailing strips.
3)
Assemble the vent assembly by applying
Mill Pac to the 4"(100mm) inner collar of the
termination and slipping the 4"(100mm) liner
over it at least 1-3/8" (35mm). Fasten with the
3 screws (drilling pilot holes will make this
easier). Apply Mill Pac to the 6-7/8"(175mm)
flex pipe and slip it over the 6-7/8" outer collar
of the vent terminal at least 1-3/8"(35mm) and
fasten with the 3 screws.
4)
Separate the 2 halves of the wall thimble and
securely fasten the one with the tabs to the
outside wall making sure that the tabs are on
top and bottom. Fasten the other thimble half
to the inside wall. The thimble halves slip inside
each other and can be adjusted for 2 x 4 or 2 x
6 walls.
The liners must slip over the collars
a minimum of 1-3/8".
5)
Slip the assembled liner and termination as-
sembly through the thimble making sure the
termination cap faces up (there are markings
on the cap that show which way is up). This will
position the termination cap with proper down
slope for draining water. Fasten the cap to the
outer wall with the 4 supplied screws.
6)
Pull the centre 4"(100mm) liner and outer
6-7/8"(175mm) liner out enough to slip over
the flue collars of the fireplace.
7)
Apply Mill Pac over the fireplace inner collar
and slip the 4"(100mm) liner down over it and
attach with 3 supplied screws.
8)
Do the same with the 6-7/8"(175mm) liner.
9)
Apply a bead of silicone between the thimble
and termination and around the outer edge of
the terminal at the wall in order to keep the
water out.
IMPORTANT: Do not locate termination
hood where excessive snow or ice
buildup may occur. Be sure to check
vent termination area after snow falls,
and clear to prevent accidental blockage
of venting system. When using snow
blowers, make sure snow is not directed
towards vent termination area.