Regency
®
P33 Gas Log Fireplace
20
Horizontal Flueing with Three (3) 90
o
Elbows
Option V
H V + V1 H + H1
Min. Max. Min. Max.
A)
0.6m
0.3m
0.9m
1.2m
B)
0.9m
0.6m
1.2m
1.5m
C)
1.2m
0.9m
1.8m
1.8m
D)
1.5m
1.2m
2.4m
2.1m
E)
1.8m
1.5m
3m
2.4m
F)
2.1m
1.8m
3.65m 2.7m
With these options,
max. total pipe length
is 30 feet with min. of
12 feet total vertical
and max. 9 feet total
horizontal.
Please note min. 1
foot between 90
o
elbows is required.
Vertical Flueing with Two (2) 90
o
Elbows
Option V
H
V + V1
Min. Max. Min
A) 0.3m
1.2m
0.6m
B)
0.6m
1.5m
0.9m
C)
0.9m
1.8m
1.2m
D)
1.2m
2.1m
1.5m
E)
1.5m
2.4m
1.8m
Vertical Flueing with Two (2) 90
o
Elbows
With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and max.
8 feet total horizontal.
Please note min. 1 foot
between 90
o
elbows is re-
quired.
Option H + H1 V
Max. Min.
A)
0.6m
0.6m
B)
0.9m
0.9m
C)
1.2m
1.2m
D)
1.5m
1.5m
E)
1.8m
1.8m
With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and max.
6 feet total horizontal.
Please note min. 1 foot
between 90
o
elbows is
required.
INSTALLATION
One 90
o
elbow = Two 45
o
elbows.
One 90
o
elbow = Two 45
o
elbows.
One 90
o
elbow = Two 45
o
elbows.
For additional vertical fl ueing
with 2 x 90
o
elbows, see
"Vertical Terminations" sections.