AERATION
SETTING
The air shutter can be adjusted by moving the
adjusting wire up or down. The burner aeration
is factory set but may need adjusting due to
either the local gas supply or altitude.
Minimum Air Shutter Opening:
NG
12.7mm
LPG
12.7mm
ULPG
Fully
Open
CAUTION: Carbon will be produced if air shutter
is closed too much.
Closed - Tall yellow
Open - Short blue
OPERATING INSTRUCTIONS
SHUTDOWN
PROCEDURE
1)
Use the wall switch, thermostat or remote
control to turn off the main burner.
2)
Turn the main gas control clockwise to the
"OFF" position to turn off the pilot.
3)
Turn off all electric power to appliance if
service is to be performed.
FIRST FIRE
The fi rst fi re in your fi replace is part of the
paint curing process. To ensure that the paint
is properly cured, it is recommended that you
burn your fi replace for at least four (4) hours
the fi rst time you use it with the fan on.
When fi rst operated, the unit will release
an odour caused by the curing of the paint,
the burning off of any oils remaining from
manufacturing. Smoke detectors in the house
may go off at this time. Open a few windows to
ventilate the room for a couple of hours.
The glass panel may require cleaning after the
unit has cooled down.
DO NOT ATTEMPT TO
CLEAN THE GLASS WHILE IT IS HOT.
Note: When the glass is cold and the
appliance is lit, it may cause
condensation and fog the glass.
This condensation is normal and
will disappear in a few minutes as
the glass heats up.
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
During the fi rst few fi res, a white fi lm
may develop on the glass front as part
of the curing process. The glass should
be cleaned or the fi lm will bake on and
become very diffi cult to remove. Use a
non-abrasive cleaner and NEVER clean
the glass while it is hot.
OPERATING
INSTRUCTIONS
1)
Read and understand these instructions
before operating this appliance.
2)
Check to see that all wiring is correct and
enclosed to prevent possible shock.
3)
Check to ensure there are no gas leaks.
4)
Make sure the glass in the door frame is
properly positioned. Never operate the
appliance with the glass removed.
5)
Verify that the flueing and cap are
unobstructed.
6)
Ensure that the brick panels are installed.
7)
Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
8)
The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
LIGHTING PROCEDURE
IMPORTANT: Gas on/off knob cannot be
turned from "PILOT" to "OFF" unless it is
partially depressed.
1)
Turn burner OFF using "ON/OFF" switch.
2)
Turn gas control knob so indicator points
to "OFF" position and allow 5 minutes for
any gas in the combustion chamber to
escape.
3)
Push in control knob all the way and hold in
until the pilot lights up. Continue to hold the
control knob in for about 20 seconds after
the pilot is lit. Release knob.
4)
When the pilot stays lit, turn the gas knob
further counterclockwise to the "ON"
position.
5)
Use the wall switch, thermostat or remote
control to turn on the unit.
6)
Rotate
the
fl ame height regulator to adjust
the fl ame height higher or lower.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
Note: Aeration Adjustment should only be
performed by an authorized Regency
®
Installer at the time of installation or
service.
Adjustment Wire: push to close
or pull to open aeration cap
wire
Air
shutter