P33 Gas Log Fireplace
7
COMBUSTIBLE MANTELS
INSTALLATION
WARNING
Fire hazard is an extreme risk if
these clearances are not ahered to.
Clearances for Bay or Flush Front
Because of the extreme heat this fi replace emits, the mantel clearances are critical.
Combustible mantel clearances from top of unit are shown in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing
is made of metal studs covered with a non-combustible board.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram below:
This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded
area or higher using the above scale.
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the
paint may discolour.
CLEARANCES
The clearances listed below are Minimum distances
unless otherwise stated:
A major cause of chimney related fi res is failure
to maintain required clearances (air space)
to combustible materials. It is of the greatest
importance that this fi replace and fl ue system
be installed only in accordance with these
instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0" (0mm)
NOTE: The minimum fl oor clearance must be main-
tained from the top surface of the carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel*
min. 7" (177mm)
Ceiling
30" from top of unit (762mm)
Side Wall Clearance
Bay or Flush Front
7-1/2"
(191mm)
Minimum Flue Clearances:
2-1/2" (64mm) Horizontal Top
1-1/2" (38mm) Horizontal Side
1-1/2" (38mm) Horizontal Bottom
1-1/4" (32mm) Vertical Flue Clearance (Simpson)
1-1/2" (38mm) Vertical Flue Clearance (Flex)
Alcove Clearances:
Max. Depth
36"
(914mm)
Min. Width
48"
(1219mm)
Min. Height
59"
(1499mm)
* see mantel clearance instructions.
Maximum
1-1/2" (38mm) projection
at 2" (51mm) minimum
clearance.
The
HeatWave
Duct Kit has different
clearance and framing requirements,
check the
HeatWave
manual for details.