Controller 

 

 

 

12 —  English  

Reflexomat Basic — 20.09.2020 - Rev. A 

 

 

 

8.1.3

 

Stop mode 

Use: 
For device commissioning. 

 

Start: 
Press "Stop" on the controller. The Auto LED at the operator panel extinguishes. 

 

Functions: 
Except for the display of information, the device is non-functional in Stop mode. 
Function monitoring is stopped. 
The following functions are deactivated: 
• 

The "CO" compressor is switched off. 

• 

The solenoid valve in the "PV" overflow line is closed. 

• 

The solenoid valve in the "WV" make-up line is closed. 

 

 

Note! 
The system returns an alarm if the Stop mode is activated for more than 
4 hours. 
If "Floating alarm contact?" in the Customer menu is set to "Yes", the 
system outputs the alarm to the group alarm contact. 

 

9

 

Controller 

9.1

 

Operator panel 

 

 

Error LED 
• 

The Error LED illuminates in the event of a fault 

Display 

Auto LED 
• 

The Auto LED illuminates green in Automatic mode 

• 

The Auto LED flashes green in Manual mode  

• 

The Auto LED is not illuminated when the system is stopped 

OK 
• 

Confirm actions 

Stop 
• 

For commissioning and entry of new values in the controller 

"Back" to the previous menu 

Manual 
• 

For tests and maintenance tasks 

Auto 
• 

For continuous operation 

"Forward" to the next menu 

10 

Menu 
• 

Call up the Customer menu 

11 

Quit 
• 

Acknowledge messages 

 
Selecting and changing parameters 
1. 

Use "OK" (5) to select the parameter. 

2. 

Use the "

" (7) or "

" (9) arrow keys to change the parameter. 

3. 

Use "OK" (5) to confirm the parameter. 

4. 

Use the "

" (7) or "

" (9) arrow keys to switch to a different menu 

option. 

5. 

Use "Quit" (11) to switch to a different menu level. 

 

9.2

 

Configuring settings in the controller 

You can configure the controller settings regardless of the currently selected and 
active operating mode. 
 
System-specific values can be corrected via the customer menu. In the course of 
initial commissioning, the factory settings must first be adjusted for the system-
specific conditions. 

 

 

Note! 
For a description of the operation, see chapter 9.1 "Operator panel" on 
page 12 . 

 
All grey marked menu items must be reviewed during commissioning. 
 
Press "Manual" to switch to manual operation. 
Press "Menu" to display the first main menu option "Customer menu". 
 

Indication on the 
display 

Meaning 

Customer menu 

Switch to the next main menu option. 

Language 

Standard software in various languages. 

Time: 

Adjust the "Hour", "Minute", and "Second" display when 
each begins to flash. 
This time is used for entries in the fault memory. 

Date: 

Adjust the "Day", "Month", and "Year" display when each 
begins to flash. 
This date is used for entries in the fault memory. 

1 % / 1.7 bar 
Null balancing? 

The controller checks whether the level sensor signal 
matches the value entered for the "RG" primary vessel in 
the controller, see chapter 7.3 "Modifying the controller's 
start routine"
 on page 10 . 

 

Note! 
The "RG" primary vessel must be completely 
empty. 

 

0 % / 0 bar 
Null balancing 
successfully 
concluded! 

One of the following messages appears on the display: 
• 

Null balancing concluded successfully 

Confirm with the "

" button. 

• 

Empty vessel and repeat the process 

Confirm with "OK". 

0 % / 0 bar 
Cancel null 
balancing? 
No 

This message appears when null balancing has failed. 
Select "Yes" or "No" on the display. 
• 

YES: The "RG" primary vessel is empty and the 
device is installed as per the instructions. If null 
balancing is still not possible, cancel with "Yes". 
Contact your Reflex Customer Service. 

• 

NO: Check the prerequisites for the commissioning, 
see chapter 7.1 "Checking the requirements for 
commissioning"
 on page 10 . 
The controller's start routine has been restarted. 

Confirm the selection of "yes" or "no" with "OK". 

Min.op.pressure 
01.8 bar 

Enter the value for the minimum operating pressure. 

 

Note! 
Calculation of minimum operating pressure, see 
chapter 7.2 "Reflexomat switching points" on 
page 10 . 

 

Make-up 

Switch to the "Make-up" main menu. 
• 

Press "OK" to open the menu. 

• 

Use the "

▼▲

" buttons to open the sub-menu. 

Make-up: ON 
at: 08 % 

If the water content is below the specified vessel size, 
add water, see chapter 7.3 "Modifying the controller's 
start routine"
 on page 10 . 
• 

If an automatic make-up device (Fillcontrol for 
example) is installed, make-up will be actuated 
automatically; otherwise the make-up must be 
manually activated. 

Содержание Reflexomat Basic RS 90 / 1

Страница 1: ...20 09 2020 Rev A Reflexomat Basic GB Operating manual Original operating manual Reflexomat RS 90 1 mounted Reflexomat external air...

Страница 2: ...5 Fitting the level sensor 8 6 4 Make up and degassing variants 8 6 4 1 Function 8 6 5 Electrical connection 9 6 5 1 Terminal diagram 9 6 5 2 RS 485 interface 9 6 6 Installation and commissioning cert...

Страница 3: ...observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe th...

Страница 4: ...or SV Safety valve PV Solenoid valve LIS Pressure load cell EC Expansion pipe Expansion vessels One primary vessel and multiple optional secondary vessels may be connected A membrane separates the ves...

Страница 5: ...otection IP 54 Noise level 72 dB Electric output 750 W Power supply 230 V 50 Hz Fusing 3 A Electrical voltage control unit 230 V 2 A Number of RS 485 interfaces 1 Weight 21 kg Permissible operating te...

Страница 6: ...eing stressed or strained If necessary provide support structures for the pipes or equipment For installation proceed as follows Position the device Complete the primary tank and the optional secondar...

Страница 7: ...cables are factory installed on the primary vessel The cables between the primary vessel and the control unit are pre installed Subsequently install the level sensor at the primary vessel see chapter...

Страница 8: ...ontroller s customer menu the external make up is activated 6 4 1 1 Make up without pump Reflexomat Basic with solenoid valve and ball valve 1 Reflexomat Basic WC Make up pipe 2 Solenoid valve Fillval...

Страница 9: ...ke up request Not used with the Reflexomat 17 Make up 230 V 18 Make up 230 V 19 PE shield Level analogue input Display at the controller Activation of the make up Factory prepared sensor plug must be...

Страница 10: ...n in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus excluded 7 3 Modifying the controller s start routine Note During commissioni...

Страница 11: ...e up pressure at least 1 3 bar above the set minimum pressure P0 Without automatic make up Use the discharge ports or the facility system to manually fill the individual tank to approximately 30 of th...

Страница 12: ...ey marked menu items must be reviewed during commissioning Press Manual to switch to manual operation Press Menu to display the first main menu option Customer menu Indication on the display Meaning C...

Страница 13: ...oftening used and the specified hardness reduction Fillsoft I soft water capacity 6000 hardness red l Fillsoft II soft water capacity 12000 hardness red l Enter the value in the controller Consult the...

Страница 14: ...ed Note Floating contacts setting in the Customer menu see chapter 9 2 Configuring settings in the controller on page 12 ER Code Alarm Floating contact Causes Remedy Alarm reset 01 Minimum pressure YE...

Страница 15: ...een option card and controller faulty Option card defective Inform Reflex Customer Service 31 EEPROM defective YES EEPROM defective Internal calculation error Inform Reflex Customer Service Quit 32 Un...

Страница 16: ...ended closing Checking Insufficient water Off 14 Check the displayed value for the Insufficient water OFF filling level message Insufficient water Off is displayed at the controller at a minimum filli...

Страница 17: ...ified by the operating company based on a safety evaluation taking into consideration the actual operating conditions experience with the mode of operation and charging material and the applicable nat...

Страница 18: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 19: ...SI2041enA 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: