Reflex Reflexomat Basic RS 90 / 1 Скачать руководство пользователя страница 15

 

Maintenance 

 

 

 

Reflexomat Basic — 20.09.2020 - Rev. A 

 

English  — 15 

 

ER 

Code 

Alarm 

Floating 

contact 

Causes 

Remedy 

Alarm reset 

08 

Pressure measurement 

YES 

Controller receives incorrect signal. 

• 

Connect the plug. 

• 

Check functioning of the pressure 
sensor. 

• 

Check the cable for damage. 

• 

Check the pressure sensor. 

"Quit" 

09 

Level sensor 

YES 

Controller receives incorrect signal. 

• 

Check functioning of the load cell. 

• 

Check the cable for damage. 

• 

Connect the plug. 

"Quit" 

10 

Maximum pressure 

• 

Set value exceeded. 

• 

Pressure relief pipe not functioning. 

• 

Dirt trap clogged. 

• 

Check set value in the Customer or 
Service menu. 

• 

Check functioning of the pressure relief 
pipe. 

• 

Clean the dirt trap. 

"Quit" 

11 

Make-up volume 

"With water meter" must be activated in the 
Customer menu. 
• 

Set value exceeded. 

• 

Severe water loss in the system. 

• 

Check set value in the Customer or 
Service menu. 

• 

Check water loss in the system and 
repair, if necessary. 

"Quit" 

15 

Make-up valve 

Contact water meter measures without 
make-up request. 

Check the make-up valve for leaks. 

"Quit" 

16 

Power failure 

No power. 

Connect to power supply. 

19 

Stop 

˃

 4 hours 

Device is in Stop mode for more than 4 
hours. 

Set the controller to Automatic mode. 

20 

Max. make-up volume 

Set value exceeded. 

Reset the "Make-up volume" meter in the 
Customer menu. 

"Quit" 

21 

Maintenance recommended  - 

Set value exceeded. 

Perform maintenance and reset the 
maintenance counter upon completion. 

"Quit" 

24 

Softening 

• 

Set value for soft water capacity 
exceeded. 

• 

Time interval for replacement of the 
softening cartridge exceeded. 

Replace the softening cartridges. 

"Quit" 

30 

I/O module fault 

• 

I/O module defective. 

• 

Connection between option card and 
controller faulty. 

• 

Option card defective. 

Inform Reflex Customer Service. 

31 

EEPROM defective 

YES 

• 

EEPROM defective. 

• 

Internal calculation error. 

Inform Reflex Customer Service. 
 

"Quit" 

32 

Undervoltage 

YES 

Supply voltage not achieved. 

Check power supply. 

33 

Adjustment parameter 
faulty 

EEPROM parameter memory defective.

 

Inform Reflex Customer Service. 

34 

Communication 
Main board faulty 

• 

Connecting cable defective. 

• 

Main board defective. 

Inform Reflex Customer Service. 

35 

Digital input voltage 
faulty 

Short-circuit of input voltage. 

Check the wiring at the digital inputs (water 
meter, for example). 

36 

Analogue input voltage 
faulty 

Short-circuit of input voltage. 

Check the wiring at the analogue inputs 
(pressure/level). 

 
 

 

10

 

Maintenance 

 CAUTION 

 

Risk of burns 
Escaping hot medium can cause burns. 
• 

Maintain a sufficient distance from the escaping medium. 

• 

Wear suitable personal protective equipment (safety gloves and 
goggles). 

 

 DANGER 

 

Risk of serious injury or death due to electric shock. 
If live parts are touched, there is risk of life-threatening injuries. 
• 

Ensure that the system is voltage-free before installing the device. 

• 

Ensure that the system is secured and cannot be reactivated by other 
persons. 

• 

Ensure that installation work for the electric connection of the device is 
carried out by an electrician, and in compliance with electrical 
engineering regulations. 

 

 
 

The device is to be maintained annually.  
–  

The maintenance intervals depend on the operating conditions and the 
degassing times. 

 
The annual maintenance is displayed upon expiry of the set operating time. Use 
"Quit" to acknowledge the "Maintenance recommended" message. Reset the 
maintenance counter in the Customer menu. 
 

 

Note! 
Arrange for maintenance tasks must be carried out only by specialist 
personnel or Reflex Customer Service. 

 

Содержание Reflexomat Basic RS 90 / 1

Страница 1: ...20 09 2020 Rev A Reflexomat Basic GB Operating manual Original operating manual Reflexomat RS 90 1 mounted Reflexomat external air...

Страница 2: ...5 Fitting the level sensor 8 6 4 Make up and degassing variants 8 6 4 1 Function 8 6 5 Electrical connection 9 6 5 1 Terminal diagram 9 6 5 2 RS 485 interface 9 6 6 Installation and commissioning cert...

Страница 3: ...observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe th...

Страница 4: ...or SV Safety valve PV Solenoid valve LIS Pressure load cell EC Expansion pipe Expansion vessels One primary vessel and multiple optional secondary vessels may be connected A membrane separates the ves...

Страница 5: ...otection IP 54 Noise level 72 dB Electric output 750 W Power supply 230 V 50 Hz Fusing 3 A Electrical voltage control unit 230 V 2 A Number of RS 485 interfaces 1 Weight 21 kg Permissible operating te...

Страница 6: ...eing stressed or strained If necessary provide support structures for the pipes or equipment For installation proceed as follows Position the device Complete the primary tank and the optional secondar...

Страница 7: ...cables are factory installed on the primary vessel The cables between the primary vessel and the control unit are pre installed Subsequently install the level sensor at the primary vessel see chapter...

Страница 8: ...ontroller s customer menu the external make up is activated 6 4 1 1 Make up without pump Reflexomat Basic with solenoid valve and ball valve 1 Reflexomat Basic WC Make up pipe 2 Solenoid valve Fillval...

Страница 9: ...ke up request Not used with the Reflexomat 17 Make up 230 V 18 Make up 230 V 19 PE shield Level analogue input Display at the controller Activation of the make up Factory prepared sensor plug must be...

Страница 10: ...n in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus excluded 7 3 Modifying the controller s start routine Note During commissioni...

Страница 11: ...e up pressure at least 1 3 bar above the set minimum pressure P0 Without automatic make up Use the discharge ports or the facility system to manually fill the individual tank to approximately 30 of th...

Страница 12: ...ey marked menu items must be reviewed during commissioning Press Manual to switch to manual operation Press Menu to display the first main menu option Customer menu Indication on the display Meaning C...

Страница 13: ...oftening used and the specified hardness reduction Fillsoft I soft water capacity 6000 hardness red l Fillsoft II soft water capacity 12000 hardness red l Enter the value in the controller Consult the...

Страница 14: ...ed Note Floating contacts setting in the Customer menu see chapter 9 2 Configuring settings in the controller on page 12 ER Code Alarm Floating contact Causes Remedy Alarm reset 01 Minimum pressure YE...

Страница 15: ...een option card and controller faulty Option card defective Inform Reflex Customer Service 31 EEPROM defective YES EEPROM defective Internal calculation error Inform Reflex Customer Service Quit 32 Un...

Страница 16: ...ended closing Checking Insufficient water Off 14 Check the displayed value for the Insufficient water OFF filling level message Insufficient water Off is displayed at the controller at a minimum filli...

Страница 17: ...ified by the operating company based on a safety evaluation taking into consideration the actual operating conditions experience with the mode of operation and charging material and the applicable nat...

Страница 18: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 19: ...SI2041enA 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: