Installation 

 

 

 

Reflexomat Basic — 20.09.2020 - Rev. A 

 

English  — 7 

 

 

ATTENTION 

 

Damage due to improper installation 
Additional device stresses may arise due to the connection of pipes or system 
equipment. 
• 

Ensure that pipes are connected from the device to the system without 
them being stressed or strained. 

• 

If necessary, provide support structures for the pipes or equipment. 

 

ATTENTION 

 

Damage to cables and pipes 
If cables and pipes are not routed professionally between tanks and the 
control unit, they may become damaged. 
• 

Route cables and pipes in a professional manner over the flooring. 

 
The following typical example describes the installation of the primary vessel 
with the attached control unit and the connection of two secondary vessels. 
Proceed accordingly for other installation variants. 

 

 

 

 

 

Expansion pipe 

 

SV  Safety valve 

Compressed air line 

 

PV  Solenoid valve 

Data line 

 

PIS  Pressure sensor 

RF  Secondary vessel 

 

AC  Compressed air line 

RG  Primary vessel 

 

EC 

Expansion pipe 

 
6.3.3.1

 

Water-side connection 

To ensure the proper function of the "LIS" level sensor, you must use the 
supplied hose to flexibly connect the primary vessel to the system. 
The "EC" expansion line provides secure locking and emptying for primary vessel 
and the optional secondary vessels. If more than one vessel is used, a collective 
line to the system is installed. 
Use points with temperatures between 0 °C and 70 °C to connect to the system. 
This is the return of the generator in heating systems and the flow in 
refrigeration systems.  
At temperatures below or above 0 °C – 70 °C, you must install in-line vessels 
between the system and the Reflexomat. 

 

 

Note! 
For details regarding the switching of Reflexomats or in-line vessels and 
the dimensions of the expansion lines, please see the planning 
documents. More information is also provided in the Reflex Planning 
Guide. 

 
6.3.3.2

 

Control unit connection 

• 

The "PV" solenoid valve, the "PIS" pressure transducer and the 
corresponding cables are factory-installed on the primary vessel. 

• 

The cables between the primary vessel and the control unit are pre-
installed. 

• 

Subsequently install the level sensor at the primary vessel, see 
chapter 6.3.5 "Fitting the level sensor" on page 8 .  
–  

The cable must be run through the assembly pipe on the rear of the 
primary vessel if it has not been pre-installed.  

• 

The flexible compressed air hose is connected with the control unit. Run 
the compressed air hose through the assembly pipe as well.  
–  

If you install only the primary vessel, you must connect the 
compressed air hose directly to the "AC" compressed air connection 
of the primary vessel. 

–  

If you install secondary vessels, you install first the supplied 
distributor at the compressed air connection of the primary vessel. 
• 

Use the supplied connection sets to connect the secondary 
vessels. 

 
6.3.4

 

Connection to an external compressed air line 

An external pressure supply can optionally be connected to the Reflexomat. 
When doing so it must be ensured that a pressure reducer is fitted in the external 
pressure line. The minimum pressure to be set depends on the relevant pressure 
rating of the vessel. 

 

 

 

Pressure reducer, site attachment 

  PIS 

Pressure sensor 

Dirt trap, site attachment 

  SV 

Safety valve 

Pressure gauge, site attachment 

  PV 

Overflow solenoid valve 

Solenoid valve, supplied by Reflex 

  LIS 

Level sensor 

 

Instead of the compressor, a solenoid valve is actuated in the external 
compressed air line, which releases the compressed air for the vessel. The 
solenoid valve is activated by the controller. The electrical connection of the 
solenoid valve is made via the terminal for the compressor in the respective 
controller. 
Properties of the external compressed air: 
• 

Quality 
–  

Fluid group 2 according to the Pressure Equipment Directive 2014 / 
68 EU. 

–  

DIN ISO 8573-1 Class 1. 

• 

Oil-free 
–  

ATTENTION Diaphragm damage caused by oil-containing 
compressed air. Keep the compressed air free of oil. 

• 

Compressed air 
–  

ATTENTION Damage to the vessel. The compressed air must be 
reduced to the respective vessel pressure rating. 

 

 

Note! 
See chapter "Terminal plan" for the solenoid valve electrical connection. 

 

Содержание Reflexomat Basic RS 90 / 1

Страница 1: ...20 09 2020 Rev A Reflexomat Basic GB Operating manual Original operating manual Reflexomat RS 90 1 mounted Reflexomat external air...

Страница 2: ...5 Fitting the level sensor 8 6 4 Make up and degassing variants 8 6 4 1 Function 8 6 5 Electrical connection 9 6 5 1 Terminal diagram 9 6 5 2 RS 485 interface 9 6 6 Installation and commissioning cert...

Страница 3: ...observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe th...

Страница 4: ...or SV Safety valve PV Solenoid valve LIS Pressure load cell EC Expansion pipe Expansion vessels One primary vessel and multiple optional secondary vessels may be connected A membrane separates the ves...

Страница 5: ...otection IP 54 Noise level 72 dB Electric output 750 W Power supply 230 V 50 Hz Fusing 3 A Electrical voltage control unit 230 V 2 A Number of RS 485 interfaces 1 Weight 21 kg Permissible operating te...

Страница 6: ...eing stressed or strained If necessary provide support structures for the pipes or equipment For installation proceed as follows Position the device Complete the primary tank and the optional secondar...

Страница 7: ...cables are factory installed on the primary vessel The cables between the primary vessel and the control unit are pre installed Subsequently install the level sensor at the primary vessel see chapter...

Страница 8: ...ontroller s customer menu the external make up is activated 6 4 1 1 Make up without pump Reflexomat Basic with solenoid valve and ball valve 1 Reflexomat Basic WC Make up pipe 2 Solenoid valve Fillval...

Страница 9: ...ke up request Not used with the Reflexomat 17 Make up 230 V 18 Make up 230 V 19 PE shield Level analogue input Display at the controller Activation of the make up Factory prepared sensor plug must be...

Страница 10: ...n in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus excluded 7 3 Modifying the controller s start routine Note During commissioni...

Страница 11: ...e up pressure at least 1 3 bar above the set minimum pressure P0 Without automatic make up Use the discharge ports or the facility system to manually fill the individual tank to approximately 30 of th...

Страница 12: ...ey marked menu items must be reviewed during commissioning Press Manual to switch to manual operation Press Menu to display the first main menu option Customer menu Indication on the display Meaning C...

Страница 13: ...oftening used and the specified hardness reduction Fillsoft I soft water capacity 6000 hardness red l Fillsoft II soft water capacity 12000 hardness red l Enter the value in the controller Consult the...

Страница 14: ...ed Note Floating contacts setting in the Customer menu see chapter 9 2 Configuring settings in the controller on page 12 ER Code Alarm Floating contact Causes Remedy Alarm reset 01 Minimum pressure YE...

Страница 15: ...een option card and controller faulty Option card defective Inform Reflex Customer Service 31 EEPROM defective YES EEPROM defective Internal calculation error Inform Reflex Customer Service Quit 32 Un...

Страница 16: ...ended closing Checking Insufficient water Off 14 Check the displayed value for the Insufficient water OFF filling level message Insufficient water Off is displayed at the controller at a minimum filli...

Страница 17: ...ified by the operating company based on a safety evaluation taking into consideration the actual operating conditions experience with the mode of operation and charging material and the applicable nat...

Страница 18: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 19: ...SI2041enA 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: