Reflex Reflexomat Basic RS 90 / 1 Скачать руководство пользователя страница 16

Maintenance 

 

 

 

16 —  English  

Reflexomat Basic — 20.09.2020 - Rev. A 

 

 

 

10.1

 

Maintenance schedule 

The maintenance schedule is a summary of maintenance tasks to be carried out 
regularly. 

 

Activity 

Ch

eck

 

W

ai

Clea

Interval 

Check for leaks. 
• 

"CO" compressor. 

• 

Screw connections of the 
compressed air connections. 

 

Annually 

Check switching points. 
• 

Switch on pressure "CO" 
compressor. 

• 

Insufficient water. 

• 

Make-up with water. 

 

 

Annually 

Clean "ST" dirt trap. 
–  

see chapter 10.3.2 "Cleaning the 
dirt trap"
 on page 17 . 

Depending on the 
operating 
conditions 

Remove condensate from the primary 
vessel and the secondary vessels, if 
applicable. 
–  

see chapter 10.3.1 "Cleaning the 
tanks"
 on page 16 . 

x  Annually 

 

10.2

 

Checking switching points 

Prerequisite for checking the switching points are the following correct settings: 
• 

Minimum operating pressure P

0

, see chapter 7.2 "Reflexomat switching 

points" on page 10 . 

• 

Level sensor at the primary vessel. 

 
Preparation 
1. 

Switch to Automatic mode. 

2. 

Close the cap valves upstream of the vessels. 

3. 

Record the displayed filling level (value in %). 

4. 

Drain the water from the vessels. 

 
Check cut-in pressure 
5. 

Check the cut-in and cut-out pressure of the "CO" compressor. 
–  

The compressor cuts in at P

+ 0.3 bar. 

–  

The compressor cuts out at P

+ 0.4 bar. 

 

Check make-up "On" 
6. 

If necessary, check the make-up value displayed at the controller. 
–  

The automatic make-up is activated at a level display of 8 %. 

 
Checking Insufficient water "On" 
7. 

Switch off the water make-up and continue to drain the water from the 
vessels. 

8. 

Check the displayed value for the "Insufficient water" filling level message. 
–  

Insufficient water "On" is displayed at the controller at a minimum 
filling level of 5 %. 

9. 

Switch to Stop mode. 

10.  Switch off the main switch. 
 
Cleaning the vessels 
If necessary, remove condensate from the vessels, see chapter 10.3.1 "Cleaning 
the tanks" o
n page 16 . 

 

Activating the device 
11.  Switch on the main switch. 
12.  Switch to Automatic mode. 

–  

Depending on the filling level and pressure, the "CO" compressor and 
the automatic make-up will be switched on. 

13.  Slowly open the cap valves upstream of the vessels and secure them 

against unintended closing.  

 
Checking Insufficient water "Off" 
14.  Check the displayed value for the Insufficient water "OFF" filling level 

message. 
–  

Insufficient water "Off" is displayed at the controller at a minimum 
filling level of 8 %. 

 

Check make-up "Off" 
15.  If necessary, check the make-up value displayed at the controller. 

–  

The automatic make-up is deactivated at a level display of 12 %. 

 

Maintenance is completed. 

 

 

Note! 
If no automatic make-up is connected, manually fill the vessels with 
water up to the noted level. 

 

 

Note! 
The setting values for pressurisation, filling levels and make-up can be 
found in the chapter Default settings, see chapter 9.2.1 "Default 
settings"
 on page 13 . 

 

10.3

 

Cleaning 

10.3.1

 

Cleaning the tanks 

 CAUTION 

 

Risk of injury due to pressurised liquid 
Injuries can occur during maintenance work if the connections have been 
installed incorrectly because condensate under pressure can suddenly 
escape. 
• 

Ensure proper connections for the draining of condensate. 

• 

Wear suitable personal protective equipment (safety gloves and safety 
goggles, for example). 

 
Regularly clean the vessels to remove condensate. The cleaning intervals depend 
on the local operational conditions. 
 
Vessels with replaceable diaphragm 
1. 

Close the cap valve in front of the vessels. 

2. 

Record the displayed level value at the controller and empty the vessel of 
water and compressed air. 

3. 

Switch off the main switch and withdraw the mains plug. 

4. 

Open the drain taps at the vessels and drain the condensate. 
–  

If more than 5 litres of water or condensate are discharged, you must 
check the vessel. 
• 

Check the diaphragm for rupture. 

• 

Check the vessel interior walls for corrosion damage. 

 

 CAUTION – Risk of injury caused by escaping pressurised liquid. 

Injuries can occur during maintenance work if the connections have been 
installed incorrectly because condensate under pressure can suddenly 
escape. 

5. 

Close the vessels' drain taps. 

6. 

Connect the mains plug and switch on the main switch.  

7. 

Open the cap valve of the vessels and secure against unauthorised 
"closing". 

8. 

Fill water and compressed air into the vessels until the recorded level value 
is reached. 

Maintenance is completed. 

 

 

Note! 
Check the installation location of the vessels for sufficient ventilation if 
the vessel interior wall are damaged by corrosion, see chapter 6.2 
"Preparatory work"
 on page 6 

.

 

 

Содержание Reflexomat Basic RS 90 / 1

Страница 1: ...20 09 2020 Rev A Reflexomat Basic GB Operating manual Original operating manual Reflexomat RS 90 1 mounted Reflexomat external air...

Страница 2: ...5 Fitting the level sensor 8 6 4 Make up and degassing variants 8 6 4 1 Function 8 6 5 Electrical connection 9 6 5 1 Terminal diagram 9 6 5 2 RS 485 interface 9 6 6 Installation and commissioning cert...

Страница 3: ...observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe th...

Страница 4: ...or SV Safety valve PV Solenoid valve LIS Pressure load cell EC Expansion pipe Expansion vessels One primary vessel and multiple optional secondary vessels may be connected A membrane separates the ves...

Страница 5: ...otection IP 54 Noise level 72 dB Electric output 750 W Power supply 230 V 50 Hz Fusing 3 A Electrical voltage control unit 230 V 2 A Number of RS 485 interfaces 1 Weight 21 kg Permissible operating te...

Страница 6: ...eing stressed or strained If necessary provide support structures for the pipes or equipment For installation proceed as follows Position the device Complete the primary tank and the optional secondar...

Страница 7: ...cables are factory installed on the primary vessel The cables between the primary vessel and the control unit are pre installed Subsequently install the level sensor at the primary vessel see chapter...

Страница 8: ...ontroller s customer menu the external make up is activated 6 4 1 1 Make up without pump Reflexomat Basic with solenoid valve and ball valve 1 Reflexomat Basic WC Make up pipe 2 Solenoid valve Fillval...

Страница 9: ...ke up request Not used with the Reflexomat 17 Make up 230 V 18 Make up 230 V 19 PE shield Level analogue input Display at the controller Activation of the make up Factory prepared sensor plug must be...

Страница 10: ...n in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus excluded 7 3 Modifying the controller s start routine Note During commissioni...

Страница 11: ...e up pressure at least 1 3 bar above the set minimum pressure P0 Without automatic make up Use the discharge ports or the facility system to manually fill the individual tank to approximately 30 of th...

Страница 12: ...ey marked menu items must be reviewed during commissioning Press Manual to switch to manual operation Press Menu to display the first main menu option Customer menu Indication on the display Meaning C...

Страница 13: ...oftening used and the specified hardness reduction Fillsoft I soft water capacity 6000 hardness red l Fillsoft II soft water capacity 12000 hardness red l Enter the value in the controller Consult the...

Страница 14: ...ed Note Floating contacts setting in the Customer menu see chapter 9 2 Configuring settings in the controller on page 12 ER Code Alarm Floating contact Causes Remedy Alarm reset 01 Minimum pressure YE...

Страница 15: ...een option card and controller faulty Option card defective Inform Reflex Customer Service 31 EEPROM defective YES EEPROM defective Internal calculation error Inform Reflex Customer Service Quit 32 Un...

Страница 16: ...ended closing Checking Insufficient water Off 14 Check the displayed value for the Insufficient water OFF filling level message Insufficient water Off is displayed at the controller at a minimum filli...

Страница 17: ...ified by the operating company based on a safety evaluation taking into consideration the actual operating conditions experience with the mode of operation and charging material and the applicable nat...

Страница 18: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 19: ...SI2041enA 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: