Reflex Reflexomat Basic RS 90 / 1 Скачать руководство пользователя страница 1

20.09.2020 - Rev. A 

Reflexomat Basic 

 

GB 

Operating manual 

Original operating manual 

Reflexomat RS 90 / 1 - mounted 

Reflexomat - external air

Содержание Reflexomat Basic RS 90 / 1

Страница 1: ...20 09 2020 Rev A Reflexomat Basic GB Operating manual Original operating manual Reflexomat RS 90 1 mounted Reflexomat external air...

Страница 2: ...5 Fitting the level sensor 8 6 4 Make up and degassing variants 8 6 4 1 Function 8 6 5 Electrical connection 9 6 5 1 Terminal diagram 9 6 5 2 RS 485 interface 9 6 6 Installation and commissioning cert...

Страница 3: ...observe the safety information can result in death or severe irreversible injuries CAUTION Damage to health The sign in combination with the signal word Caution indicates danger failure to observe th...

Страница 4: ...or SV Safety valve PV Solenoid valve LIS Pressure load cell EC Expansion pipe Expansion vessels One primary vessel and multiple optional secondary vessels may be connected A membrane separates the ves...

Страница 5: ...otection IP 54 Noise level 72 dB Electric output 750 W Power supply 230 V 50 Hz Fusing 3 A Electrical voltage control unit 230 V 2 A Number of RS 485 interfaces 1 Weight 21 kg Permissible operating te...

Страница 6: ...eing stressed or strained If necessary provide support structures for the pipes or equipment For installation proceed as follows Position the device Complete the primary tank and the optional secondar...

Страница 7: ...cables are factory installed on the primary vessel The cables between the primary vessel and the control unit are pre installed Subsequently install the level sensor at the primary vessel see chapter...

Страница 8: ...ontroller s customer menu the external make up is activated 6 4 1 1 Make up without pump Reflexomat Basic with solenoid valve and ball valve 1 Reflexomat Basic WC Make up pipe 2 Solenoid valve Fillval...

Страница 9: ...ke up request Not used with the Reflexomat 17 Make up 230 V 18 Make up 230 V 19 PE shield Level analogue input Display at the controller Activation of the make up Factory prepared sensor plug must be...

Страница 10: ...n in extreme cases Note Avoid dropping below the P0 minimum operating pressure Vacuum vaporisation and cavitation are thus excluded 7 3 Modifying the controller s start routine Note During commissioni...

Страница 11: ...e up pressure at least 1 3 bar above the set minimum pressure P0 Without automatic make up Use the discharge ports or the facility system to manually fill the individual tank to approximately 30 of th...

Страница 12: ...ey marked menu items must be reviewed during commissioning Press Manual to switch to manual operation Press Menu to display the first main menu option Customer menu Indication on the display Meaning C...

Страница 13: ...oftening used and the specified hardness reduction Fillsoft I soft water capacity 6000 hardness red l Fillsoft II soft water capacity 12000 hardness red l Enter the value in the controller Consult the...

Страница 14: ...ed Note Floating contacts setting in the Customer menu see chapter 9 2 Configuring settings in the controller on page 12 ER Code Alarm Floating contact Causes Remedy Alarm reset 01 Minimum pressure YE...

Страница 15: ...een option card and controller faulty Option card defective Inform Reflex Customer Service 31 EEPROM defective YES EEPROM defective Internal calculation error Inform Reflex Customer Service Quit 32 Un...

Страница 16: ...ended closing Checking Insufficient water Off 14 Check the displayed value for the Insufficient water OFF filling level message Insufficient water Off is displayed at the controller at a minimum filli...

Страница 17: ...ified by the operating company based on a safety evaluation taking into consideration the actual operating conditions experience with the mode of operation and charging material and the applicable nat...

Страница 18: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Страница 19: ...SI2041enA 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...