Controller
12 — English
Reflexomat Basic — 20.09.2020 - Rev. A
8.1.3
Stop mode
Use:
For device commissioning.
Start:
Press "Stop" on the controller. The Auto LED at the operator panel extinguishes.
Functions:
Except for the display of information, the device is non-functional in Stop mode.
Function monitoring is stopped.
The following functions are deactivated:
•
The "CO" compressor is switched off.
•
The solenoid valve in the "PV" overflow line is closed.
•
The solenoid valve in the "WV" make-up line is closed.
Note!
The system returns an alarm if the Stop mode is activated for more than
4 hours.
If "Floating alarm contact?" in the Customer menu is set to "Yes", the
system outputs the alarm to the group alarm contact.
9
Controller
9.1
Operator panel
1
Error LED
•
The Error LED illuminates in the event of a fault
2
Display
3
Auto LED
•
The Auto LED illuminates green in Automatic mode
•
The Auto LED flashes green in Manual mode
•
The Auto LED is not illuminated when the system is stopped
4
OK
•
Confirm actions
5
Stop
•
For commissioning and entry of new values in the controller
6
"Back" to the previous menu
7
Manual
•
For tests and maintenance tasks
8
Auto
•
For continuous operation
9
"Forward" to the next menu
10
Menu
•
Call up the Customer menu
11
Quit
•
Acknowledge messages
Selecting and changing parameters
1.
Use "OK" (5) to select the parameter.
2.
Use the "
▼
" (7) or "
▲
" (9) arrow keys to change the parameter.
3.
Use "OK" (5) to confirm the parameter.
4.
Use the "
▼
" (7) or "
▲
" (9) arrow keys to switch to a different menu
option.
5.
Use "Quit" (11) to switch to a different menu level.
9.2
Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and
active operating mode.
System-specific values can be corrected via the customer menu. In the course of
initial commissioning, the factory settings must first be adjusted for the system-
specific conditions.
Note!
For a description of the operation, see chapter 9.1 "Operator panel" on
page 12 .
All grey marked menu items must be reviewed during commissioning.
Press "Manual" to switch to manual operation.
Press "Menu" to display the first main menu option "Customer menu".
Indication on the
display
Meaning
Customer menu
Switch to the next main menu option.
Language
Standard software in various languages.
Time:
Adjust the "Hour", "Minute", and "Second" display when
each begins to flash.
This time is used for entries in the fault memory.
Date:
Adjust the "Day", "Month", and "Year" display when each
begins to flash.
This date is used for entries in the fault memory.
1 % / 1.7 bar
Null balancing?
The controller checks whether the level sensor signal
matches the value entered for the "RG" primary vessel in
the controller, see chapter 7.3 "Modifying the controller's
start routine" on page 10 .
Note!
The "RG" primary vessel must be completely
empty.
0 % / 0 bar
Null balancing
successfully
concluded!
One of the following messages appears on the display:
•
Null balancing concluded successfully
Confirm with the "
▼
" button.
•
Empty vessel and repeat the process
Confirm with "OK".
0 % / 0 bar
Cancel null
balancing?
No
This message appears when null balancing has failed.
Select "Yes" or "No" on the display.
•
YES: The "RG" primary vessel is empty and the
device is installed as per the instructions. If null
balancing is still not possible, cancel with "Yes".
Contact your Reflex Customer Service.
•
NO: Check the prerequisites for the commissioning,
see chapter 7.1 "Checking the requirements for
commissioning" on page 10 .
The controller's start routine has been restarted.
Confirm the selection of "yes" or "no" with "OK".
Min.op.pressure
01.8 bar
Enter the value for the minimum operating pressure.
Note!
Calculation of minimum operating pressure, see
chapter 7.2 "Reflexomat switching points" on
page 10 .
Make-up
Switch to the "Make-up" main menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
Make-up: ON
at: 08 %
If the water content is below the specified vessel size,
add water, see chapter 7.3 "Modifying the controller's
start routine" on page 10 .
•
If an automatic make-up device (Fillcontrol for
example) is installed, make-up will be actuated
automatically; otherwise the make-up must be
manually activated.