Controller
44 — English
Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B
9.2.2
Service menu
The Service menu is password-protected. Only Reflex service technicians are able to access this menu, see chapter 12.1 "Reflex Customer
Service" on page 53 .
Parameter
Setting
Remarks
Pressurisation
Pump "ON"
P
0
+ 0.3 bar
Differential pressured added to the "P
0
" minimum operating
pressure
Pump "OFF"
P
0
+ 0.4 bar
Differential pressured added to the "P
0
" minimum operating
pressure
Forced start of the pumps
24 h
If the pumps are standing still for 24 hours, they are forced to run
for 3 seconds
"Pump run time exceeded" message
30 minutes
The message is displayed after the pumps run for 30 minutes
Maximum pressure
6 bar
Degassing, active only in Fillcontrol Auto 2PS
Degassing
P
0
+ 0.4 bar
Differential pressured added to the "P
0
" minimum operating
pressure
Degassing time of interval degassing mode
90 seconds
Idling time of interval degassing mode
120 minutes
Interval degassing start
08:00 h
Interval degassing end
18:00 h