Commissioning
Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B
English — 31
7.4
Modifying the controller's start routine
The start routine is used to set the required parameters for the device commissioning. It commences with the first activation of the
controller and can be run only once. Parameters can be changed or checked in the customer menu after the start routine has terminated,
see chapter 9.2.1 "Customer menu" on page 43 .
1. Establish a 230 V power supply by plugging the power plug into a corresponding outlet.
2. Press "Stop" on the controller's operator panel.
– You are in Stop mode. The "Auto" LED on the operator panel has extinguished.
Device name
Fillcontrol Auto xxx
Standard software in various languages.
Language
1. Prior to commissioning, read the entire operating manual and verify the proper
assembly.
Read the operating manual!
2. Enter the value for the minimum operating pressure "P
0
".
– For calculating the minimum operating pressure, see chapter 7.2 "Determining
minimum operating pressure for the controller" on page 29 .
Min. op. pressure
3. Enter the value for the release pressure of the safety valve.
– This value may be the same as the release pressure of the facility system safety
valve.
Safety valve pressure
4. Change the flashing display items for "Hour", "Minute", and "Seconds" to the current
time.
•
The time of an alarm will be stored in the fault memory of the controller.
Time
5. Change the flashing display items for "Day", "Month", and "Year" to the current date.
•
The date of an alarm will be stored in the fault memory of the controller.
Date
The system displays this message after a successfully completed start routine:
6. Select either "Yes" or "No" and confirm with "OK" on the controller operator panel.
Terminate routine?
YES
– YES: The start routine is terminated, the device switches to Stop mode.
– NO: The start routine restarts.
The pressure is displayed.
2.0 bar
STOP
Note!
After successful conclusion of the start routine, you are in Stop mode.
– Do not yet switch to Automatic mode.
7.5
Parametrising the controller in the Customer menu
Use the Customer menu to display or correct system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
– For adjusting the default settings, see chapter 9.2 "Configuring settings in the controller" on page 40 .
– For information about controller operation, see chapter 9.1 "Operator panel" on page 39 .