Controller
40 — English
Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B
9.2
Configuring settings in the controller
Use the Customer menu to display or correct system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
For a description of the operation, see chapter 9.1 "Operator panel" on page 39 .
Proceed as follows:
All grey marked menu items must be reviewed during commissioning.
Press "Manual" to switch to manual operation.
Press "Menu" to display the first main menu option "Customer menu".
Switch to the next main menu option.
Customer menu
,
Standard software in various languages.
Language
Adjust the "Hour", "Minute", and "Second" display when each begins to flash.
This time is used for entries in the fault memory.
Time:
This date is used for entries in the fault memory.
Adjust the "Day", "Month", and "Year" display when each begins to flash.
Date:
Berechnung P
0,
see chapter 7.2 "Determining the P
minimum operating pressure for the
controller" on page 29 .
Min. op. pressure
Specify the tripping pressure of the applicable safety valve for the device protection. This is
usually the safety valve at the system heat generator.
Safety valve pressure
Note!
The following degassing settings apply only to Fillcontrol Auto 2PS.
– Degassing settings are not required for Fillcontrol Auto 2P.
Switch to the "Degassing" sub-menu.
Degassing
Switch to the next list item.
Degassing
Select from 2 degassing programmes:
•Continuous degassing
•Interval degassing
Degassing programme
Time setting for Continuous degassing.
– Depends on the facility volume and the glycol content, if required.
Time Continuous. degas.