9.5.4
Gateway Settings
Click
Gateway Configuration ->
Gateway Settings
in the main menu to display this
screen. Use the Gateway Settings screen to view and modify processing and forwarding
data from the serial ports to the Ethernet interface.
Fig. 82: Connect Gateway - Serial Gateway [1,2] Settings Screen
Serial Gateway [1,2] Settings
Gateway Mode
: Select the mode of operation for this gateway.
Inactive
: This port is not active. Settings are not displayed.
Raw TCP Server
: The port protocol is basic TCP.
Modbus TCP Server
: The port protocol is MODBUS over TCP.
COM Port Binding
: Select the port for this gateway (Unassigned, DATA 1, DATA 2).
Unassigned
: The gateway is not active.
DATA1
: The gateway is assigned to port DATA1.
DATA2
: The gateway is assigned to port DATA2.
Serial Gateway [1,2] Data Packing
Packet length
: Enter the Ethernet packet length (up to 1024) when packing serial data.
Force Transmit (msec)
: Enter the maximum time period (0-65535 milliseconds) to
collect serial data before forwarding the data over the Ethernet port. This function can be
used to aggregate serial data and forward it over the TCP/IP in a single Ethernet frame.
The buffered data is forwarded immediately if the receive data buffer reaches maximum
capacity (1 KB).