2-INSTALLATION
12
CONNECTION OF THE SMOKE EXHAUST DUCT
When making the hole for the passage of the smoke discharge pipe, one must take into account the possible presence of flammable
materials. If the hole must be made through a wooden wall or thermolabile material, the
INSTALLER MUST
first of all use the appropriate
wall fitting (minimum diameter 13 cm) and suitably insulate the pipe of the product that passes through it using adequate insulating
materials (1.3 - 5 cm thick with minimum thermal conductivity 0.07 W/m°K).
The same minimum distance must be applied if the pipe of the product must pass through vertical or horizontal sections near the
thermolabile wall.
It is recommended to use an insulated double-wall pipe in external sections in order to prevent condensation from forming.
The combustion chamber works in negative pressure.
REAR VIEW OF A PELLET STOVE (EXAMPLE)
1) SMOKE OUTLET
2) COMBUSTION AIR INLET