6-PROBLEMS/CAUSES/SOLUTIONS
ANOMALY
LED
POSSIBLE CAUSES
SOLUTIONS
The product
indicates that
the pellet hopper
temperature
exceeds the safety
threshold.
Led 0
Pellet load is excessive.
Wait for the product to cool down, restart it and
decrease the pellet load.
Room fan power is too low.
Wait for the product to cool down, restart it and
increase the fan power via knob A.
The door is not closed properly or the
gaskets are worn.
Close the door or replace the gaskets with original
ones.
The combustion chamber is dirty.
Clean the combustion chamber.
Clogged outlet.
Clean the smoke duct.
Faulty or malfunctioning pressure switch.
Replace the pressure switch.
The structure overheats due to reduced
heat dissipation.
Verify the correct position of the product.
Increase the smoke fan speed in accordance
with the technical manual.
Faulty room fan.
Replace the room fan.
The product
indicates that
the smoke fan
is operating
abnormally.
Led +1 Fan rotation is obstructed.
Verify what the obstruction is.
Faulty smoke fan.
Replace the faulty component.
The product
indicates the smoke
temperature is too
high or the smoke
probe is faulty.
Led +2
Pellet load is excessive.
Decrease the pellet load.
Unsuitable pellets.
Empty the hopper from the unsuitable pellets and
replace them with those recommended by the
manufacturer.
Room fan power is too low.
Increase the fan speed via knob A.
The structure overheats due to reduced
heat dissipation.
Verify the correct position of the product.
Faulty room fan.
Replace the faulty component.
Faulty smoke probe.
Replace the faulty component.
Clogged smoke outlet.
Clean the smoke exhaust.