18 CIRCULATOR PUMPS CURVES
19 READING OF THE INDOOR UNIT MANOMETERS
Each indoor unit is equipped with two manometers.
The
differ
ence between the manometers (1 and 2) reading can be used as approximate value
for verifying the water
fl
ow rate/pressure head when the unit works on the plant (so when the
3-way valve diverts the
flo
w to the l
eft
side on the line A).
To the
differ
ence of manometers value you should subtract the pressure drop of the 3-way
valve for ge
tti
ng an approximate value of the available pressure head of the plant.
The characteri
stic
curve corresponding to the Head pressure versus Water
fl
ow rate of the
three-way diverter valve, whose values should be deducted at the manometric readings for
verifying with
suffici
ent accuracy the available sta
ti
c pressure of the plant system at the
nominal opera
ting
points marked in the curves of Chapter 17.
It is recommended for safety to remove an
additiona
l 5% from the obtained values.
mod. US 06 E- US 09 E
mod. US 12 E- US 16 E