EN
14
P.63
Protocollo variant
-
1
2
1
1 = Standard
2 = Special
P.70 Minimum
temperature
curve
killing Legionella
°C 50 62 50
See
section
3.3
P.71
Killing time at minimum
temperature
min 1
250 240
See
section
3.3
P.72
Average temperature curve killing
Legionella
°C 55 69 55
See
section
3.3
P.73
Killing time at average
temperature
min 1
250 120
See
section
3.3
P.74
Istantaneous temperature curve
killing Legionella
°C 65 75 65
See
section
3.3
P.80
Offset tank temperature probe
°C
-10.0 10.0
0.0
Correction to be applyed to
tank temperature probe
P.81
Offset recirculation temperature
probe
°C
-10.0 10.0
0.0
Correction to be applyed to
recirculation temperature
probe
P.82
Enabling logging derivative alarm
-
0
1
0
0 = Derivative alarm disabled
1 = Derivative alarm enabled
P.98
% using electrical resistor
%
0
100
-
Read only. Shows the using
power percent of the resistor
P.99
Default data
-
0
1
0
Set to 1 to carry default data.
Содержание DHW
Страница 2: ......
Страница 10: ...EN 8 1 7 WIRING DIAGRAM ...
Страница 22: ......
Страница 30: ...IT 28 1 7 SCHEMA COLLEGAMENTO ELETTRICO ...
Страница 42: ......
Страница 43: ......
Страница 44: ...FAG0FC001AB 00 12 2018 bit ly rdzwebsite ...