3.4 ANTI-FREEZE MANAGEMENT
If the control unit is turned on in the standby state, it is possible to activate the anti-freeze function (parametro
P.02). If the water temperature in the tank falls below 5.0 °C, the control unit activates all available heat sources
until the temperature rises above 10 °C.
3.5 HEAT PUMP ALARM
When the 230 Vac alarm/defrost contact from the heat pump is activated (in case it is connected to the control unit),
if the control unit is in demand, the resistance is turned on immediately, or if the resistance is already on, it is
increased Of one step the power of resistance.
When the alarm contact is switched off, the resistance goes off or is lowered by a step.
3.6 SMART ENERGY
Coming soon.