Operation mode
-
0
4
2
0 = OFF: Heating OFF (but
protections ON)
1 = ECO: Only heat pump
2 = SMART: Heat pump plus
integration resistor if the pump
is not enough
3 = FAST: Heat pump + resistor
together active
4 = BACKUP: Only resistor
P.22
SMART ENERGY enabling
-
0
1
0
0 = OFF
1 = ON
See section
3.6 SMART ENERGY
P.50
Network frequency settings
-
0
1
0
0 = 50 Hz
1 = 60 Hz
P.51
Recirculation settings
-
0
3
1
0 = OFF
1 = ON 10% - OFF 90%
2 = % ON based on recirculation
NTC probe
3 = MAX
See section
3.2
P.52
PWM recirculation timing
min
1
60
2
Recirculation pump activation
time if P.51 = 1 or 2.
See section
3.2
P.53
Minimum derivative recirculation
temperature
°C 0 20 5
Minimum
recirculation
temperature increase in 60
min. See section
3.2
P.54
Max storage tank temperature
°C
30
90
85
P.55
Min storage tank temperature
°C
0
15
5
P.56 Heat
Pump
maximum
temperature
°C
40
58
50
Maximum temperature at
which the heat pump can carry
the tank . Beyond this
temperature the heat pump is
switched off and only the
electrical resistance is used (if
P.20
≠
0 and
≠
1)
P.57 Tank
temperature
regulation
hysteresis
°C 1 30 17
See
section
3.1
P.58
Minimum derivative tank
temperature
°C
1.0
20.0
5.0
Minimum tank temperature
increase in 60 min.
P.59
Derivative control timing
min
1
120
30
Derivative control timing for
minimum derivative (P.58).
Note: For the first 30 minutes
of the heating cycle the
derivative is not checked .
See section
3.1
P.60
BPS bus RS485 (9600-19200-
115200)
- 1 3 1
P.61
Network adress Bus 485
-
0
255
1
P.62
Network Protocol
-
1
3
1
1 = MODBUS slave
2 = MODBUS master
3 = SACBUS (owner)