2.3 PARAMETERS SETUP
USER ACCESS:
Press the "SET" button for a brief moment to access the level 1 parameters
TECHNICAL ACCESS:
Press the “SET” button for 2 seconds (access the Password entry page);
Use “UP” and “DOWN” to select characters, use “SET” to confirm the actual character
and place the cursor at the next position. Insert password “8 3 9”
Now accesses the device's configuration parameters, which change depending on access level.
Parameters settings procedure:
•
To scroll the parameter list press “UP” or “DOWN”.
•
To enter in selected parameter press one time “SET”. The display shows the parameter value.
•
To modify the selected parameter hold “SET” for 2 seconds. The parameter value start blinking.
•
Press “UP” or “DOWN” to set value.
•
Press “SET” to confirm the setting or “ON-OFF” to restore original value. The display stops blinking. If no button
pressed for 2 minutes, the unit restore the original value and display stops
•
Press “ON-OFF” to return at parameter list.
•
Press “ON-OFF” to return to menu level 0 (ON state).
•
If the uniti s in menu page level livello 1 or 2, in the parameter list and no button pressed for 2 minutes,
automatically return to level 0 (Main screen).
2.4 PARAMETER TABLE
Nr PARAMETER
UNIT
MIN
MAX
DEFAULT
STATE DESCRIPTION
P.01 Desired
tank
temperature
(SETPOINT)
°C 40 80 50
P.02 Anti-freeze
protection
enabling - 0
1
1
0 = Anti-freeze protection
disabled
1 = Anti-freeze protection
enabled
See section
3.4
P.03
Maximum power to electrical
resistor
-
1
4
1
1 = 25% 2 = 50%
3 = 75% 4 = 100%
P.04
Anti-legionella manual start
-
0
1
0
0 = Anti-legionella free
1 = Anti-legionella manual start.
This parameter resets to 0 after
starting cycle.
See section
2.7
P.05
Enter event list
-
-
-
-
See section
2.6
P.10
Clock: hour setting
-
0
23
-
P.11
Clock: minute setting
-
0
59
-
P.12
Clock: day of week setting
-
1
7
-
1 = Monday
…
7 = Sunday
P.13
Clock: day of month setting
-
0
31
-
P.14
Clock: month setting
-
1
12
-
P.15
Clock: year setting
-
00
99
-
P.16
Anti-legionella frequency
days
0
30
3
Minimum interval in days
between two anti-legionella
cycles.
Setting 0 disables Anti-
legionella cycles.