UM-1097
Revision B
100
Security
Unlock
N/A
40099 40099 N/A
3
6
This register must be written
with the Modbus® unlock
code before any parameter
can be written using function
codes 6 or 16. 0000 – 9999,
1234
Standard Relay 1
Type
Channel First
Last
Block
Size
Read
FC
Write
FC
Notes
A1 Votes
N/A
40100 40100 N/A
3
6, 16
Alarm 1 channels required. 0 -
16
A2 Votes
N/A
40101 40101 N/A
3
6, 16
Alarm 2 channels required. 0 –
16
A3 Votes
N/A
40102 40102 N/A
3
6, 16
Alarm 3 channels required. 0 -
16
Acknowledge N/A
40103 40103 N/A
3
6, 16
Relay is acknowledgeable. No
= 0, Yes = 1
Failsafe
N/A
40104 40104 N/A
3
6, 16
Relay is failsafe. No = 0, Yes =
1
Zone 1
Enable
N/A
40105 40105 N/A
3
6, 16
Use zone 1 channels for
voting. No = 0, Yes = 1
Zone 2
Enable
N/A
40106 40106 N/A
3
6, 16
Use zone 2 channels for
voting. No = 0, Yes = 1
Zone 3
Enable
N/A
40107 40107 N/A
3
6, 16
Use zone 3 channels for
voting. No = 0, Yes = 1
Содержание ViewSmart 1600+
Страница 75: ...UM 1097 Revision B 65 4 7 5 2 Channel Configuration Figure 45 Webpage Channel Configuration Menu...
Страница 77: ...UM 1097 Revision B 67 4 7 5 4 Programmable Relays Figure 47 Webpage Programmable Relays Menu...
Страница 78: ...UM 1097 Revision B 68 4 7 5 5 System Configuration Figure 48 Webpage System Configuration Menu...
Страница 134: ...UM 1097 Revision B 124 Appendix 4 Menu Navigation...
Страница 140: ...UM 1097 Revision B 130 Appendix 6 Ordering Information Main Assemblies Option and Replacement Boards...
Страница 141: ...UM 1097 Revision B 131 Wireless Options and Accessories Expansion Options...