UM-1097
Revision B
90
Coils
All coils are duplicated in the holding register table. These values can be read or written using either the
coil register or the holding register.
Actions
Alarm
Reset
N/A
1
1
N/A 1
5
Write 1 to simulate pressing the
alarm reset button
Save Config N/A
95
95
N/A 1
5
Saves configuration now
Config
Changed
N/A
96
96
N/A 1
5
This register is set to 1 when a
configuration parameter has
changed. The user can clear it by
writing 0.
Discrete Inputs
All discrete inputs are duplicated in the input register table. These values can be read using either discrete
register or the holding register.
Type
Channel First
Last
Block
Size
Read
FC
Write
FC
Notes
Lock Status N/A
112005 112005 N/A
2
N/A
Indicates the lock state for
Modbus® writes.
Locked = 1
Unlocked = 0
Standard
Relay 1
State
N/A
112020 112020 N/A
2
N/A
Off = 0, On = 1, doesn’t take
into account failsafe
Standard
Relay 2
State
N/A
112021 112021 N/A
2
N/A
Off = 0, On = 1, doesn’t take
into account failsafe
Содержание ViewSmart 1600+
Страница 75: ...UM 1097 Revision B 65 4 7 5 2 Channel Configuration Figure 45 Webpage Channel Configuration Menu...
Страница 77: ...UM 1097 Revision B 67 4 7 5 4 Programmable Relays Figure 47 Webpage Programmable Relays Menu...
Страница 78: ...UM 1097 Revision B 68 4 7 5 5 System Configuration Figure 48 Webpage System Configuration Menu...
Страница 134: ...UM 1097 Revision B 124 Appendix 4 Menu Navigation...
Страница 140: ...UM 1097 Revision B 130 Appendix 6 Ordering Information Main Assemblies Option and Replacement Boards...