UM-1097
Revision B
51
5.
Press Edit until the desired channel group is displayed
6.
Replace the PGM Jumper (J2)
7.
Press Next twice
8.
Press Edit to accept the changes, and reboot the controller
The Channel group LED should now be illuminated next to the desired channel group.
4.6.1
Optional Relays
4.6.1.1
Programmable Relays
Each Optional I/O board must be assigned to a channel group (either 1-8 or 9-16). The current channel
group a board is assigned to will be indicated at the top of the option board by a green LED. To change
the assigned channel group perform the following:
1.
Enter the Diagnostics Menu
a)
Press the Main Menu button
b)
Press the Up button to highlight Diagnostics
c)
Press Edit three times to enter the Diagnostics Menu
2.
Press Up to highlight I/O Board Config
3.
Press Edit
4.
Remove the PGM Jumper (J2) on the option board you wish to configure
5.
Press Edit until the desired channel group is displayed
6.
Replace the PGM Jumper (J2)
7.
Press Next twice
8.
Press Edit to accept the changes, and reboot the controller
The Channel group LED should now be illuminated next to the desired channel group.
4.6.1.2
A1 A2, A3 and Fault Votes Required
A1 Votes Required, A2 Votes Required, A3 Votes Required and Fault Votes Required are the number of
A1, A2, A3 and Fault level alarms that must be present for the relay to activate. This allows creation of
logical AND function equations that control standard relays. Default settings for standard relay 1 are A1
Votes = 01 A2 Votes = 00 & A3 Votes = 00 which causes relay 1 to trip if any channel has an A1 level alarm
active. Default settings for standard relay 2 are A1 Votes = 00 A2 Votes = 01 & A3 Votes = 00 which causes
relay 2 to trip if any channel has an A2 level alarm active. Example: If either default setting is modified
such that A1 Votes = 02 and A2 Votes = 01, then any two channels must have an A1 level alarm active and
any one channel must have an A2 level alarm active to trip that relay.
REMEMBER!
One of the A1s and the A2 could be on the same channel. These level alarms must come
from a channel included in the Zone entry described below.
Содержание ViewSmart 1600+
Страница 75: ...UM 1097 Revision B 65 4 7 5 2 Channel Configuration Figure 45 Webpage Channel Configuration Menu...
Страница 77: ...UM 1097 Revision B 67 4 7 5 4 Programmable Relays Figure 47 Webpage Programmable Relays Menu...
Страница 78: ...UM 1097 Revision B 68 4 7 5 5 System Configuration Figure 48 Webpage System Configuration Menu...
Страница 134: ...UM 1097 Revision B 124 Appendix 4 Menu Navigation...
Страница 140: ...UM 1097 Revision B 130 Appendix 6 Ordering Information Main Assemblies Option and Replacement Boards...
Страница 141: ...UM 1097 Revision B 131 Wireless Options and Accessories Expansion Options...